NEC 2023 Practice Test

NEC 2023 Practice Test

Assessment

Quiz

Mathematics

University

Practice Problem

Hard

Created by

Mr. Know-It-all

FREE Resource

AI

Enhance your content in a minute

Add similar questions
Adjust reading levels
Convert to real-world scenario
Translate activity
More...

25 questions

Show all answers

1.

MULTIPLE CHOICE QUESTION

5 mins • 4 pts

A circuit breaker protecting a non-motor-operated appliance shall not exceed 20 amperes if the overcurrent rating is not marked and the appliance is rated _______or less.

12.3 amperes

15.3 amperes

14.3 amperes

13.3 amperes

Answer explanation

422.11 (E)

2.

MULTIPLE CHOICE QUESTION

5 mins • 4 pts

What is the full-load current rating on the secondary side terminals of a 75 kVA, three-phase transformer having a 277/480 volt primary and a 208Y/120 volt secondary?

156 amperes

208 amperes

360 amperes

362 amperes

Answer explanation

75 x 1000 = 75000 / 208 x 1.732 = 75000/360.25 = 208

3.

MULTIPLE CHOICE QUESTION

5 mins • 4 pts

A 150 kVA, single-phase transformer having a secondary voltage of 120/240 Volts is to be installed in a multi-family dwelling. The current available at the Secondary terminals is ____________.

329 amperes

421 amperes

625 amperes

729 amperes

Answer explanation

15000 / 240 = 625

4.

MULTIPLE CHOICE QUESTION

5 mins • 4 pts

When installed on the service of a building or structure, a Type 2 SPD shall be connected----.

on the line side of the service disconnect overcurrent device

on the load side of the service disconnect device

on the meter housing

at the final overcurrent device

Answer explanation

242.14 (A)

5.

MULTIPLE CHOICE QUESTION

5 mins • 4 pts

The maximum number of No. 10 AWG conductors in a 4 inch x 1-1/4 inch square box is ________.

Seven

Four

Five

Six

Answer explanation

Table 314.16 (A)

6.

MULTIPLE CHOICE QUESTION

5 mins • 4 pts

The minimum clearance above a diving platform of a swimming pool and 120/240-volt, single-phase, messenger supported, service-drop conductors is ____________.

14-1/2 feet

22-1/2 feet

19 feet

21 feet

Answer explanation

Table 680.9 (A)

7.

MULTIPLE CHOICE QUESTION

5 mins • 4 pts

The minimum space between the bottom of a 600-volt rated switchboard and non-insulated bus bars mounted in the switchboard cabinet is ------.

6 inches

8 inches

10 inches

12 inches

Answer explanation

Table 408.5

Access all questions and much more by creating a free account

Create resources

Host any resource

Get auto-graded reports

Google

Continue with Google

Email

Continue with Email

Classlink

Continue with Classlink

Clever

Continue with Clever

or continue with

Microsoft

Microsoft

Apple

Apple

Others

Others

Already have an account?