Liquid Cooling System for Data Center Commissioning
Authored by Hanna Awaluddin
Professional Development
Used 2+ times

AI Actions
Add similar questions
Adjust reading levels
Convert to real-world scenario
Translate activity
More...
Content View
Student View
5 questions
Show all answers
1.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
What is the primary function of the Coolant Distribution Unit (CDU) in a Direct Liquid Cooling (DLC) architecture?
To act as a reservoir for all facility water in the data center
To directly cool the chips using facility water (FWS)
To isolate the facility water loop (FWS) from the IT coolant loop (TCS) and manage flow/pressure
To convert AC power to DC power for the liquid-cooled racks
2.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
Which of the following is the main reason for using a Propylene Glycol mixture (e.g., PG25) in the Technology Cooling System (TCS) secondary loop instead of pure facility water?
It has superior heat capacity compared to water
It is cheaper than De-ionized (DI) water
It provides necessary electrical conductivity for grounding
It provides corrosion and freeze protection, isolating the IT equipment
3.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
In a full-scale liquid cooling system commissioning sequence, what critical activity is typically performed during the high-load testing phases (Cx3, Cx5)?
Chemical flushing of the FWS primary loop
Performing a hydronic pressure test on the rack connections
Performing a heat load test (HLT) at 100% IT load using liquid-cooled load banks
CDU sensor calibration and alarm verification
4.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
What is the purpose of the multi-stage flushing process (Dynamic, Chemical, and DI water flushing) performed on the TCS piping?
To test the pipes for pressure leaks
To achieve system start-up and initial coolant circulation
To introduce the initial PG25 coolant mixture
To ensure the piping is free of debris, oils, and chemical residues before filling with the final coolant
5.
MULTIPLE CHOICE QUESTION
30 sec • 1 pt
Which loop is referred to as the primary cooling loop and is typically responsible for transferring heat to an external rejection source, such as a cooling tower?
Facility Water System (FWS)
Technology Cooling System (TCS)
Coolant Distribution Unit (CDU)
In-Row Cooler System (IRC)
Access all questions and much more by creating a free account
Create resources
Host any resource
Get auto-graded reports

Continue with Google

Continue with Email

Continue with Classlink

Continue with Clever
or continue with

Microsoft
%20(1).png)
Apple
Others
Already have an account?