1.

Prior to any installation work, which of the following documentation shall be provided and maintained on site by the installer?

a)

Braze test coupon

b)

Brazing history and procedure qualification

c)

Brazing procedure and date of expiration

d)

Qualification of brazing procedures and individual brazers

2.

Clean, non-shedding abrasive pads shall be used to clean the exterior surfaces of the tube ends, and shall not result in ___________ the surfaces to be joined..

a)

cleaning

b)

grooving

c)

either of the outcomes listed are acceptable

d)

neither of the outcomes listed are acceptable

3.

Mechanical ventilation shall have the opening(s) located _____________ and located adjacent to the cylinders or containers.

a)

within 1 ft. of the floor

b)

within 1 ft. of the ceiling

c)

within 1 ft. of the floor and within 1 ft. of the ceiling

d)

there are no guidelines regarding placement of the opening(s)

4.

Refer to Diagram #4, identify #14.

a)

In-line valve

b)

EOSC

c)

Future valve

d)

Zone valve

5.

To assure that all ambient air has been removed from the pipeline prior to brazing, a/an __________ shall be used to verify the effectiveness of the nitrogen purge.

a)

Oxygen analyzer

b)

Nitrogen analyzer

c)

Breathalyzer

d)

Air analyzer

6.

Refer to Diagram 1. This is a picture of a tool used to dimple fittings to a mechanically limited depth, what is the minimum depth for 1.25" (1.375" OD) tubing?

a)

.25 in.

b)

.28 in.

c)

.31 in.

d)

.34 in.

7.

Which of the following is labeled incorrectly?

a)

Oxygen with green background and white text

b)

WAGD with green background and white text

c)

Medical air with yellow background and black text

d)

WAGD with violet background and white text

8.

After completion of the installer-performed tests, individual pressurization is one method used to determine that no cross-connection exists. All systems are dropped to zero, and the system being tested will be pressurized to a gauge pressure of __________.

a)

30 psi

b)

50 psi

c)

150 psi

d)

300 psi

9.

Refer to Diagram #3, choose the correct distance for the location at capital letter D.

a)

10'

b)

20'

c)

25'

d)

There is NOT a stated requirement in NFPA 99

10.

Where medical gas systems operate at pressures other than the standard gauge pressures, which of these is required to be listed on the station outlet identification?

a)

Gas registration number and a toll-free number to call for information

b)

Name of the gas and the non-standard operating pressure

c)

Name of the gas

d)

The non-standard operating pressure

11.

Excluding outdoor locations, which of these is an NFPA 99 requirement for the wiring of each of the two mandatory master alarms?

a)

Wired independently to the initiating device(s) for each signal

b)

Without splices

c)

Alarms shall be sent to the area alarm panel in the emergency room

d)

Common conductors

12.

Indicators adjacent to __________ shall be labeled to identify the name or chemical symbol of the system that they monitor.

a)

master alarm actuators

b)

area alarm actuators

c)

local alarm actuators

d)

master and area alarm actuators

13.

What is NOT required for the purity parameters of medical air?

a)

Medical air must be a bulk system

b)

Dew point must be

35º F or less

c)

Gaseous hydrocarbons must be less than 30 ppm

d)

Carbon monoxide must be less than 10 ppm

14.

The source valve on a cryogenic fluid source, shall be installed by persons holding which certification?

a)

ASSE 6010

b)

ASSE 6015

c)

ASSE 6030

d)

ASSE 6035

15.

An assembly of equipment that holds a capacity greater than ______ cubic feet is defined as a

Bulk Oxygen System.

a)

3,000

b)

10,000

c)

20,000

d)

28,000

16.

Where compressors that separate the oil containing section from the compression chamber are used, each compressor shall be monitored for which of the following?

a)

Gaseous hydrocarbons

b)

High temperature

c)

Liquid hydrocarbons

d)

Both gaseous hydrocarbons and high temperature

17.

Instrument air intake shall be permitted to be drawn from all EXCEPT ________________.

a)

outside

b)

outside within 25 feet of an exhaust

c)

a clean air duct

d)

the equipment room

18.

Stainless steel tube may be joined by any method EXCEPT which of the following?

a)

Braze

b)

Gas Tungsten Arc Welding (GTAW)

c)

Metal Inert Gas (MIG)

d)

Tungsten Inert Gas (TIG)

19.

Vacuum piping for ________ shall be connected separately from the medical-surgical system, directly to the receiver tank through its own isolation valve and fluid trap located at the receiver.

a)

Each WAGD system

b)

A location requiring seismic restraint

c)

The standing vacuum test

d)

A teaching laboratory

20.

Which type of connectors shall connect medical air compressors with their intake and outlet piping?

a)

Insulated

b)

Dielectric

c)

Compression

d)

Flexible

21.

Which type of tube hangers are permitted in a potentially damp location?

a)

Carbon steel

b)

Copper coated

c)

Plastic coated

d)

Solid copper

22.

Audible and visual alarm indicators shall meet which of the following Requirements?

a)

Testing to determine indicator function should be scheduled periodically and records maintained between testing

b)

Individual indicators shall NOT be less than DN20 size

c)

CGA C-7

d)

The staff should be trained to operate the test button periodically and report malfunctions

23.

Medical gas alarm wiring shall be protected by which of the following? Choose the answer that includes ALL permitted options.

a)

Conduit or free air

b)

Conduit, free air or wire

c)

Conduit, free air, wire or cable tray

d)

Conduit, free air, wire, cable tray or raceways

24.

How many hours must the medical air compressor system be operating normally, before air quality tests can be performed?

a)

2

b)

8

c)

12

d)

24

25.

The level of sedation allowed for use in a Category 2 dental health facility is which of the following?

a)

General anesthesia and deep sedation

b)

Maximum sedation only

c)

Minimal or no sedation

d)

Moderate and minimal

26.

Which of these is a requirement for a station inlet?

a)

A secondary demand valve

b)

A primary valve

c)

A main vacuum line

d)

A primary optional in-line

27.

Clean, _______ shall be used to clean the exterior surfaces of the tube ends, and then wiped clean using a lint-free white cloth.

a)

non -shedding steel wool

b)

non-shedding sand cloth

c)

non-shedding sand screen

d)

non-shedding abrasive pads

28.

Fittings for positive pressure medical gas systems shall be cleaned for oxygen service by __________ in accordance with CGA G-4.1.

a)

The manufacturer

b)

The supplier

c)

A third party agency other than the manufacturer

d)

Any of the choices are acceptable

29.

The medical air compressor intake shall be located a minimum of ____ feet from plumbing vents, ____ feet above the ground, and shall be _________________.

a)

10, 25, plugged or capped

b)

15 ,20, CMT

c)

25, 10, screened

d)

25, 20, turned down and screened

30.

Instrument air systems shall be located ____________ in a dedicated mechanical room, with adequate ventilation and required utilities.

a)

indoors

b)

outdoors

c)

on the roof

d)

in the basement

31.

Medical support gas sources shall be permitted to be piped into, or used for, any purpose EXCEPT________________.

a)

areas for treatment of patients or laboratories, if appropriate to the procedures

b)

general utility purposes

c)

non-medical support applications

d)

powering equipment used in patient care procedures, or operating medical-surgical tools

32.

Stainless tube may be joined by any of the following methods EXCEPT which?

a)

Soldering

b)

Tungsten inert gas (TIG)

c)

Gas tungsten arc welding (GTAW)

d)

Metal inert gas (MIG)

33.

The scale range of positive pressure analog indicators, shall have the normal pressure fall within the ______ percentage of the gauge scale.

a)

1/4

b)

1/3

c)

1/2

d)

2/3

34.

WAGD networks shall provide a(n) ___________ inlet/outlet in all locations where nitrous oxide or halogenated anesthetic gas is intended to be administered.

a)

Vacuum

b)

WAGD

c)

Oxygen

d)

Medical air

35.

Computer systems used as a master alarm shall be continuously attended, or shall provide remote signaling of responsible parties through all of the following EXCEPT __________.

a)

pagers

b)

telephone

c)

cell phone

d)

email

36.

The maximum support spacing for 2.5" or larger plastic pipe used in dental vacuum systems is ________.

a)

3 feet

b)

4 feet

c)

5 feet

d)

6 feet

37.

The master alarm system shall include an indication from each compressor site, when the medical air dew point is greater than _______° F.

a)

22

b)

32

c)

40

d)

35

38.

Brazing performed between cryogenic fluid central supply system vessels and their vaporizers, shall be permitted to be brazed using _________________.

a)

BCuP with flux

b)

BAg with flux

c)

BAg without flux

d)

Any of the listed materials are permitted

39.

The cryogenic fluid central supply system shall have a local signal that visibly indicates the operating status, and an indicator at all master alarms, when or at a predetermined set point before the reserve internal pressure falls too low for the reserve to operate properly indicating ____________.

a)

system failure

b)

reserve failure

c)

maintenance needed

d)

emergency reserve in use

40.

__________________ fittings shall not be required on zone valve pressure indicators.

a)

Gas specific demand check

b)

1/8 inch threaded

c)

1/4 inch threaded

d)

Gas specific D.I.S.S.

41.

Each outlet in a medical gas piping shall be purged until there is no discoloration on _________.

a)

the cleaned test equipment

b)

a clean filter

c)

a clean white cloth

d)

a clean outlet body

42.

Instrument air standby headers shall have a minimum of _______ cylinders attached.

a)

an average day’s supply

b)

1 hour of normal operation

c)

3

d)

4

43.

Oxygen concentrator supply systems used as all three sources of supply shall include all of the following EXCEPT:

a)

A documented risk analysis by the governing authority

b)

An isolation valve and check valve shall be provided to isolate each of the three sources

c)

Shall join the pipeline systems through control arrangements that allow a flow of 100 percent of the peak calculated demand

d)

An NPS 1/8 valved sample port shall be provided on the patient side of the line pressure controls, and the source side of the source valve, for sampling of oxygen

44.

The master alarm system shall consist of two or more alarm panels at sperate locations. One panel should be located in the office or work space, of the on-site individual responsible for maintenance of the med gas and vacuum systems. The other panel shall be located in an area of __________________.

a)

public occupancy

b)

continuous surveillance

c)

emergency surveillance

d)

continuous observation

45.

The master alarm system shall activate when the pressure in the main supply lines increase or decrease by ________ percent.

a)

10

b)

20

c)

40

d)

50

46.

Which of the following is true of Category 1 support gases?

a)

Permitted to power medical-surgical tools and subject to greater hazards present in other piped gases

b)

Used for respiration

c)

Used to calibrate respiratory equipment

d)

None of the choices listed are correct

47.

What percent of the zones shall be tested at the outlet most remote from the source, to verify the piping particulate test?

a)

25%

b)

50%

c)

75%

d)

100%

48.

What is the standard gauge pressure (in. HgV) for a medical-surgical vacuum service?

a)

12 - 24

b)

50 - 55

c)

15 - 30

d)

It varies with system type

49.

Central supply systems for nitrous oxide and carbon dioxide using cylinders or portable containers, shall be prevented from reaching temperatures lower than ______º F.

a)

20

b)

-20

c)

32

d)

125

50.

ASSE 6000 Annex J provides “Recommended Guidelines for Conducting Planned Medical Gas Systems Shutdown and Temporary Backfeed”. Annex J guidelines do NOT include a list of responsibilities for which type of worker?

a)

Medical Gas Generalist

b)

Installer

c)

Shutdown Coordinator

d)

Verifier

51.

When is the initial pressure test conducted by the installer?

a)

After the blow down of the distribution piping

b)

After installation of the alarm sensors

c)

Before blow down of the distribution piping

d)

Before installation of station rough-in assemblies

52.

A method used to provide a source of drainage, aspiration and suction in order to remove bodily fluid from patients.

a)

Anesthesia

b)

Negative pressure

c)

WAGD

d)

Medical-surgical vacuum

53.

Standby headers shall be allowed in medical air compressor area only under which circumstance?

a)

When there is no instrument air equipment in the area

b)

When there is sufficient supply for 1 hour normal operation

c)

Only empty cylinders are allowed

d)

Only Nitrogen is allowed at compressor site

54.

A patient care space is any space of a health care facility wherein patients are intended to be ________.

a)

Admitted or discharged

b)

Sent for x-rays

c)

Interviewed

d)

Examined or treated

55.

Medical air compressor intake shall be located outdoors a minimum distance of ______ from all doors, windows or other openings in the building,

a)

10 ft

b)

20 ft

c)

25 ft

d)

There is no distance requirement

56.

Prior to the installation of a manufactured assembly, documentation shall be provided for all EXCEPT which of the following tests?

a)

Cross connection test

b)

Initial pressure test

c)

Piping purge test

d)

Operational pressure test & Standing pressure test

57.

Refer to diagram 4. The valve labeled #11 is a __________.

a)

Source Valve

b)

Zone Valve

c)

Main line valve

d)

Emergency shutoff valve

58.

Medical air compressors shall be sufficient to serve the peak calculated demand, with the largest single compressor out of service. In no case shall there be fewer than ________ compressors.

a)

2

b)

3

c)

4

d)

5

59.

The final connection between new piping and an existing vacuum system, shall be tested with a(n) __________________ or other means that will allow detection of leaks in an active

a)

supersonic leak detector

b)

oxygen analyzer

c)

ultrasonic leak detector

d)

dew point monitor

60.

Which of the following systems shall NOT be permitted to be located in an outdoor enclosure?

a)

Bulk cryogenic liquid system

b)

Manifolds for cryogenic liquid cylinders

c)

Manifolds for gas cylinders, with or without reserve

d)

Medical air compressor supply sources

61.

A medical air proportioning system shall have a minimum of how many recorders, in order to record system performance and air quality for a period of no less than 24 hours?

a)

1

b)

2

c)

3

d)

4

62.

The medical-surgical vacuum exhaust shall be turned down and screened. The screening material shall be fabricated using what type of material?

a)

Steel mesh

b)

Steel wire

c)

Any non-corroding material

d)

Any non-corrosive material

63.

What is the maximum length of flexible connectors, when used for a category 1 dental system?

a)

3 feet

b)

5 feet

c)

7 feet

d)

No longer than necessary

64.

Cryogenic fluid central supply systems shall include ___________, sized for greater than an average day’s supply, with capacity determined after consideration of the customer usage requirements, delivery schedules and proximity to alternative supplies, and the emergency

a)

a reserve header

b)

a reserve supply

c)

a reserve regulator

d)

a reserve connection

65.

Mechanical exhaust for central supply locations shall not be more than __________.

a)

50 cfm

b)

72 cfm

c)

100 cfm

d)

500 cfm

66.

Cryogenic fluid central supply systems shall be installed in accordance with ____________.

a)

21 CFR 210

b)

21 CFR 211

c)

CGA M-1

d)

all that are listed

67.

To assure that all ambient air has been removed from the pipeline prior to brazing, an oxygen analyzer shall be used to verify the effectiveness of the nitrogen purge. The oxygen level shall read below _______ before brazing begins.

a)

1%

b)

3%

c)

5%

d)

10%

68.

Outdoor bulk cryogenic liquid systems shall have at least ___ means of egress provided for any enclosure.

a)

1

b)

2

c)

3

d)

4

69.

Which level of anesthesia is described as: A drug-induced state during which patients respond normally to verbal commands?

a)

General anesthesia

b)

Deep sedation/analgesia

c)

Moderate sedation/analgesia

d)

Minimal sedation (anxiolysis)

70.

New or replacement shutoff valves for medical gas pressure piping systems shall __________.

a)

Be quarter turn valves

b)

Be of materials suitable for the service

c)

Have extensions for brazing

d)

All of the choices are required

71.

Which of the following is labeled incorrectly?

a)

Instrument air with green background and white text

b)

Instrument air with red background and white text

c)

Medical air with yellow background and black text

d)

WAGD with violet background and white text

72.

The maintenance of a Category 1 medical gas system must be performed by individuals trained & certified by health care facility or a person certified in which of the following Code/Standard?

a)

ASSE 6040

b)

ASTM 6010

c)

AWS B-22

d)

CGA - 4.1

73.

The complete source of supply for a medical gas or vacuum system or a medical support gas system?

a)

Central supply system

b)

Compressed medical gases

c)

EOSC

d)

Medical air compressor

74.

The source valve on a cryogenic fluid source, shall be installed according to which standard?

a)

NFPA 55

b)

NFPA 99

c)

NFPA 101

d)

NFPA 70

75.

If a non-metallic connector is being used in a Category 1 health care facility to connect the manifold to the distribution piping, what is the maximum length (feet) permitted for the flexible connector?

a)

5 ft

b)

They shall be no longer than necessary

c)

3 ft

d)

The use of flexible connectors is not permitted

76.

Factory installed outlet tubes on station inlets shall not be less than ____NPS with 0.4 inch minimum inside diameter.

a)

1/4

b)

3/8

c)

1/2

d)

5/8

77.

A medical gas master or area alarm panel, should be set to actuate a(an) __________ indicator when the communication with the alarm-initiating device is disconnected.

a)

Audible

b)

Visual

c)

High and low

d)

Audible and visual

78.

After a final brazed connection in a positive pressure medical gas pipeline is made without a purge, an outlet in the immediate ______ zone of the affected portions of both the new and existing piping shall be tested.

a)

upstream

b)

downstream

c)

upstream and downstream

d)

parallel

79.

What is the standard gauge pressure (psi) for medical air gas service?

a)

0-300

b)

50-55

c)

15-30

d)

It varies with system type

80.

What is the standard gauge pressure (in. HgV) for WAGD service?

a)

12-24

b)

50-55

c)

15-30

d)

It varies with system type

81.

Station outlets in systems having nonstandard operating pressures shall be ______________.

a)

gas specific

b)

pressure specific

c)

self removing

d)

gas specific and pressure specific

82.

In those portions of systems intended to handle oxygen at gauge pressure greater than ________ psi, interconnecting hoses shall contain no polymeric materials.

a)

350

b)

335

c)

450

d)

435

83.

Which of the following is NOT an approved means of securing for all valves, other than those located in zone valve box assemblies?

a)

inaccessible above ceilings

b)

latched in their operating position

c)

Located in secure areas

d)

Locked in their operating position

84.

Refer to diagram 4. Area A would be classified as a __________.

a)

Patient care area

b)

Anesthetizing area

c)

Critical care area

d)

Waste disposal area

85.

The accuracy of digital indicators shall be +/- _____ % of the operating pressure at which they are used.

a)

1

b)

3

c)

5

d)

7

86.

Which source shall NOT be used to power the venturi of a WAGD system?

a)

Instrument air

b)

Medical Air

c)

Water

d)

Inert gas

87.

Medical air compressor systems shall have a pressure relief valve set at _____ percent above line pressure.

a)

20

b)

30

c)

40

d)

50

88.

All cryogenic fluid systems shall be provided with an auxiliary source connection point, of the same size as the main. Which statement is true of the connection point?

a)

It shall be located immediately on either side of the source valve

b)

It shall consist of a tee, a valve and a plug or cap

c)

It shall always be kept closed and secured

d)

It shall consist of a tee, a valve and a plug or cap and It shall normally be kept closed and secured

89.

Each set of wires from a master alarm shall NOT run ______ to the alarm initiating device they monitor.

a)

with interruption

b)

without interruption

c)

with or without interruption

d)

NFPA 99 does not specity

90.

Pressure/vacuum indicators shall be readable from a ___________ position

a)

sitting

b)

standing

c)

climbing

d)

sitting, standing or climbing

91.

When a single source supplies multiple free standing buildings,

where is the required location for the main line valve?

a)

At the source

b)

At the branch connection

c)

Inside each building served

d)

Outside each building served

92.

A single initiating device shall be permitted to actuate ________ master alarms.

a)

1

b)

2

c)

3

d)

multiple

93.

Each alarm shall be ___________ for its area of surveillance.

a)

wired

b)

labeled

c)

observed

d)

installed

94.

Inspection and testing shall be performed on all new piped gas systems, additions, renovations, temporary installations or repaired systems, to assure the facility that all applicable provisions of NFPA 99C have been adhered to and system integrity has been achieved or maintained. What is required of the of the individual doing the testing or inspecting?

a)

Have two years experience

b)

Have a documented process & procedure

c)

Be a certified tester

d)

None of the choices are correct

95.

Which of the following is an instrument air quality requirement?

a)

It shall be compliant with instrument air section in ANSI/ISA S-7.0.01

b)

It shall be compliant with medical air USP

c)

It shall be filtered to .7 micron

d)

It shall be dry to a dew point of -30º F

96.

A system used in dentistry for oral evacuation and nitrous oxide/oxygen scavenging.

a)

Category 4 vacuum pump system

b)

Dental vacuum/scavenging system

c)

Medical-surgical vacuum system

d)

WAGD system

97.

Hyperbaric chambers when used in a veterinary care facility, shall be classified as _________.

a)

Class A

b)

Class B

c)

Class C

d)

There is no classification for veterinary care

98.

What is the standard gauge pressure (in. HgV) for a combination medical-surgical vacuum/WAGD service?

a)

12-24

b)

15-30

c)

50-55

d)

It varies with system type

99.

Refer to diagram 3. What is the minimum distance requirement at letter C?

a)

10 feet

b)

15 feet

c)

20 feet

d)

25 feet

100.

What is the standard gauge pressure (psi) for nitrous oxide gas service?

a)

12-24

b)

15-30

c)

50-55

d)

0-300