1.

MULTIPLE CHOICE QUESTION

3 mins • 1 pt

Under which of the following conditions is it permissible to perform work as an ASSE 6010 Installer?

When workers, not certified in brazing procedures, are overseen by someone who is and ASSE 6010 Installer

When working directly with a certified installer who has a record of previous performance qualification tests

When brazing procedures have been qualified by a technically competent agency

When working for a contractor who obtains a copy of job site brazing procedure specifications in advance of the work

Answer explanation

Reference section 5.1.10.11.10

Installer is to provide and maintain documentation on the job site of brazing PROCEDURES, and qualified brazers.

2.

MULTIPLE CHOICE QUESTION

3 mins • 1 pt

It is NOT permissible to pipe and utilize medical support gases, such as oxygen, for which of these purposes?

General utility, such as moisture removal from instruments

Direct respiration by patients

Simulation centers for the assessment of healthcare specialists

Operating medical equipment that is only intended for patient

Answer explanation

Section 5.1.3.5.2

3.

MULTIPLE CHOICE QUESTION

3 mins • 1 pt

Which of the following is NOT a requirement of a bulk oxygen system installed to supply compressed gas?

Terminates where the gas, at service pressure, first enters the main line

Maximum storage capacity must be 25,000 ft3

Consists of stationary and movable containers

Cubed source gas is stored as a compressed gas or cryogenic fluid

Answer explanation

While there is a minimum storage requirement of 20,000 cubic feet to be defined as a Bulk Oxygen system, the NFPA 99 code does not define Bulk system maximum storage sizing.

Section 3.3.20.3

4.

MULTIPLE CHOICE QUESTION

3 mins • 1 pt

Certified individuals installing CMT shall do so in accordance with which of the following?

Facility Engineering

Manufacturer's instructions

Qualified Contractor

ASSE 6010

Answer explanation

Section 5.1.10.11.10.3

5.

MULTIPLE CHOICE QUESTION

3 mins • 1 pt

The emergency oxygen supply connection (EOSC) shall consist of all EXCEPT which of the following?

A minimum of five feet clearance around the EOSC for connection of temporary auxiliary source

four alarm connection points installed to both master alarm panels

manual shutoff valve to isolate the EOSC when not in use and physical protection to prevent unauthorized tampering

valves necessary to allow connection of an emergency supply of oxygen and isolation of piping to the normal source supply

Answer explanation

Section 5.1.3.5.12.2 (8)

6.

MULTIPLE CHOICE QUESTION

3 mins • 1 pt

Which of the following would describe an assembly of equipment for supplying compressed gas that terminates where the gas at service pressure first enters the main line?

The source gas is stored as compressed gas or cryogenic fluid in storage containers that are either stationary or movable and include unconnected reserves on hand at the site

Compact System

Bulk System

Main Supply Pad

Essential Supply System

Answer explanation

Section 3.3.20

7.

MULTIPLE CHOICE QUESTION

3 mins • 1 pt

A gauge reading that exceeds 200 psig is defined in NFPA 99 as which type of pressure?

Gauge

High

Positive

Absolute

Answer explanation

Section 3.3.156.4

Access all questions and much more by creating a free account

Create resources

Host any resource

Get auto-graded reports

Google

Continue with Google

Email

Continue with Email

Classlink

Continue with Classlink

Clever

Continue with Clever

or continue with

Microsoft

Microsoft

Apple

Apple

Others

Others

Already have an account?