Electrical Fault Finding B

Electrical Fault Finding B

Assessment

Quiz

Physics

University

Medium

Created by

Craig Carlin

Used 320+ times

FREE Resource

15 questions

Show all answers

1.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

Media Image

The accessory pictured is often used in testing when conducting test using what particular method?

Test method 2

Test method 1

Continuity of ring final conductors

Test method 3

2.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

The Ze is to be measured as part of the initial verification process, what instrument should be used for this task?

An earth fault loop impedance tester

An insulation resistance tester

An RCD tester

A low resistance ohmmeter

3.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

The maximum value of earth electrode resistance for a TT installation protected by a 500mA RCD is given by BS7671 as

1660Ω

500Ω

160Ω

100 Ω

4.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

A 100mA RCD protecting a TT installation tested at 1/2 I should

Operate within 300ms

Operate within 200ms

Not operate

Operate within 40ms

5.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

The following readings were taken on a test performed on a ring final circuit, Line to Line 0.8 Ω Neutral to Neutral 0.8 Ω cpc to cpc 0.8 Ω . What would be the expected reading between line and cpc at each socket outlet?

1.6 Ω

0.4 Ω

0.8 Ω

0.2 Ω

6.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

What is the importance of verifying readings obtained with those listed within BS7671 and associated documents?

The circuit is safe and within design parameters

The circuit protection does not operate accidentally without warning

The instrument is functioning correctly and within stated tolerances

The instrument conforms to BS EN 61010

7.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

If two bonding conductors or equal length were connected in parallel the resistance would

Increase

Double

Not change

Halve