Spray applied fireproofing 1a
Authored by Piledriverob Piledriverob2375
Science
1st - 5th Grade
Used 12+ times

AI Actions
Add similar questions
Adjust reading levels
Convert to real-world scenario
Translate activity
More...
Content View
Student View
11 questions
Show all answers
1.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
According to the IBC, for SFRM not more than ___ of the individual thickness measurements shall be less than that specified in the construction documents
10 %
20 %
25%
Answer explanation
IBC 1705.15.4
THICKNESS:
Not more than 10% of the thickness measurements of the sprayed fire-resistant material applied to FLOOR, ROOF and WALL assemblies & structural members shall be less than the thickness required by the approved fire-resistance design,
2.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
___% of primary structural frame members shall be measured for thickness determination
25%
10%
20%
Answer explanation
IBC 1705.15.4.5
STRUCTURAL MEMBERS:
............Thickness testing shall be performed on not less than 25 percent of the structural member on each floor
3.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
When verifying thickness of SFRM for FLOOR, ROOOF and WALL assemblies, at least ____ measurements shall be made for every _____ of sprayed area or portion thereof in each story
FOUR /
1000ftsq
8 /
2500
9 /
2500
Answer explanation
IBC
1705.15.4.2
FLOORS, ROOF, and WALL assemblies:
..........not less than FOUR measurements for each 1,000 square feet of the sprayed area
4.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
How many measurements at a single cross section are required for a wide flange column
12
seven
one
Answer explanation
IBC
1705.15.4.8
WIDE FLANGED COLUMN:
at wide flanged columns, thickness measurements shall be made AT 12 LOCATIONS........
5.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
What is the minimum allowable individual thickness measurements if the specified thickness is 1-5/8 inches ?
1 - 3/8 in.
one and five eighth
one and seven sixteenth
Answer explanation
IBC
1705.15.4.1
MINIMUM ALLOWABLE THICKNESS:
for design thicknesses 1 inch or greater the minimum allowable individual thickness shall be the design thickness minus 1/4 inch.......................
6.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
According to the building code how often should DENSITY samples for a FLOOR assembly be taken ?
EVERY 2500 square feet
1000 ft/sq
12 ft
Answer explanation
IBC
1705.15.5
DENSITY:
......................
1. From each FLOOR , ROOF and WALLS assembly at the rate of not less than ONE sample for every 2,500 square feet of portion thereof of the sprayed area in each story.
7.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
How many measurements at a single cross section are required for a beam
9
seven
twelve
Answer explanation
IBC
1705.15.4.6
BEAMS and GIRDERS:
At BEAMS & GIRDERS thickness measurements shall be made at NINE locations around the BEAM or GIRDER at each end of a 12 inch length