INTERNATIONAL FUEL GAS CODE (Part 2)

Total questions: 28

Worksheet time: 14mins

Name
Class
Date
1.

CHAPTER 5: CHIMNEY & VENTS -

501.1 General :Scope

The construction, repair, maintenance and approval of masonry chimneys shall be regulated by the International ________________ Code . 

a)

Houses

b)

Building

c)

Repair

d)

Maintenance

2.

CHAPTER 4 : GAS PIPING AND INSTALLATION

416 : Overpressure Protection Device

For appliance designed to operate at 14 inches w.c. or less, overpressure protection devices are required only if the service supply pressure exceeds _________psi.  

a)

1 psi

b)

2 psi

c)

3 psi

d)

4 psi

3.

CHAPTER 4 : GAS PIPING INSTALLATIONS

415.1 - Support of Piping

The maximum spacing between hangers supporting ¾ -inch steel gas piping is _________ feet.

a)

6 feet

b)

7 feet

c)

8 feet

d)

9 feet

4.

CHAPTER 4 : GAS PIPING INSTALLATION

413.4.3 Compressed Natural Gas Motor Vehicle Fuel-Dispensing Facilities

Where residential compressed natural gas (CNG) fueling appliances are located indoors, a methane gas detector shall be located within____________ inches of the highest point of the room or space.

a)

3 inches

b)

5 inches

c)

6 inches

d)

9 inches

5.

CHAPTER 4 : GAS PIPING INSTALLATIONS

SECTION 412-Liquefied petroleum gas motor vehicle fuel-dispensing facilities

Self-service LP-gas motor vehicle dispensing systems shall be provided with an emergency shutoff switch located within _________feet of but not less than________ feet, from dispensers.

a)

100 feet, 20 feet

b)

150 feet, 20 feet

c)

100 feet, 25 feet

d)

150 feet, 25 feet

6.

CHAPTER 4 : GAS PIPING INSTALLATION

413.3.4 - Residential Fueling Installations

For residential CNG fueling appliances installed indoors, the capacity shall not exceed ___________ standard cubic feet per minute of natural gas.

a)

3

b)

4

c)

5

d)

6

7.

CHAPTER 4 : GAS PIPING INSTALLATIONS

406. - Inspection, Testing and Purging

The highest end of the scale for mechanical gauges used to measure test pressures must not be greater than ________ times the test pressure.

a)

3 times

b)

5 times

c)

10 times

d)

15 times

8.

CHAPTER 4 : GAS PIPING INSTALLATIONS

406 - Inspection, Testing and Purging

The test pressure for gas piping shall be not less than 1 ½ time the proposed maximum working pressure, but not less than ________psig, irrespective of design pressure.

a)

3 psig

b)

55 psig

c)

100 psig

d)

125 psig

9.

CHAPTER 2 : DEFINITIONS

202 - General Definition

The installation of pipe, valves or fittings installed on a premise or in a building and utilized to convey fuel gas.

a)

Fuel Piping

b)

Water Piping

c)

Gas Piping

d)

Air Piping

10.

CHAPTER 2 : DEFINITIONS

202 - General Definitions

Any location is considered to be a fire hazard for flammable vapors, dust, combustible fibers or other highly combustible substances.

a)

Hazardous Location

b)

Dangerous Place

c)

Prohibited Location

d)

Uninhabitable Location

11.

CHAPTER 3 : GENERAL REGULATIONS

305 - Installations

Appliances located in public garages, motor fuel-dispensing facilities, repair garages or other areas frequented by motor vehicles shall be installed a minimum of ________feet above the floor.

a)

12 feet

b)

10 feet

c)

8 feet

d)

6 feet

12.

CHAPTER 2 : DEFINITIONS

202- General Definitions

A metal-to-metal compression ___________ in which a conical spread is made on the end of a tube that is compressed by a _________ nut against a mating flare.

a)

joint,

flare

b)

joint,

flame

c)

bonded,

flare

d)

bonded,

flake

13.

CHAPTER 3 : GENERAL REGULATIONS

306 - Access and Service Space

Where obtaining outdoor combustion air through horizontal ducts, each opening shall have a minimum free area of not less than 1 square inch per ________ Btu/h of total input rating of all appliance closure.

a)

2000 Btu/h

b)

2500 Btu/h

c)

3000 Btu/h

d)

4000 Btu/h

14.

CHAPTER 3 : GENERAL REGULATIONS

304 - Combustions, Ventilations and Dilution

For indoor combustion air, the volumes of spaces in different stories shall be considered as ___________  ___________ where connected by openings indoors or floors having a total minimum free area of 2 square inches per 1,000 Btu/h of total input rating of all appliances

a)

Communicating Spaces

b)

Combining Spaces

c)

Conducting Spaces

d)

Contributions Spaces

15.

CHAPTER 3 : GENERAL REGULATIONS

304 - Combustion, Ventilations and Dilution

One permanent opening for obtaining outdoor combustion air shall have a minimum free area of 1 square inch per ________Btu/h of the total input rating of all appliances located in the enclosure.

a)

1000 Btu/h

b)

2000 Btu/h

c)

3000 Btu/h

d)

4000 Btu/h

16.

CHAPTER 3 : GENERAL REGULATIONS

304 : Combustions, Ventilations and Dilution

Outdoor combustion air provided by a mechanical air supply system requires a supply rate not less than ________ cubic feet per minute per 1000 Btu/h of total input rating of all appliances located within the space.  

a)

0.25 cubic

b)

0.35 cubic

c)

0.45 cubic

d)

0.55 cubic

17.

CHAPTER 3 : GENERAL REGULATIONS

304 - Combustions, Ventilations and Dilution Air

Each of the appliances shall be __________with the mechanical combustions air supply system to prevent main burner operation when the mechanical air supply system is not in operation

a)

interconnected

b)

interlocked

c)

international

d)

intercom

18.

CHAPTER 3: GENERAL REGULATIONS

304 - Combustion, Ventilations, and Dilution Air

The standard method for calculating indoor combustion air cannot be used where the air infiltration rate is known to be less than ______________ air changes per hour (ACH).

a)

0.30

b)

0.40

c)

0.50

d)

0.60

19.

CHAPTER 4 : GAS PIPING INSTALLATIONS

403 - Piping Materials

For flanged joints, materials for __________ shall be capable of withstanding the design temperature and pressure of the piping system and the chemical constituents of the gas being conducted.

a)

gaskets

b)

bolts

c)

valves

d)

fittings

20.

CHAPTER 4 : GAS PIPING INSTALLATIONS

403 - Piping Materials

Field drilled and tapped pipe fittings are permitted under limited conditions when the work is performed by the ____________  _____________.  

a)

foreman instructions

b)

manager instruction

c)

company supplier

d)

gas supplier

21.

CHAPTER 4 : GAS PIPING INSTALLATIONS

403 : Piping Materials

The maximum size of a metallic threaded fitting is ___________ inches.

a)

4 inches

b)

5 inches

c)

6 inches

d)

7 inches

22.

CHAPTER 4 : GAS PIPING INSTALLATIONS

403- Piping Materials

The type of metallic piping joint used shall be suitable for the ________________- ______________ conditions.

a)

mechanical strength

b)

press connect

c)

Pressure temperature

d)

pressure expansion

23.

CHAPTER 4 : GAS PIPING INSTALLATIONS

403 - Piping Materials

Pipe, tubing and fittings shall be free from cutting burrs and ______________ in structure or threading, and shall be thoroughly brushed, and chip and scale blown.

a)

defects

b)

good quality

c)

useful

d)

dangerous

24.

CHAPTER 4 : GAS PIPING INSTALLAMENTS

403: Piping Materials

_________ _________ and __________  __________ __________ plastic pipe, tubing and fitting shall not be used to supply fuel gas.  

a)

polyvynil chloride (PVC)

b)

Chlorinated polyvynil chloride  (CPVC)

c)

Molecularly Oriented PVC

(PVC-O)

d)

High Impact PVC (PVC-Hi)

25.

CHAPTER 4 : GAS PIPING INSTALLATIONS

403: Piping Materials

_________ - _____________ pipe shall not be use for gas piping.

a)

wrought iron

b)

cast iron

c)

alloy

d)

copper

26.

CHAPTER 3 : GENERAL REGULATIONS

305 - Installations

Equipment and appliance having an ignition source shall be elevated such that the source of ignition is not less than____________ inches above the floor in hazardous locations and public garages, private garages, repair garages, motor fuel-dispensing facilities and parking garages.  

a)

12

b)

15

c)

18

d)

21

27.

CHAPTER 2 : DEFINITIONS

202 : General Definitions

A completely self-contained appliance for heating air through metal to the air, and designed to supply heated air through ducts to spaces remote or adjacent to the appliance location.

a)

furnace

b)

furnace central

c)

furnace enclose

d)

furnace plenum

28.

CHAPTER 2 : DEFINITIONS

202 : General Definitions

An air compartment or chamber to which one or more ducts are connected and that forms part of an air distribution system.

a)

furnace

b)

furnace central

c)

furnace plenum

d)

furnace enclosed