WorksheetsTesting and Inspection - Electrical
Total questions: 15
Worksheet time: 7mins
Which is classed as a statutory document from the below
EAWR
Guidance Note 3
GS38
BS7671
How Many Keys must be made available for safe isolation lock off kit
1
2
3
4
What is the maximum permitted probe tip length to comply with GS38
1.5mm
2mm
3mm
4mm
Which document is required for the completion of a new socket to existing ring main
Minor Electrical Works
Electrical Installation Certificate
Electrical Installation Condition Report
N/A
What is the minimum insulation resistance value for a new electrical installation?
0.5 MΩ
1 MΩ
2 MΩ
5 MΩ
Which Document is required upon completion of a new consumer unit
MW
EIC
EICR
N/A
Which of the following Human Senses is not used during testing and inspection
Hearing
Taste
Sight
Touch
When doing a Global IR test of an installation, you obtain a reading of 4Mega-ohm. What would you do next:
Nothing, This is above 1MΩ and therefore acceptable
Record the result to be checked again in the near future
Breakdown the installation and retest individually circuit by circuit
Breakdown the installation and test in smaller grouped circuits.
The first three tests in sequence of testing are:
Safe Isolation
Continuity of CPC
Ring Main Final Testing
Polarity
Insulation Resistance
The Maximum permitted Ze value for a TN-S earthing arrangement is:
200
0.8
0.35
0.55
The maximum permitted Ze for a TT earthing system is:
200
0.8
0.35
0.55
The correct calculation for IR is:
RT = R1 + R2 + R3 ...
RT = 1/R1 + 1/R2 + 1/R3 ...
1/RT = 1/R1 + 1/R2 + 1/R3 ...
1/RT = 1/R1 - 1/R2 - 1/R3
The maximum permitted Zs value in the On-Site Guide accounts for the "Rule of Thumb" for circuit diversity. This value is:
0.8
70%
0.75
85%
What is the minimum IP rating for an item installed within Zone 2 of a bathroom area:
IPX2
IP44
IPXXD
IP22
Which of the following is classed as a Signatory on an EIC certificate
Installer
Client
Customer
Inspector