WorksheetsHIGH VOLTAGE
Total questions: 81
Worksheet time: 1hrs 21mins
Enter enrollment Number
An experiment method for computing the field distribution is
solution of laplace equation
electrolytic tank method
digital solution
field intensity method
Finite element method used only with
field which are bounded
filed which are unbounded
both bounded and unbounded
high accuracy is not required
Most suitable method to solve electrostatic field problem is
Laplace equation
charge simulation method
finite difference method
resistance analog method
The accuracy obtain in numerical computation of electric field is usually
very high
at very low
5 to 10 %
2 to 5%
Electrical conduction in gases was first studied in 1905 by
Loeb
Maxwell
Townsend
Hertz
An electronegative gas is one in which
positive ions formed along with electrons
gas has inherent negative charge
gas is ionized due to electron bombardment
gas in which electron get attached to from negative ion.
SF6 is a
neutral gas
electronegative gas
ionizes easily to form ions
non attaching gas
Ionization coefficients α γ are function of
applied voltage
pressure and temperture
electrical field
ration of electrical field to pressure
Time lag is dependent upon
time difference between instant of applied voltage and occurrence of breakdown
time difference between instant of applied voltage and occurrence of electrical field
time difference between instant of applied voltage and pressure
all above
streamer mechanism of breakdown explain phenomena of electrical breakdown of
very short spark gaps
very long spark gaps
spark subjected to impulse volatges
very long gaps where filed is non-uniform
Minimum sparking potential of air is about
100V
100KV
325V
325KV
for a 1 cm gap in air at 760 mm pressure and 20C temperture the breakdwon voltge is
24KV
24.5 KV
30.3 KV
30.4 KV
The requirement of gases for insulation purpose is
high dielectric strength the thermal stability
high dielectric strength only
high thermal stability
low thermal stability
The mechanism of a gases for insulation purpose is
partical exchange
clump formation
filed emission
all of above
SF6 has the following property which is not favorable for use in electrical apparatus:
High dielectric strength
low dielectric strength
It is not environmental friendly and causes global warming
None of the above
The breakdown voltage of spark gap for impulse voltage is .................compare to the breakdown voltage of power frequency ac
same
larger
smaller
none of above
Among gases used electrical insulation which gas the highest breakdown strength at atmospheric pressure?
Air
Nitrogen
SF6
Oxygen
Transformer oil is
askeral
silicone oil
polyester
mineral oil
The breakdown strength of mineral oil is about
20 KV/mm
50 KV/mm
3 to 5 KV/mm
120 KV/mm
tanδ for liquid insulants at 50 Hz should less than
0.1
0.001
0.0005
10−6
Dielectric constant of mineral oils is about
1.5 to 2
2.2 to 2.9
1.008
2.2 to 2.4
conduction and breakdown in commercial liquid is affected by
solid partical
vapour or air bubbles
electrode material
all above
stressed oil volume theory is applicable when
small volume of liquid is involved
large volume of liquid is involved
large gap distance is involved
pure liquids are involved
The parameter that effect the breakdown strength of liquid is
pressure temperature dissolved impurities and suspended particles.
dielectric constant
dissolved imputites
hydrostatic pressure
In pure liquid dielectric with increase in hydrostatic pressure the breakdown stress
increase linearly up to some extent and does not change afterward
increases exponentially
decreases
none of above
The intrinsic breakdown stregth of solid dielctric is
50 to 100 kv/mm
500 to 1000 kv/mm
5 to 10 kv/mm
1 to 5 kv/mm
The usual mechanism breakdown in solid dielectric is
intrinsic breakdown
electro mechanical breakdown
thermal breakdown
chemical breakdown
Long term deterioration and breakdown occurs in solid dielectric due to
thermal phenomenon
surface discharge
internal discharge
treeing phenomenon
paper insulation is used in
cable and capacitor
transformer
rotating machine
circuit breaker
Thermal classification of insulating material is done
gases
liquid
solid
composite insulation
Breakdown due to internal discharge develop
in millisecond
in few second
over a long duration of several days
all above
Aging in electrical insulating material under electrical field means
gradual reduction in dielectric strength which may lead to breakdown
decrease in insulation resistance of materials
progressive building up of distributive discharge inside material
all the above
For generator coil insulation the class of insulation used in
class A
class B
class C
class F
The insulation used in high voltage circuit breaker of large power rating is
air
vacuum
SF6
mineral oil
For HV cable insulation the material used are
glass and ceramic
silicone rubber
XLPE
paper-oil insulation
Gas insulation is now a days used in which application
Generator
Motor
Transformer
Circuit Breaker and substation
Resins and varnishes are mainly used for
Transformer coil impregnation
Generator and motor coil impregnation
In cable and capacitor insulation
overhead line insulation
In high voltage switchgear, the insulation used inside breaker is
Epoxy resin
Procelain
Vulcanized
Fiber and resin bonded glass fiber
Synethetic liquid dielectric are mainly used
capacitor and cable insulation as impregnates
In transformer insulation
In circuit breaker
all above
Peak to peak ripple is define as
the difference between average dc voltage and peak value
the difference between maximum and minimum and maximum dc voltage
only dc rms value
None above
In testing with a reasonat transformer the output voltage is
rectangular wave
triangular wave
trapezoidal wave
pure sine wave
Parallel resonant transformer the output voltage is
large test voltage are needed
stable output voltage with high rate of rise voltage is needed
large current is needed
small current is needed
Tesla coil used for
generation of sinusoidal output voltage
generation of very high voltage
generation of rectangular voltage
generation of high frequency ac voltage
Average electrical field is magnitude of electrical field
at mid point between conductors
ratio of potential difference to the distance between conductors
at surface of the lower potential electrode
at surface of the higher potential electrode
The value of charging voltage used in medium size impulse generator is
10 to 50 KV
50 to 100 KV
500 Kv
any value
In an impulse current generator the capacitor connected
series
parallel
connected in parallel while charging and series while discharge
connected in series while charging and parallel while discharge
A trigetron gap is used with
cascade transformer unit
impulse current unit
impulse voltage unit
dc voltage double units
The energy rating of different resistor in impulse generator of medium and large size
less than 1 KJ
10 to 20 KJ
1 to 2 KJ
2 to 5 KJ
voltage stabilizer used for regulating high dc voltage are
series type
shunt type
both series and shunt type
shunt or series or degenerating
A series capacitor voltmeter measure
dc voltge
ac voltage
ac voltage peak value
impulse voltage
Electrostatic voltmeter can measure
only dc voltge
both dc and ac voltage up to high frequency
impulse volatge
none above
A generating voltmeter is used
impulse voltage
ac voltage
dc voltage
high frequency ac voltage
CVT when tuned does not have
ratio error
phase angle error
both ration and phase angle errors
temperature error
sphere gaps are used to measure
dc voltage
ac peak voltage
dc ac peak and impulse voltages
on dc peak voltage
The main factor that effect the spark over voltage of sphere gap are
humidity and waveform
nearby earthed objects and atmospheric condition
diameters of the sphere
gap spacing diameter and waveform
Rogoswski coil and high frequency current transformer have bandwidth of about
100 Khz
10 Mhz
1.0 Mhz
1100 Mhz
with series capacitor voltmeter large error will result when
capacitance is larger
meter used is an electromechanical meter
voltage to be measured non-sinusoidal and contain harmonics
none above
To measure high volatge of peak value for 150 kv suitable sphere gap would be
5 or 10
10 or 15
15 or 25
50 or 100
which instrument measure impulse current of short duration
park tubular shunt
current transformer
hall generator
Faraday ammeter
The electric field developed with in cloud before lighting stroke occurs can be of the order of
0.1 KV/cm
1.0 KV/cm
100 KV/cm
10 KV/cm
The velocity of return or main stroke may be
0.01 C
0.001C
0.1 C
0.8 C
The peak value of lighting stroke currents are of order
100 A
1000 A
10 to 100 kA
0.1 KA
The cumulative probability of 10 kA lighting stroke current is about
0.6
0.2
0.1
0.98
switching overvoltage in power system network in order of
1.5 pu
2.5 to 3.5 pu
10 pu or more
1 pu
The material used in gaps less surge arresters used in hv power system is
graphite
aluminium oxide
zinc oxide
metal oxide
The duration of switching surges in GIS is
milisecond
microsecends
few nanosecond and less than a microsecond
none above
For resistivity and dielectric constant measurement the electrode system used
two electrode
three electrode
four electrode
none of above
The power supply used in resistivity measurement is
110 V
250 V
500 V
500 to 2000 V
Loss of charge method is used to deteime
insulation resistance
dielectric constant
loss factor
rate of charging of capacitor
The equivalent circuit of loosy capacitor is
R-C series circuit
R-R series circuit
R-C parallel circuit
R-L series circuit
Partial discharge magnitude is
quantity of charge measured at the terminals of the specimen
crake in solid material
voltage across solid materials
none above
Fifty percentage flash over voltage is define as
the voltage at which the flash over probability is 0.5
the voltage at which the flash over probability is 0.15
the voltage at which the flash over probability is 0.20
the voltage at which the flash over probability is 0.50
Most important test on isolatros are
voltage withstand test
short circuit test
high current test
temperature rise test
Fault location in an HV cable is done by
voltage withstand test
partial discharge scanning test
life test
impulse test
In impulse test of transformer fault location is usually done
neutral current oscillogram
chopped wave oscillation
observing for noise or smoke
scanning method
Most important test on assert the proper functions of surge divertor is
100 % impulse test
front of wave spark over and residual voltage test
impulse current test
pollution test
The salt-fog test done on insulatros
impulse test
power frequency pollution test
impulse current test
impulse voltage test
C - tan δ test on bushing is done using
impulse generator
high voltage schering bridg
low voltage schering bridge
resoant transformer
Impulse test of transformer indicates
dielectric strength quantity of insulation and processing
Full wave standard impulse
Chopped wave standard impulse
Half wave standard impulse
The tests which are not performed under power frequency tests is
Partial discharge tests
Momentary withstand test
Visible discharge tests
Full wave withstand tests