Cable calculations
Presentation
•
Construction
•
Vocational training
•
Practice Problem
•
Hard
Dave Pugh
FREE Resource
33 Slides • 21 Questions
1
2
3
Open Ended
Describe a situation where choosing the wrong cable size could lead to problems in an electrical installation.
4
Multiple Choice
Why is it important to select the correct size of electrical cable for an installation?
To ensure safety and prevent overheating
To reduce the cost of installation
To make the installation process faster
To use up leftover cable stock
5
6
Multiple Choice
Which of the following best describes the relationship needed to achieve coordination between the load, circuit conductor, and overload protective device?
Ib ≤ In ≤ Iz
Ib ≥ In ≥ Iz
Ib = In = Iz
Ib > In < Iz
7
8
Open Ended
List the steps involved in determining the correct cable size for an electrical installation.
9
10
Multiple Choice
What is the formula used to calculate the design current (Ib) of a circuit?
Ib = VP
Ib = PV
Ib = P×V
Ib = IV
11
12
Fill in the Blanks
If a single-phase load has a power of 1.7kW and operates at 230V, what is the design current (Ib)?
13
14
15
Multiple Choice
Which of the following combinations of power and voltage results in a design current (Ib) of 13.04A?
3000W, 230V
6500W, 230V
10kW, 230V
1700W, 230V
16
Fill in the Blanks
Calculate the design current (Ib) for a load of 6500W at 230V.
17
18
Multiple Choice
According to Stage 2, what must be true about the protective device rating (In) compared to the design current (Ib)?
In must be less than Ib
In must be equal to Ib
In must be greater than or equal to Ib
In must be double Ib
19
20
Multiple Choice
Using the information from Appendix B, what is the maximum measured earth fault loop impedance (in Ω) for a BS EN 60898 16A Type B circuit-breaker?
1.16 Ω
1.09 Ω
2.2 Ω
1.75 Ω
21
22
23
Fill in the Blanks
What are the correct protective device ratings (in amperes) for the following design currents: 13.04A, 28.26A, and 43.47A, as shown in the work examples?
24
Multiple Choice
Based on the work examples, match the following protective devices to their corresponding design currents: 60898 Type B Circuit Breaker, Semi-enclosed Fuse - BS 3036, BS 88 High Rupturing Capacity Fuse.
13.04A, 28.26A, 43.47A
16A, 30A, 50A
10A, 25A, 40A
13.04A, 30A, 50A
25
26
Open Ended
Explain how the rating factors (Ca, Ci, Cg, Cf) identified in Stage 3 can affect the selection of cable size in an electrical installation.
27
28
Multiple Choice
According to Table F1, what is the rating factor (Ca) for a cable with 70°C thermoplastic insulation at an ambient temperature of 35°C?
1.03
0.94
0.87
1.00
29
30
Multiple Choice
According to Table F2, what is the derating factor for a cable surrounded by 400mm of thermal insulation?
0.88
0.51
0.63
0.78
31
32
Multiple Choice
Which arrangement and number of cables in Table F3 results in the lowest rating factor for current-carrying capacity?
Bunched in air, 12 cables
Single layer on wall, 1 cable
Single layer multicore on tray, 3 cables
Single layer multicore on ladder, 5 cables
33
34
35
36
Multiple Select
Which of the following factors are considered in the formula for calculating the cable rating (Iz) as shown in Stage 4?
Ambient temperature factor (Ca)
Thermal insulation factor (Ci)
Grouping factor (Cg)
Cable length factor (Cl)
37
38
Fill in the Blanks
Calculate the minimum cable rating (Iz) required for a circuit with a nominal current (In) of 30A, using the rating factor 0.79 as shown in the work examples.
39
40
41
42
43
Multiple Choice
According to Table F4(i), what is the maximum current-carrying capacity (in amperes) for a 16 mm² conductor using Reference Method C (clipped direct)?
87 A
76 A
61 A
79 A
44
45
46
47
48
49
50
51
52
53
Multiple Choice
Which of the following is an important reason for referring to relevant codes of practice and standards when selecting cables?
To ensure safety and compliance in electrical installations
To reduce the cost of cables
To increase the length of the cable run
To avoid using any insulation
54
Open Ended
What are the key principles to consider when selecting the right size of cable for an electrical installation?
Show answer
Auto Play
Slide 1 / 54
SLIDE
Similar Resources on Wayground
50 questions
Design Cable Capacity
Presentation
•
KG - University
49 questions
Present tenses Review
Presentation
•
Professional Development
48 questions
Curriculum Reforms in SL
Presentation
•
Professional Development
51 questions
At the coffee shop
Presentation
•
Professional Development
48 questions
PRACTICE TO PERFECT
Presentation
•
Professional Development
49 questions
5.18
Presentation
•
KG
46 questions
4.25 - Lesson
Presentation
•
KG
48 questions
STEAM Deadliest Animal
Presentation
•
KG - Professional Dev...
Popular Resources on Wayground
6 questions
PRIDE Always and Everywhere
Presentation
•
12th Grade
20 questions
Lab Safety Quiz
Quiz
•
6th Grade
26 questions
KOR Review Kahoot Questions
Quiz
•
8th Grade
21 questions
Continents and Oceans
Quiz
•
6th Grade
12 questions
Unit Zero lesson 2 cafeteria
Presentation
•
9th - 12th Grade
20 questions
Parts of Speech
Quiz
•
5th Grade
10 questions
Riddles Riddles fun Riddles
Quiz
•
6th - 12th Grade
16 questions
Subject & Predicate
Quiz
•
5th Grade