Liquid Cooling System for Data Center Commissioning

Authored by Hanna Awaluddin

Professional Development

Used 2+ times

Liquid Cooling System for Data Center Commissioning
AI

AI Actions

Add similar questions

Adjust reading levels

Convert to real-world scenario

Translate activity

More...

    Content View

    Student View

5 questions

Show all answers

1.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

What is the primary function of the Coolant Distribution Unit (CDU) in a Direct Liquid Cooling (DLC) architecture?

To act as a reservoir for all facility water in the data center

To directly cool the chips using facility water (FWS)

To isolate the facility water loop (FWS) from the IT coolant loop (TCS) and manage flow/pressure

To convert AC power to DC power for the liquid-cooled racks

2.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

Which of the following is the main reason for using a Propylene Glycol mixture (e.g., PG25) in the Technology Cooling System (TCS) secondary loop instead of pure facility water?

It has superior heat capacity compared to water

It is cheaper than De-ionized (DI) water

It provides necessary electrical conductivity for grounding

It provides corrosion and freeze protection, isolating the IT equipment

3.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

In a full-scale liquid cooling system commissioning sequence, what critical activity is typically performed during the high-load testing phases (Cx3, Cx5)?

Chemical flushing of the FWS primary loop

Performing a hydronic pressure test on the rack connections

Performing a heat load test (HLT) at 100% IT load using liquid-cooled load banks

CDU sensor calibration and alarm verification

4.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

What is the purpose of the multi-stage flushing process (Dynamic, Chemical, and DI water flushing) performed on the TCS piping?

To test the pipes for pressure leaks

To achieve system start-up and initial coolant circulation

To introduce the initial PG25 coolant mixture

To ensure the piping is free of debris, oils, and chemical residues before filling with the final coolant

5.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

Which loop is referred to as the primary cooling loop and is typically responsible for transferring heat to an external rejection source, such as a cooling tower?

Facility Water System (FWS)

Technology Cooling System (TCS)

Coolant Distribution Unit (CDU)

In-Row Cooler System (IRC)

Access all questions and much more by creating a free account

Create resources

Host any resource

Get auto-graded reports

Google

Continue with Google

Email

Continue with Email

Classlink

Continue with Classlink

Clever

Continue with Clever

or continue with

Microsoft

Microsoft

Apple

Apple

Others

Others

Already have an account?