Fire

Total questions: 76

Worksheet time: 39mins

Name
Class
Date
1.

AN ACT ESTABLISHING A COMPREHENSIVE FIRE CODE OF THE PHILIPPINES, REPEALING PRESIDENTIAL DECREE NO. 1185 AND FOR OTHER PURPOSES. SECTION 1.

a)

RA 9514

b)

PD 957

c)

BP 220

d)

RA 9266

2.

Minimum width of egress:

0-500

a)

2 exits

b)

3 exits

c)

4 exits

d)

1 exits

3.

Minimum width of egress:

501 - 1000

a)

3 exits

b)

4 exits

c)

1 exit

d)

2 exits

4.

Arrangement of Exit:

2 exit access door

a)

1/2 diagonal

b)

1/3 diagonal

c)

1/4 diagonal

d)

3/4 diagonal

5.

Arrangement of Exit:

2 exit access door with automatic fire suppression

system

a)

1/3 diagonal

b)

1/2 diagonal

c)

1/4 diagonal

d)

3/4 diagonal

6.

Measurement of Travel Distance to Exits:

Maximum distance from any point in the room to the rood door ?.

a)

10m

b)

15m

c)

18m

d)

20m

7.

No Deadends allowed in excess of..

a)

6m

b)

5m

c)

8m

d)

10m

8.

Swing and Force to Open:

 Door shall be swing out when occupant load is...

a)

50 or more persons

b)

30 or more persons

c)

20 or more persons

d)

45 or more persons

9.

Reentry:

Door opening of 4 or more stories shall be provided with re-entry mechanism. There

shall be re-entry mechanism every ..

a)

4 floors

b)

5 floors

c)

6 floors

d)

3 floors

10.

Width and Floor Level:

Minimum width of means of egress/door.

a)

71 cm

b)

70 cm

c)

72 cm

d)

75 cm

11.

Width and Floor Level:

Maximum width of doorway

a)

122cm

b)

120cm

c)

130cm

d)

125cm

12.

Width and Floor Level:

a)

1.3 cm

b)

13mm

c)

14mm

d)

1.4mm

13.

Threshold in excess of 6mm shall be beveled with a

slope of ____

a)

1:2

b)

1:3

c)

1:5

d)

1:4

14.

Panic Hardware:

Door weight

a)

7kg/f

b)

6kg/f

c)

8kg/f

d)

10kg/f

15.

Panic Hardware:

Panic device placement 760 – 112 cm above

a)

760 – 112 cm above

b)

800 - 120 cm above

c)

850 - 125cm above

d)

900 - 130cm above

16.

When is Revolving door okay for means of egress?

a)

If located within 6 meters

of a swinging door and

must not exceed number

of swining doors.

b)

If located within 8 meters

of a swinging door and

must exceed number

of swining doors

c)

If located within 10 meters

of a swinging door and

must not exceed 2 number

of swining doors

d)

If located within 12 meters

of a swinging door and

must not exceed number

of swining doors

17.

When is turnstile okay for means of egress?

a)

Over 91cm, and must be

located within 6.1m of a

swinging door

b)

Over 80cm, and must be

located within 6 m of a

swinging door

c)

Over 100cm, and must be

located within 7.2m of a

swinging door

d)

Over 110cm, and must be

located within 8.1m of a

swinging door

18.

New Stairs (min) 915 mm

a)

915 mm

b)

200 mm

c)

180 mm

d)

185cm

19.

Curved Stairs :

Minimum width of tread from 305mm from

narrowest end

280mm

a)

305mm, 280mm

b)

250mm, 300mm

c)

150mm, 200mm

d)

NOTA

20.

Spiral stairs :

For Occupant load 3 higher

Max riser 180mm

Minimum Tread 280mm

a)

Max Riser: 180mm

Min. Tread: 280mm

b)

Max Riser: 200mm

Min. Tread: 250mm

c)

Max Riser: 250mm

Min. Tread: 250mm

d)

Max Riser: 190mm

Min. Tread: 250mm

21.

Stair Details:

Maximum load carried by stair 488kg/sq m or 136kg

(concentrated load)

a)

136kg concentrated load

b)

488kg/ sqm.

c)

50kg/sqm.

d)

150kg concentrated load

22.

Stair Details:

Variation of width in treads or in height shall not exceed ____

Nosing of 25mm required for ________

a)

5mm, 25cm

b)

3mm, 30cm

c)

10mm, 25cm

d)

4mm, 30cm

23.

Handrail 760-865 mm

a)

760-865mm

b)

800-900mm

c)

750-850mm

d)

650- 750mm

24.

In Vestibule, Location of Smoke detector ____

a)

Within 3m

b)

Above 3m

c)

Exceed 3m

d)

3m

25.

Ramps:

Minimum width

a)

1120mm

b)

1300mm

c)

1100mm

d)

1500mm

26.

FIRE ESCAPE STAIRS :

Minimum widths

a)

600mm

b)

800mm

c)

1000mm

d)

1200mm

27.

Stand pipe:

64mm hose connection (40m travel distance from required exit)

a)

class 1

b)

class 2

c)

class 3

d)

class 4

28.

Dry stand pipe (Class I)

a)

300psi

b)

250psi

c)

200psi

d)

150psi

29.

Dry stand pipe (Class I):

Size of standpipe(23m or less above the fire service connection)

a)

4''

b)

3''

c)

2''

d)

5''

30.

Dry stand pipe (Class I)

All 102mm dry standpipe shall be equipped with what?

a)

Four-way service connection

b)

Two-way service connection

c)

One-way service connection

d)

NOTA

31.

Dry stand pipe (Class I):

Location of service connection

a)

46cm (min), 122cm (max) above grade

b)

40cm (min), 125cm (max) above grade

c)

30cm (min), 110cm (max) above grade

d)

NOTA

32.

Dry stand pipe (Class I):

Size of Outlet

a)

64mm

b)

60mm

c)

54mm

d)

75mm

33.

Wet Standpipe:

THIS ARE REQUIREMENTS EXCEPT

a)

Assembly exceeding 1000 OL

b)

4 stories or more in height

c)

Storage and mercantile exceeding 1,860 sq m

d)

Hangar

34.

FIRE CODE:

Assembly: Corridor Width

a)

112 cm

b)

100 cm

c)

150 cm

d)

125cm

35.

FIRE CODE:

Assembly: Occupancy Load (concentrated use)

a)

0.65 sq m

b)

1.4 sq m

c)

0.28 sq m

d)

0.60 sq m

36.

FIRE CODE:

Educational: Corridor Width

a)

1.83m

b)

112 cm

c)

2.44m

d)

115 cm

37.

FIRE CODE:

Educational: Occupancy Load (classroom)

a)

1.9 sq m

b)

4.6 sq m

c)

3.3 sq m

d)

11.1 sq m

38.

FIRE CODE:

Healthcare: Corridor Width (in hospitals and nursing homes)

a)

2.44m

b)

1.83m

c)

112 cm

d)

2.55m

39.

FIRE CODE:

Healthcare: Occupancy Load (healthcare sleeping departments)

a)

11.1 sq m

b)

22.30 sq m

c)

24.50 sq m

d)

20.00 sq m

40.

FIRE CODE:

Correctional: Fire Exit Distance without Sprinkler from any travel point

EXCEPT.

a)

30m any room door to exit

b)

46m any point in a room and an exit

c)

10m any point in a sleeping room to the door in that room

d)

23m (without sprinkler)

41.

FIRE CODE: Corridor Width

Residential

Class A - Hotel

Class B - Dormitories

a)

112 cm

b)

1.83m

c)

2.44m

d)

1.83m

42.

FIRE CODE: Corridor Width

Class C- Apartment buildings with 3 or more living units

Class D- Lodging or rooming house with 15 or less occupants

Class E- single and two family dwellings

a)

112 cm

b)

1.83m

c)

2.44m

d)

NOTA

43.

FIRE CODE: Automatic Fire Suppression Requirement

Residential

Class A- Hotel

Class B- Dormitories

Class C- Apartment buildings with 3 or more living units

Class D- Lodging or rooming house with 15 or less occupants

Class E- single and two family dwellings

a)

4 storeys above

b)

5 storey above

c)

2 storeys above

d)

3 storeys above

44.

FIRE CODE: Fire Exit Distance without Sprinkler from any travel point

Mercantile

Class A- 2787 sq m or 3 storeys above

Class B- 287 < 2787 sq m

Class C- 287 sq m below

a)

23m (without sprinkler)

30m (with sprinkler)

b)

25m (without sprinkler)

40m (with sprinkler)

c)

20m (without sprinkler)

35m (with sprinkler)

d)

18m (without sprinkler)

25m (with sprinkler)

45.

FIRE CODE: Mercantile

Occupancy Load (for stores with no street floor but with access from the street by stairs)

a)

2.8 sq m

b)

5.6 sq m

c)

9.3 sq m

d)

11.1 sq m

46.

FIRE CODE: Industrial

Corridor Width

a)

112m

b)

1.83m

c)

2.44m

d)

NOTA

47.

FIRE CODE: Industrial

Occupancy Load

a)

9.3 sq m

b)

5.6 sq m

c)

2.8 sq m

d)

11.1 sq m

48.

FIRE CODE: Storage

Fire Exit Distance without Sprinkler from any travel point

a)

23m (without sprinkler)

30m (with sprinkler

b)

15m (without sprinkler)

22m (with sprinkler

c)

18m (without sprinkler)

25m (with sprinkler

d)

25m (without sprinkler)

32m (with sprinkler

49.

FIRE CODE: Storage

Occupancy Load

a)

9.3 sq m

b)

11.1 sq m

c)

22.30 sq m

d)

5.6 sq m

50.

DIVISION 3 FIRE AND LIFE SAFETY ASSESSMENT REPORT

Applicability:

All private and public buildings, facilities and structures to be constructed or being constructed upon the effectivity of this IRR shall be required to submit ______, among other documents to the City/municipal Fire marshall

a)

FALAR 1

b)

FALAR 2

c)

FALAR 3

51.

DIVISION 3 FIRE AND LIFE SAFETY ASSESSMENT REPORT

Applicability:

All existing private and public buildings with an occupancy of at least 50 persons

a)

FALAR 1

b)

FALAR 2

c)

FALAR 3

52.

what is FSIC ?

a)

FIRE SAFETY INSPECTION CERTIFICATE

b)

FIRE SAFETY INSPECTION CREDENTIAL

c)

FOR SAFETY INSPECTION CERTIFIDE

d)

FIRE SAFETY INSPECTION CERTIFIDE

53.

FIRE CODE OF THE PHILIPPINES:

Revised 2019

a)

RA 9514

b)

RA 9266

c)

BP 344

d)

PD 1096

54.

The active principle of burning, characterized by the heat and light of combustion.

a)

fire

b)

air

c)

earthquake

d)

intensity of Air

55.

fire involving ORDINARY COMBUSTIBLE MATERIALS such as:

wood, cloth, rubber, & plastics

a)

CLASS A FIRE

b)

CLASS B FIRE

c)

CLASS C FIRE

d)

CLASS D FIRE

e)

CLASS K FIRE

56.

LIQUID & GASES

a)

CLASS B FIRE

b)

CLASS A FIRE

c)

CLASS C FIRE

d)

CLASS D FIRE

e)

CLASS F FIRE

57.

ENERGIZED ELECTRICAL EQUIPMENT

a)

CLASS D FIRE

b)

CLASS C FIRE

c)

CLASS A FIRE

d)

CLASS B FIRE

e)

CLASS F FIRE

58.

SODIUM, MAGNESIUM, POTASIUM & other similar materials.

a)

CLASS D FIRE

b)

CLASS C FIRE

c)

CLASS A FIRE

d)

CLASS B FIRE

e)

CLASS F FIRE

59.

COOKING APPLIANCES that involve combustible cooking media (vegetable, animal oils and fats.)

a)

CLASS F FIRE

b)

CLASS D FIRE

c)

CLASS C FIRE

d)

CLASS B FIRE

e)

CLASS A FIRE

60.

A written report composed of plans, specifications and design analysis per building prepared by its Engineer/Architect-of-Record and Fire Safety Practitioner.

a)

Fire Safety Compliance Report (FSCR)

b)

Fire Safety Compliance and Commissioning Report (FSCCR)

c)

Fire Safety Construction

d)

Fire Safety Evaluation Clearance (FSEC)

61.

A compilation report of all approved submittals, test and acceptance forms of all fire protection and life safety features, which shall form part of the “as-built” documents turned over by the contractor to the building owner.

a)

Fire Safety Compliance and Commissioning Report (FSCCR)

b)

Fire Safety Compliance Report (FSCR)

c)

Fire Safety Construction

d)

Fire Safety Evaluation Clearance (FSEC)

62.

Refers to the design and installation of walls, barriers, doors, windows, vents, means of egress and other elements integral to and incorporated into a building or structure in order to minimize danger to life from fire, smoke, fumes or panic before the building is evacuated.

a)

Fire Safety Construction

b)

Fire Safety Evaluation Clearance (FSEC)

c)

Fire Safety Inspector (FSI)

d)

Fire Safety Inspection Certificate (FSIC)

63.

A document issued by the BFP as a prerequisite for the grant of Building Permit by the Office of Building Official having jurisdiction upon determination that the evaluated plans are compliant with RA 9514 and its RIRR.

a)

Fire Safety Evaluation Clearance (FSEC)

b)

Fire Safety Compliance and Commissioning Report (FSCCR)

c)

Fire Safety Compliance Report (FSCR)

d)

Fire Safety Inspection Certificate (FSIC)

64.

A uniformed/non-uniformed personnel of the BFP responsible for fire safety inspection and assessment of fire hazards, and whose function, duties and responsibilities are defined under Division 1, Chapter 2, Rule 8 of this RIRR.

a)

Fire Safety Inspector (FSI)

b)

Fire Safety Practitioner

c)

Fire Volunteer Organization (FVO)

d)

Fire Volunteer

65.

A document issued by the BFP as a prerequisite for the grant of Certificate of Occupancy, Business Permit, Certificate of Annual Inspection from PEZA and other licenses and permits being issued by other government agencies upon determining that the required fire safety construction are in place, and fire protective and/ or warning systems are properly installed in accordance with the approved plans and specifications and in compliance with RA 9514 and its RIRR.

a)

Fire Safety Inspection Certificate (FSIC)

b)

Fire Safety Maintenance Report (FSMR)

c)

Fire Safety Evaluation Clearance (FSEC)

d)

Fire Safety Compliance and Commissioning Report (FSCCR)

66.

A written report prepared by the building owner, his/her fire safety practitioner or authorized representative. This is a compilation of the maintenance

a)

Fire Safety Maintenance Report (FSMR)

b)

Fire Safety Inspection Certificate (FSIC)

c)

Fire Safety Evaluation Clearance (FSEC)

d)

Fire Safety Compliance Report (FSCR)

67.

written report prepared by Architect.

a)

FALAR 1

b)

FALAR 2

c)

FALAR 3

68.

Documentation submitted by CONTRACTOR/S and CONSTRUCTION MANAGER.

a)

FALAR 1

b)

FALAR 2

c)

FALAR 3

69.

Documentation prepared by BUILDING OWNER.

a)

FALAR 1

b)

FALAR 2

c)

FALAR 3

70.

EXITS:

1 Hour fire rating; 2 Hour fire rating

a)

3 storey

b)

4 storey

c)

2 storey

d)

5 storey

71.

minimum width: means of egress

a)

915mm

b)

1001mm

c)

956mm

d)

975mm

72.

FIRE CODE: EXITS

minimum HEAD ROOM

a)

2 meters

b)

2.1 meters

c)

2.4 meters

d)

2.5 meters

73.

FIRE CODE: EXITS

minimum DOOR OPENING

a)

710mm

b)

670mm

c)

810mm

d)

910mm

74.

FIRE CODE: EXITS

maximum Door

a)

1220mm

b)

1200mm

c)

1560mm

d)

1350mm

75.

FIRE CODE:

PANIC DOOR HARDWARE: panic bar installation height

a)

760mm (MIN.)

1120mm (MAX.)

b)

800mm (MIN.)

1100mm (MAX.)

c)

650mm (MIN.)

1000mm (MAX.)

d)

900mm (MIN.)

1200mm (MAX.)

76.

FIRE CODE:

EXIT SIGN LIGHT

a)

10.7 lux

b)

9.0 lux

c)

11.05 lux

d)

12.3 lux