Cases and Evaporators Part 1

Cases and Evaporators Part 1

Assessment

Flashcard

Other

Professional Development

Practice Problem

Hard

Created by

Wayground Content

FREE Resource

Student preview

quiz-placeholder

6 questions

Show all answers

1.

FLASHCARD QUESTION

Front

Using the pressure temperature chart, calculate the superheat for this evaporator. Suction line temperature is 12﮿ F and suction pressure is 26 PSIG.

Media Image

Back

8° superheat

2.

FLASHCARD QUESTION

Front

Store Dewpoint needs to be 52° or less so that case operation and defrost are operating efficiently. True or False?

Back

True

3.

FLASHCARD QUESTION

Front

You walk into a store and there is heavy moisture on the Low Temperature glass doors. You check the rack receiver level first.

Back

False

4.

FLASHCARD QUESTION

Front

Before checking and/or adjusting case superheat, ensure the case is turned off.

Back

False

5.

FLASHCARD QUESTION

Front

When measuring superheat on an evaporator always use the Dew Point scale on the PT chart.

Back

True

6.

FLASHCARD QUESTION

Front

It takes patience to adjust superheat correctly. Always allow the evaporator suction temperature to bottom out 3 cycles before getting the average superheat number and then make a small adjustment. Repeat cycle.

Back

True

Access all questions and much more by creating a free account

Create resources

Host any resource

Get auto-graded reports

Google

Continue with Google

Email

Continue with Email

Classlink

Continue with Classlink

Clever

Continue with Clever

or continue with

Microsoft

Microsoft

Apple

Apple

Others

Others

Already have an account?