10 questions

Show all answers

1.

MULTIPLE CHOICE QUESTION

2 mins • 1 pt

Where the transfer of supply to an alternative supply is to take place in a TN system, a multi-pole switch must be used which switches the line and neutral conductors, this method prevents?

a)       Electromagnetic fields due to stray currents in the main supply system
b)       The earth-fault loop impedance exceeding maximum values
c)        The prospective fault current tripping the main protective circuit breaker
d)       The rated residual current tripping any RCD devices

2.

MULTIPLE CHOICE QUESTION

2 mins • 1 pt

Simultaneously accessible exposed-conductive parts shall be connected to the same earthing system?

a)       Independent of each system
b)       Individually, in groups or collectively
c)        Not at all
d)       Through a high resistance impedance

3.

MULTIPLE CHOICE QUESTION

2 mins • 1 pt

What is the minimum impulse voltage for 120 V Category II equipment?

a)             1.5 kV
b)          2.5 kV
c)             4.0 kV
d)            6.0kV

4.

MULTIPLE CHOICE QUESTION

2 mins • 1 pt

The external influence code CA2 refers to?

a)        Where a building is subject to ground tremors
b)        Where a building is mainly constructed of combustible material e.g. wood
c)        Where a building is subjected to heavy water waves
d)        Where a building is subjected to extreme ultra-violet radiation

5.

MULTIPLE CHOICE QUESTION

2 mins • 1 pt

In an IT system that does not have a neutral conductor it is permitted to omit a device to provide overload protection if?

a)        The DNO supply fuse will provide this protection
b)       The IT earth-impedance is sufficiently high enough
c)         Harmonic currents will not be present
d)        An RCD is installed in each circuit

6.

MULTIPLE CHOICE QUESTION

2 mins • 1 pt

A BS 88-2 fuse is to be fitted to a TN circuit with a Zs value of 2.4 Q and requiring a disconnection time of 0.4s What is the maximum rated fuse that couId be used?

a)             25 A
b)          32 A
c)             16 A
d)             20 A

7.

MULTIPLE CHOICE QUESTION

2 mins • 1 pt

A temperature cut-out device shall have only?

a)        A manual reset
b)       An automatic reset
c)        A re-settable reset
d)       A master reset

Access all questions and much more by creating a free account

Create resources

Host any resource

Get auto-graded reports

Google

Continue with Google

Email

Continue with Email

Classlink

Continue with Classlink

Clever

Continue with Clever

or continue with

Microsoft

Microsoft

Apple

Apple

Others

Others

Already have an account?