1.
MULTIPLE CHOICE QUESTION
1 min • 1 pt
An operative carrying out fault diagnosis would not need to be familiar with:
supply earthing system
schedule of test results
repair cost
voltage present
2.
MULTIPLE CHOICE QUESTION
1 min • 1 pt
Which of the following would not be required in a fault finding sequence:
time repair will take
safe isolation
testing
analysis of results
3.
MULTIPLE CHOICE QUESTION
1 min • 1 pt
A continuity test as part of fault diagnosis would be carried out with which instrument:
earth-fault loop impedance tester
high resistance ohmmeter
low resistance ohmmeter
RCD tester
4.
MULTIPLE CHOICE QUESTION
1 min • 1 pt
A loose termination could cause the following
short circuit between live conductors
overcurrent
arcing
operation of the protective device
5.
MULTIPLE CHOICE QUESTION
1 min • 1 pt
The guidance for test leads used on instruments is contained in
BS 7671
EAWR
HASAWA
GS38
6.
MULTIPLE CHOICE QUESTION
1 min • 1 pt
Which dead test would be carried out during intial fault diagnosis
RCD test
insulation resistance
functional
earth-fault loop impedance
7.
MULTIPLE CHOICE QUESTION
1 min • 1 pt
Whilst fault finding you check and discover the BS 3036 fuse protecting the circuit has ruptured with globules of copper spattered over the holder together with black carbon powder. The most likely fault would be:
short circuit
open circuit
loose termination
broken conductor