Requirements for System Types

Total questions: 20

Worksheet time: 10mins

Name
Class
Date
1.

The NFPA 13 standard shall provide ______ for the design and installation of automatic fire sprinkler systems and exposure protection sprinkler systems.

a)

the minimum requirements

b)

the maximum requirements

c)

formulaic reciprocity

d)

CAD based drawings

2.

The most common type of sprinkler system in use today is ______.

a)

a wet system

b)

a dry system

c)

a preaction system

d)

an antifreeze system

3.

A wet pipe system shall be provided with a listed relief valve not less than ___ in size and set to operate at 175 psi or 10 psi in excess of the maximum system pressure.

a)

1/4"

b)

1/2"

c)

3/4"

d)

1"

4.

The dry pipe valve and supply pipe _____ against freezing and mechanical injury.

a)

should be protected

b)

shall be protected

c)

might need to be protected

d)

should never need protection

5.

For dry pipe systems, with the exception of some refrigerated spaces, the air supply shall have a capacity capable of restoring normal air pressure in the system within _____.

a)

60 seconds

b)

10 minutes

c)

30 minutes

d)

60 minutes

6.

The connection pipe from the air supply to the dry pipe valve shall not be less than _____ in diameter and shall enter the sytem aove the priming water level of the dry pipe valve.

a)

1/4 inch

b)

1/2 inch

c)

3/4 inch

d)

1 inch

7.

For deluge systems, the detection devices or systems shall be _____ supervised.

a)

automatically

b)

manually

c)

automatically or manually

d)

hydraulically

8.

________ shall not be used in lieu of heated valve enclosures to protect the valve and supply pipe from freezing.

a)

heat tracing

b)

body heat

c)

heat paint

d)

a small gas torch

9.

A ________ with a connection conforming to section 16.7 shall be provided on each wet pipe system utilizing metallic pipe.

a)

priming valve

b)

single mechanical outlet

c)

single air vent

d)

contoured steel pipe

10.

Dry pipe systems are _______ than wet pipe systems and require greater attention regarding their design, installation, and maintenance.

a)

less complicated

b)

more complex

c)

cheaper to install

d)

slightly heavier

11.

For dry pipe systems protecting dwelling unit portions of any occupancy, system size shall be such that initial water is discharged from the connection in not more than ____, starting at the normal air pressure on the system and at the time of fully opened inspection test connection.

a)

60 seconds.

b)

30 seconds

c)

20 seconds

d)

15 seconds

12.

Dry pipe systems that are limited to a maximum volume of 500 gallons (or 750 gallons with a quick opening device) have _____ water delivery time limit.

a)

no required

b)

a 15 second

c)

a 30 second

d)

a 60 second

13.

Unless __________, check valves shall not be used to subdivide the dry pipe systems.

a)

given prior written authorization

b)

requested by the manufacturer

c)

installed in a heated enclosure

d)

obtained from a wholesaler

14.

In refrigerated spaces maintained below 5°F, normal system air pressure shall be permitted to be restored within ___ minutes.

a)

15

b)

30

c)

45

d)

60

15.

A single air compressor supplying multiple dry pipe systems is _____ to restore all systems simultaneously.

a)

required

b)

encouraged

c)

not expected

d)

obligated

16.

A ________ shall be installed in the air filling connection.

a)

tamper switch

b)

check valve

c)

flexible hose of the appropriate thickness

d)

ventilation device

17.

Each dry pipe system shall have ______.

a)

a flow capability of at least 3cu.ft/min

b)

a vane type water flow alarm

c)

CPVC adapters listed for dry system use

d)

a dedicated air maintenance device

18.

Removal of an electric actuator from the preaction or deluge valve that it controls shall result in an _______.

a)

increased water flow velocity

b)

audible and visual indication of system impairment

c)

automatic system restart

d)

immediate flow of water from most activated sprinklers

19.

For single and non-interlock preaction systems, not more than ___ automatic sprinklers shall be controlled by any one preaction valve.

a)

100

b)

200

c)

500

d)

1000

20.

If a fire protection system installed prior to 2012 still uses antifreeze in the system, you must at a minimum _______.

a)

flush the system and replace with a listed noncombustible replacement solution

b)

collect the solution drained from the system to use for refilling

c)

remove the system piping and install a dry pipe valve

d)

determine that the specific gravity of the solution is within tolerable limits