1.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

Appliances shall not be installed in a location subject to vehicle damage except____________.

45. a.when listed for that particular installation
46. b.when installed per the manufacturer’s installation instructions
47. c.where protected by an approved means
48. d.when installed behind steel barriers
303.4

2.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

Where the air-infiltration-rate is unknown, a room or space providing indoor combustion air requires a minimum volume of __________ cubic feet per 1,000 Btu/h of the appliance input rating.

57. a.15
58. b.25
59. c.50
60. d.75
304.5.1

3.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

Openings obtaining indoor combustion air from a different story require a total minimum free area of_________ square inch(es) per 1,000 Btu/h of the total input rating of appliances.

69. a.2
70. b.3
71. c.1
72. d.4
304.5.3.2

4.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

Where a space is provided outdoor combustion air through two openings, one opening must begin within _________ inches of the top and within ____________inches of the bottom of the enclosure.

73. a.3, 3
74. b.6, 6
75. c.12, 12
76. d.18, 18
304.6.1

5.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

Within dwelling units, unobstructed _____________ are permitted to convey combustion air.

97. a.shafts
98. b.stud and joist spaces
99. c.chases enclosing chimneys
100.           d.chimneys
304.11, Item 1 Exception

6.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

Where vehicles are capable of passing under an appliance installed in a public garage, the appliance shall be installed a minimum of ________________ inches higher than the tallest vehicle garage door opening.

1.      a.24
2.      b.18
3.      c.12
4.      d.6
305.4

7.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

Condensate waste and drain lines shall be not less than ________________ -inch internal diameter.

1.      a.1
2.      b.½
3.      c.⅝
4.      d.¾
307.3

Access all questions and much more by creating a free account

Create resources

Host any resource

Get auto-graded reports

Google

Continue with Google

Email

Continue with Email

Classlink

Continue with Classlink

Clever

Continue with Clever

or continue with

Microsoft

Microsoft

Apple

Apple

Others

Others

Already have an account?

Discover more resources for Professional Development