1.
MULTIPLE CHOICE QUESTION
2 mins • 1 pt
Services exceeding 1000 volts nominal are covered by Part VIII of Article 230. Which other parts of Article 230 also cover services exceeding 1000 volts nominal where applicable?
Part I, General
Part V, Service Equipment, General
All other parts
No other parts
2.
MULTIPLE CHOICE QUESTION
2 mins • 1 pt
A fuse rated in continuous amperes not to exceed ? times the ampacity of the conductor, or a circuit breaker with a trip setting of not more than ? times the ampacity of the conductors, shall be considered as providing the required short-circuit protection for service entrance conductors which operate at over 1000 volts, nominal.
three / three
three / six
six / three
six / six
Answer explanation
230.208
3.
MULTIPLE CHOICE QUESTION
2 mins • 1 pt
A ground-fault circuit interrupter is generally required to be installed to protect luminaires, submersible pumps, and other submersible equipment installed in permanently installed fountains in accordance with requirements in Part ? of Article 680.
III
IV
V
VI
Answer explanation
230.202(B), Table 300.50
4.
MULTIPLE CHOICE QUESTION
2 mins • 1 pt
What is the minimum cover requirements for Type USE, direct-buried cables which operate at 24 kilovolts? The cables are installed without concrete protection or encasement on commercial property not subject to vehicular traffic.
18"
24"
36"
42"
Answer explanation
680.51(A)
5.
MULTIPLE CHOICE QUESTION
2 mins • 1 pt
Pool associated motors shall be permitted to employ cord-and-plug connections. The flexible cord shall not exceed ? in length.
3'
4'
5'
6'
Answer explanation
680.21(A)(3)
6.
MULTIPLE CHOICE QUESTION
2 mins • 1 pt
Where a permanently installed pool is installed, no fewer than one 125-volt, 15- or 20-ampere receptacle on a general-purpose branch circuit shall be located not less than ? from, and not more than ? from, the inside wall of the pool.
6' / 10'
6' / 15'
6' / 20'
6' / 25'
Answer explanation
680.22(A)(1)
7.
MULTIPLE CHOICE QUESTION
2 mins • 1 pt
In locations such as assembly occupancies and theaters, a ? for controlling emergency lighting systems shall be located in the lobby or at a place conveniently accessible thereto.
key
relay
schedule
switch
Answer explanation
700.21