NFPA 13: Finding the section and answer
Professional Development
University
Used 514+ times

AI Actions
Add similar questions
Adjust reading levels
Convert to real-world scenario
Translate activity
More...
Content View
Student View
25 questions
Show all answers
1.
MULTIPLE CHOICE QUESTION
1 min • 1 pt
When supporting a run of 6 inch sprinkler main entirely with expansion shields in the vertical position, their maximum spacing apart is:
5 feet
8 feet
10 feet
12 feet
2.
MULTIPLE CHOICE QUESTION
1 min • 1 pt
Sprinklers under glass or plastic skylights exposed to the direct rays of the sun shall be of the _________ temperature classification.
intermediate
ordinary
high
extra high
3.
MULTIPLE CHOICE QUESTION
1 min • 1 pt
The frame of an upright sprinkler head should be installed______.
parallel to the attached piping
perpendicular to the attached piping
with the pitch of the roof
pointing in the direction to the shut off valve
4.
MULTIPLE CHOICE QUESTION
1 min • 1 pt
Hydrostatic testing per NFPA-13 requires that the hydrostatic testing be performed with the clapper off its seat if the valve is:
an alarm valve
a pre-action valve
a differential type dry-pipe valve
a latch clapper type dry-pipe valve
5.
MULTIPLE CHOICE QUESTION
1 min • 1 pt
A new dry pipe system shall be tested for 24 hours with
40 psi air
50 PSI air
150 PSI water
200 PSI water
6.
MULTIPLE CHOICE QUESTION
1 min • 1 pt
The distance between a hanger and the centerline of an upright sprinkler shall not be less than
3 inches
4 inches
5 inches
6 inches
7.
MULTIPLE CHOICE QUESTION
1 min • 1 pt
A minimum clearance between the top of storage and a standard spray pendent sprinkler's deflector shall be?
24 inches
18 inches
12 inches
6 inches