Refrigeration System Knowledge Assessment

Total questions: 15

Worksheet time: 8mins

Name
Class
Date
1.

What is the primary purpose of a moisture indicating sight glass in a refrigeration system?

a)

To check the refrigerant level

b)

To check the refrigerant for moisture

c)

To measure the pressure of the refrigerant

d)

To regulate the flow of refrigerant

2.

Why should the liquid-line filter drier be replaced anytime a system is opened for service?

a)

It becomes clogged with refrigerant

b)

It loses its ability to filter moisture

c)

It is a regulatory requirement

d)

It is a standard maintenance procedure

3.

What is the consequence of closing the discharge service valve on an operating reciprocating compressor?

a)

It will increase the efficiency of the compressor

b)

It can result in compressor damage and severe personal injury

c)

It will decrease the system pressure

d)

It will improve the cooling capacity

4.

How does a crankcase heater help in a refrigeration system?

a)

By increasing the refrigerant pressure

b)

By reducing the amount of refrigerant in the oil and reducing oil foaming

c)

By cooling the compressor

d)

By increasing the system's cooling capacity

5.

What is the purpose of using nitrogen when evacuating a system with large amounts of moisture?

a)

To increase the system pressure

b)

To counteract freezing of the moisture

c)

To reduce the refrigerant charge

d)

To improve the efficiency of the vacuum pump

6.

Why is it important to maintain system pressure slightly above atmospheric pressure in an idled low-pressure refrigeration system?

a)

To prevent refrigerant loss

b)

To prevent air accumulation

c)

To increase system efficiency

d)

To reduce maintenance costs

7.

What is the maximum test pressure when leak testing a low-pressure centrifugal chiller with nitrogen?

a)

5 psig

b)

10 psig

c)

15 psig

d)

20 psig

8.

What is the role of a purge unit in a low-pressure chiller system?

a)

To increase refrigerant pressure

b)

To remove non-condensables that leak into the system

c)

To add refrigerant to the system

d)

To cool the refrigerant

9.

According to ASHRAE Guideline 3, when should a system be checked for leaks during a standard vacuum test?

a)

If the pressure rises from 1 mm Hg to above 2.5 mm Hg

b)

If the pressure remains constant at 1 mm Hg

c)

If the pressure drops below 1 mm Hg

d)

If the pressure rises to 5 mm Hg

10.

What is the EPA's maximum allowable leak rate for appliances used for comfort cooling as of January 1, 2019?

a)

5% of the charge per year

b)

10% of the charge per year

c)

20% of the charge per year

d)

30% of the charge per year

11.

What should be done if a chiller with a charge of 200 pounds of an ozone-depleting refrigerant passes the initial verification leak test?

a)

No further action is required

b)

Conduct a follow-up verification test within 10 days

c)

Increase the refrigerant charge

d)

Replace the refrigerant with a non-ozone-depleting alternative

12.

What is the primary reason for using a hydrostatic tube test kit in a refrigeration system?

a)

To measure refrigerant pressure

b)

To determine if a tube is leaking

c)

To increase system efficiency

d)

To reduce refrigerant charge

13.

What is the consequence of having non-condensables, such as air, in a refrigeration system?

a)

It will lower the system's cooling capacity

b)

It will increase the discharge pressure of the system

c)

It will reduce the refrigerant charge

d)

It will improve system efficiency

14.

What is the purpose of using a pressure regulator on nitrogen cylinders in a refrigeration system?

a)

To increase the pressure of nitrogen

b)

To reduce the pressure to a safe level

c)

To measure the nitrogen pressure

d)

To increase system efficiency

15.

What should be done if an appliance with 50 or more pounds of a regulated refrigerant exceeds the threshold leak rate?

a)

Ignore the leak and continue operation

b)

Repair the appliance to bring the leak rate below the threshold, retrofit, or retire the appliance

c)

Increase the refrigerant charge

d)

Replace the refrigerant with a non-regulated alternative