1.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
The top part of a distribution board must conform to?
IP2X
IPX2
IP4X
IP67
Answer explanation
The top part of a distribution board must conform to IP4X, which indicates protection against solid objects larger than 1mm. This ensures safety and compliance in electrical installations.
2.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
The correct formula for calculating earth fault loop impedance is?
Zs=Ze-(R1+R2)
Zs=Ze+(R1xR2)
Zs=Ze+(R1+R2)
Zs=Ze/(R1+R2)
Answer explanation
The correct formula for calculating earth fault loop impedance is Zs=Ze+(R1+R2). This accounts for the earth fault loop impedance (Zs) as the sum of the earth fault loop impedance (Ze) and the resistances (R1 and R2).
3.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
Which type of earthing system uses the armour/metallic sheath of the supply cable as the Earth?
TT
TN-C-S
IT
TN-S
Answer explanation
The TN-S earthing system uses the metallic sheath of the supply cable as the Earth. This provides a direct path for fault currents, enhancing safety and system reliability.
4.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
Which type of earthing system relies on the general mass of Earth as the Earth conductor?
TT
TN-C-S
IT
TN-S
Answer explanation
The TT earthing system uses the general mass of the Earth as the Earth conductor, providing a direct connection to the ground. This distinguishes it from other systems like TN-C-S, IT, and TN-S, which have different configurations.
5.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
Which type of earthing system uses a combined PEN conductor, external to the installation?
TT
TN-C-S
IT
TN-S
Answer explanation
The TN-C-S system uses a combined Protective Earth and Neutral (PEN) conductor, which is external to the installation. This distinguishes it from other systems like TT and IT, which do not utilize a combined PEN conductor.
6.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
An earth fault loop impedance test performed on a ring final circuit would record?
the resistance of the protective conductor
the resistance of the protective conductor and the line conductor
the external loop impedance
the resistance of the line conductor, protective conductor and external loop impedance
Answer explanation
An earth fault loop impedance test on a ring final circuit measures the total impedance, which includes the resistance of the line conductor, the protective conductor, and the external loop impedance.
7.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
A polarity test is conducted to verify that?
every single pole device is connected to the line and neutral conductors
the circuit protective conductors are correctly connected
All conductors are terminated correctly, single pole devices terminated in the line only
the resistance is high enough to operate the protective device within 0.4 seconds
Answer explanation
The polarity test ensures that all conductors are terminated correctly, confirming that single pole devices are connected to the line only, which is crucial for safe and proper circuit operation.
Access all questions and much more by creating a free account
Create resources
Host any resource
Get auto-graded reports

Continue with Google

Continue with Email

Continue with Classlink

Continue with Clever
or continue with

Microsoft
%20(1).png)
Apple
Others
Already have an account?
Popular Resources on Wayground
15 questions
Fractions on a Number Line
Quiz
•
3rd Grade
20 questions
Equivalent Fractions
Quiz
•
3rd Grade
25 questions
Multiplication Facts
Quiz
•
5th Grade
22 questions
fractions
Quiz
•
3rd Grade
20 questions
Main Idea and Details
Quiz
•
5th Grade
20 questions
Context Clues
Quiz
•
6th Grade
15 questions
Equivalent Fractions
Quiz
•
4th Grade
20 questions
Figurative Language Review
Quiz
•
6th Grade