1.

Minimum headroom shall be provided for all working spaces about service equipment, switchboards, panelboards or motor control centers except in service equipment or panelboards in dwelling units that do not exceed (a)   amperes.

2.

For equipment rated 1200 amperes or more 600 volts or less, containing overcurrent devices, switching devices or control devices, there shall be one entrance not less than _____ mm wide and _____ mm high at each end.

a)

6000, 200

b)

600, 2000

c)

200, 6000

d)

2000, 600

3.

In all cases the work space in front of electrical equipment shall permit at least a (a)   degree opening of equipment doors or hinged panels.

4.

Voltage to ground of 151-600 with exposed live parts on both sides of the working space must have a clear distance not less than which of the following:

a)

1200 mm

b)

1000 mm

c)

900 mm

d)

600 mm

5.

Conduit encased in a concrete trench is considered a (a)   location.

6.

The circuit conductors between the service entrance equipment or isolated generating plant and the branch circuit overload device or devices.

(a)  

7.

Unless specified otherwise, live parts of electrical equipment operating at (a)   volts or more shall be guarded.

8.

Where the required work space is doubled, _____ entrance(s) to the working space is/are required.

a)

1

b)

2

c)

3

d)

4

9.

What is the minimum working clearance on a circuit 120 volts to ground, exposed live parts on one side and no live or grounded parts on the other side of the working space?

a)

1200 mm

b)

600 mm

c)

1000 mm

d)

900 mm

10.

A piece of electrical equipment that is designed to operate at alternate intervals of (1) load and no load; or (2) load and rest; or (3) load, no load and rest is called _____ duty.

a)

Periodic

b)

Varying

c)

Intermittent

d)

Short time

11.

The elevation for unguarded live parts in a working space for equipment operating between 601 to 7500 nominal volts between phases is (a)   mm.

12.

The space measured horizontally above a show window must have at least one receptacle for each _____ linear mm.

a)

1800

b)

2400

c)

3600

d)

3000

13.

In each kitchen and dining area a receptacle outlet shall be installed at each counter space _____ mm or wider.

a)

900

b)

600

c)

1200

d)

300

14.

Floor boxes shall be considered to meet the requirements of the spacing of receptacles on walls if they are within _____ mm to the wall.

a)

450

b)

500

c)

600

d)

760

15.

For household ranges rated _____ kW or more rating, the minimum branch circuit rating shall be 40 amperes.

a)

8 3/4

b)

8

c)

4

d)

6

16.

In a residence, no point along the floor line in any wall space may be more than (a)   mm from an outlet.

17.

Overhead conductors, not supported by messenger wires, for festoon lighting shall not be smaller than ____.

a)

2.0 mm^2

b)

3.5 mm^2

c)

5.5 mm^2

d)

8.0 mm^2

18.

A service drop over a residential driveway shall have a minimum height of _____ mm.

a)

3000

b)

3600

c)

4500

d)

5500

19.

The minimum clearance for service drops, not exceeding 600 volts, over commercial areas subject to truck traffic is _____ mm.

a)

3000

b)

5500

c)

4500

d)

3600

20.

For open conductors of not over 600 volts, clearance from ground shall be _____ mm, above finished grade where the supply conductors have a nominal voltage limited to 150 volts to ground and accessible to pedestrians only.

a)

5500

b)

3600

c)

3000

d)

4500

21.

The minimum size service lateral to a branch circuit limited load is _____ copper.

a)

2.0 mm^2

b)

3.5 mm^2

c)

8.0 mm^2

d)

14.0 mm^2

22.

For an installation consisting of not more than two 2-wire branch circuits, the service disconnecting means shall have a rating of not less than _____ amperes.

a)

30

b)

100

c)

60

d)

20

23.

The height of a circuit breaker used as a switch shall not exceed _____ above the floor.

a)

1500 mm

b)

1200 mm

c)

2000 mm

d)

1350 mm

24.

Where used as switches in 120 volt and 277 volt fluorescent lighting circuits, circuit breakers shall be marked _____.

a)

UL

b)

AMPS

c)

SWD

d)

VA

25.

The minimum size of bonding jumper shall be ___ for copper and ___ for aluminum or copper-clad aluminum.

a)

8.0 mm2, 14.0 mm2

b)

14.0 mm2, 22.0 mm2

c)

2.0 mm2, 3.5 mm2

d)

5.5 mm2, 8.0 mm2

26.

Type _____ is a single or multiconductor solid dielectric insulated cable rated 2001 volts or higher.

a)

MV

b)

MC

c)

MI

d)

NM

27.

Type _____ cable is a factory assembly of one or more conductors, each individually insulated and enclosed in a metallic sheath of interlocking tape, or a smooth or corrugated tube.

a)

MV

b)

MC

c)

MI

d)

AC

28.

Intermediate metal conduit must be supported every (a)   mm.

29.

The bending radius for nonshielded cables operating at 4160v shall be less than _____ times the diameter.

a)

10

b)

8

c)

12

d)

6

30.

_____ cable shall be flame-retardant, moisture-resistant, fungus-resistant and corrosion-resistant.

a)

NM

b)

NMC

c)

MI

d)

USE