KUIS IK PURGING BOILER UNIT 1-4
Authored by Febrian Indra
Specialty
Professional Development
Used 1+ times

AI Actions
Add similar questions
Adjust reading levels
Convert to real-world scenario
Translate activity
More...
Content View
Student View
20 questions
Show all answers
1.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
Berapa nomor dokumen IK PURGING BOILER UNIT 1-4
IK.SLA.05.02.76
IK.SLA.05.02.77
IK.SLA.05.02.78
IK.SLA.05.02.79
2.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
Proses Pembilasan gas-gas sisa hasil pembakaran yang masih terjebak di dalam laluan gas dalam boiler dengan menggunakan media udara sekunder untuk mengindari terjadinya eksplosive saat proses firing adalah pengertian dari :
Boiler start up
Boiler Purging
Boiler Run Back
Boiler Trip
3.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
Saat purging boiler, furnace pressure di setting berapa?
-700 mmWg
-10 mmWg
-100 mmWg
-30 mmWg
4.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
Air Heater Balancing di setting 100% maka pembukaan damper-damper Air Heater ?
MAIN AH Gas out 100% dan MILL AH Gas out 100%
MAIN AH Gas out 50% dan MILL AH Gas out 50%
MAIN AH Gas out 100% dan MILL AH Gas out 0%
MAIN AH Gas out 0% dan MILL AH Gas out 100%
5.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
Air Heater Balancing di setting 0% maka pembukaan damper-damper Air Heater ?
MAIN AH Gas out 0% dan MILL AH Gas out 100%
MAIN AH Gas out 0% dan MILL AH Gas out 0%
MAIN AH Gas out 100% dan MILL AH Gas out 0%
MAIN AH Gas out 100% dan MILL AH Gas out 100%
6.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
Air Heater Balancing di setting 50% maka pembukaan damper-damper Air Heater ?
MAIN AH Gas out 0% dan MILL AH Gas out 100%
MAIN AH Gas out 50% dan MILL AH Gas out 50%
MAIN AH Gas out 100% dan MILL AH Gas out 0%
MAIN AH Gas out 100% dan MILL AH Gas out 100%
7.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
Economizer Bypass di setting 50% maka pembukaan damper-damper ?
EcoBypass Damper (F1) 50% dan Eco Outlet ControlDamper (F9) 50%
EcoBypass Damper (F1) 100% dan Eco Outlet ControlDamper (F9) 50%
EcoBypass Damper (F1) 50% dan Eco Outlet ControlDamper (F9) 100%
EcoBypass Damper (F1) 100% dan Eco Outlet ControlDamper (F9) 100%