_____________________ is the comparison of a measurement device (an unknown) against an equal or better standard.
Installation
Troubleshooting
Calibration
Planning
______________ is the signal coming from the field at its lower range value (LRV). i.e, 4mA
Dead Zero
Live Zero
Range
Span
_____________________ means the value of actual signal coming from field is zero (0) i.e, signal fails to reach the controller or no power supply
Dead Zero
Live Zero
Range
Span
In calibration, which adjustment is used to change the slope of the input-output curve?
Span Adjustment
Zero Adjustment
Linearization Adjustment
Combined Zero and Span Adjustment
___________________ is the region between the limits within which a quantity is measured, received or transmitted, expressed by stating the lower (LRV) and upper (URV) range values.
Range
Span
Zero
Zeroing
___________________________ is the algebraic difference between the upper range value (URV) and lower range value (LRV).
Span value
Range Value
Zero
Live Zero
_____________________ is defined as the maximum allowable deviation or error between a standard of known accuracy and your instrument.
Tolerance
Span
Calibration frequency
Zeroing
Given a signal range of 4-20 mA, what is the span?
20 mA
4 mA
16 mA
12 mA
An instrument has an input range of 0.2-1.0 bar. If the instrument requires 25% of span during calibration, what must be the input value?
0.4 bar
0.6 bar
0.8 bar
1.0 bar
A pressure transmitter has the following specification:
Input: 3 - 15 psi
Output: 4-20 mA
If the pressure being measured by the transmitter is 9 psi, what must be the output?
8 mA
12 mA
16 mA
20 mA
Pressure, level, flow, and temperature are examples of _________________.
Set point
Pneumatic Valve
Controller
Process Variable
Which element of the automatic control measures the value of a controlled or process variable?
Controller
Sensor
Final Control Element
Transmitter
Which element of the automatic control continuously compares the value of the process variable (usually a transmitter output signal) with the set point setting.
Controller
Sensor
Transmitter
Process variable
Which element of the control system adjust the value of the process variable?
Sensor
Final Control Element
Transmitter
Controller
Which of the following is a pneumatic signal?
4-20 mA
3-15 psi
0-10 V
0-20 mA
A _______________________ is an instrument or device which receives one form of energy and changes or converts it to another form.
Controller
PLC
Final control element
Transducer
Which of the following is an example of a final control element?
Flow transmitter
Capacitive level sensor
Contoller
Pneumatic Valve
Which of the following is an example of a controller?
PLC
Pressure sensor
Differential pressure transmitter
Digital Display
What is the purpose of a periodic calibration?
To install an instrument
To check if the instrument is new
To verify if the instrument is connected into the system
To detect and correct instrument error
Which calibration is performed on only one instrument with the input and output disconnected?
Loop calibration
System calibration
Individual calibration
No need for calibration
A _________________ is a set of instruments that are grouped and calibrated together. The input and output of the whole group determines the pass or fail status of the calibration.
Individual calibration
Loop calibration
Loop installation
Individual installation
During a five point calibration, the technician found out that the instrument at 100% of the input value needs adjustment. Which adjustment must be done?
Zero adjustment
Span adjustment
Linearization adjustment
Both span and zero adjustment
In a five point calibration, what is the next step after adjusting the span at 100% of the input value?
Go back to 0% of span and adjust zero.
Go to 50% and adjust span
Go to 50% and adjust zero
No need for further adjustment.
The instruments in the photo are called ___________________?
Controllers
Transmitter
Gauge
Final control element
Which instrument or device accepts a pneumatic signal at the input to the instrument and produces a current signal at the output?
Pneumatic-to-Current transducer
Current-to-Pneumatic transducer
Valve positioners
I/P converter