BL M-02 FIRE CODE FLASHCARDS 02

Total questions: 51

Worksheet time: 26mins

Name
Class
Date
1.

When was the Fire Code of the Philippines effective?

a)

Nov 17, 2009

b)

Jan 20, 2009

c)

Jan 19, 2008

d)

Nov 20, 2004

e)

None of the Above

2.

When was the IRR of RA 9514 effective?

a)

Nov 17, 2009

b)

Jan 20, 2009

c)

Jan 19, 2008

d)

Nov 20, 2004

e)

None of the Above

3.

Which is not covered by RA 9514?

a)

All persons

b)

design and installation of MEPS relative to Fire Protection

c)

Fire safety planning, design, construction, repair, maintenance, rehabilitation and demolition

d)

Petroleum industry installation

e)

None of the Above

4.

What is FALAR?

a)

Fire and Life Assessment Report

b)

Fire Alarm Location And Route

c)

Fire and Life Safety Assessment Report

d)

Fire Assessment And Life Safety Assurance Report

e)

None of the Above

5.

Required for all private and public buildings, facilities and structures to be constructed or being constructed

a)

FALAR 1 & 2

b)

FALAR 1 & 3

c)

FALAR 2 & 3

d)

FALAR 1

e)

None of the Above

6.

Required for all existing private and public buildings, facilities or structures with occupancy of at least 50 persons.

a)

FALAR 1 & 2

b)

FALAR 1 & 3

c)

FALAR 2 & 3

d)

FALAR 3

e)

None of the Above

7.

Any qualified person, recognized by the BFP, engaged in, but not limited to, the design, construction, installation, repair, and maintenance, assessment, and rehabilitation of fire safety construction, suppression and control systems, or employed as a safety officer of public and private establishments/companies.

a)

Fire Safety Officer

b)

Fire Safety Practitioner

c)

Fire Safety Inspector

d)

Fire Safety Chief

e)

None of the Above

8.

A collective term that is used to refer to a group of firefighters, primarily performing fire suppression activities in areas such as but not limited to community/barangay, company, and other government and non-government establishments.

a)

Fire Volunteer

b)

Fire Volunteer Organization (FVO)

c)

Fire Brigade

d)

Fire Fighters

e)

None of the Above

9.

An organized group of private firefighters recognized by the BFP, who have voluntarily formed themselves to perform fire-related activities

a)

Fire Volunteer

b)

Fire Volunteer Organization (FVO)

c)

Fire Brigade

d)

Fire Fighters

e)

None of the Above

10.

A person who voluntarily enters into firefighting service through a Fire Volunteer discipline as that of BFP firefighters

a)

Fire Volunteer

b)

Fire Volunteer Organization (FVO)

c)

Fire Brigade

d)

Fire Fighters

e)

None of the Above

11.

All business establishments employing at least ____ persons shall establish an organization of fire brigade to deal with fire and other related emergencies.

a)

50

b)

100

c)

30

d)

40

e)

None of the Above

12.

Any condition or act which increases or may cause an increase in the probability of the occurrence of fire, or which may obstruct, delay, hinder or interfere with fire fighting operations and the safeguarding of life and property

a)

Fire Trap

b)

Fire Hazard

c)

Fire Spread

d)

Flammability

e)

None of the Above

13.

any street, alley or other strip of land unobstructed from the ground to the sky, deeded, dedicated or otherwise permanently appropriated for public use.

a)

Public Area

b)

Public Access

c)

Public Way

d)

Public Lane

e)

None of the Above

14.

time in which flame will spread over the surface of a burning material

a)

Fire Resistance Rating

b)

Flame Spread Rating

c)

Smoke Developed Rating

d)

Fire Spreading Rating

e)

None of the Above

15.

time duration that a material or construction can withstand the effect of a hundred fire test

a)

Fire Resistance Rating

b)

Flame Spread Rating

c)

Smoke Developed Rating

d)

Fire Spreading Rating

e)

None of the Above

16.

a rating of combustible material based on the density and volume of smoke developed within a certain period of time when its surface is ignited

a)

Fire Resistance Rating

b)

Flame Spread Rating

c)

Smoke Developed Rating

d)

Fire Spreading Rating

e)

None of the Above

17.

means of egress that leads from any occupied point in the building or structure to an exit

a)

Exit Access

b)

Exit

c)

Exit Discharge

d)

Exit Components

e)

None of the Above

18.

portion of a means of egress that is separated by construction or equipment as required to provide a protected way of travel to an exit discharge.

a)

Exit Access

b)

Exit

c)

Exit Discharge

d)

Exit Components

e)

None of the Above

19.

portion of a means of egress between the termination of an exit and a public way

a)

Exit Access

b)

Exit

c)

Exit Discharge

d)

Exit Components

e)

None of the Above

20.

shall be constructed as an integral part of the building or shall be permanently affixed thereto

a)

Exit Access

b)

Exit

c)

Exit Discharge

d)

Exit Components

e)

None of the Above

21.

a passageway serving as a required exit, enclosed by walls of fire-resistive construction

a)

Exit Corridor

b)

Exit Door

c)

Exit Staircase

d)

Exit Passageway

e)

None of the Above

22.

door providing access to a means of egress, swinging in the direction of exit travel and usually equipped with a panic hardware

a)

Exit Corridor

b)

Exit Door

c)

Exit Staircase

d)

Exit Passageway

e)

None of the Above

23.

a stairway leading to an exit passageway, exit court, or a public way having no openings other than required exits and enclosed by fire-resistive construction as required for the walls, floors and ceiling of the building served

a)

Exit Corridor

b)

Exit Door

c)

Exit Staircase

d)

Exit Passageway

e)

None of the Above

24.

a yard or court providing egress to a public way for one or more required exits.

a)

Exit Corridor

b)

Exit Court

c)

Exit Staircase

d)

Exit Passageway

e)

None of the Above

25.

what is the fire resistance rating needed for 3 stories or less

a)

3-hour

b)

2-hour

c)

1-hour

d)

1 1/2-hour

e)

None of the Above

26.

what is the fire resistance rating needed for 4 or more stories?

a)

3-hour

b)

2-hour

c)

1-hour

d)

1 1/2-hour

e)

None of the Above

27.

The maximum number of persons that may be in the space at any time

a)

Maximum Occupant Load

b)

Maximum Load

c)

Occupant Load

d)

Occupancy Load

e)

None of the Above

28.

the number computed by dividing the floor area assigned to that use by the occupant load factor

a)

Maximum Occupant Load

b)

Maximum Load

c)

Occupant Load

d)

Occupancy Load

e)

None of the Above

29.

projections of not more that ____ at a maximum height of ____mm within the means of egress on each side shall be permitted.

a)

120mm; 900mm

b)

115mm; 850mm

c)

150mm;960mm

d)

114mm;965mm

e)

None of the Above

30.

(2 exits or exit access doors) shall be located at a distance from one another note less than ____ of the length of the maximum overall diagonal dimension of the building

a)

3/4

b)

1/2

c)

2/3

d)

1/4

e)

None of the Above

31.

In buildings protected throughout by an approved supervised automatic sprinkler system, the minimum separation distance between two exits or exit access doors shall not be less than ____ the length of the maximum overall diagonal dimension of the building.

a)

3/4

b)

1/2

c)

1/3

d)

1/4

e)

None of the Above

32.

What is the minimum travel distance to an exit if the building is not protected with AFSS?

a)

30m

b)

46m

c)

52m

d)

61m

e)

None of the Above

33.

What is the minimum travel distance to an exit if the building is protected with AFSS?

a)

30m

b)

46m

c)

52m

d)

61m

e)

None of the Above

34.

A door from a room to an exit or to a way of exit access shall be of the ____?

a)

dual-hinge, swinging type

b)

side-hinge, swinging type

c)

side-hinge, sliding type

d)

single-hinge, sliding type

e)

None of the Above

35.

A door from a room to an exit or to a way of exit access shall swing with exit travel for ____ occupant load.

a)

50+

b)

10+

c)

100+

d)

60+

e)

None of the Above

36.

Where shall all exits terminate directly?

a)

public way or fire lane

b)

fire lane

c)

exit discharge or exit corridor

d)

public way or exit discharge

e)

None of the Above

37.

An area affording safety from fire or smoke coming from the area from which escape is made

a)

Area of Safety

b)

Center of Refuge

c)

Area of Refuge

d)

Safety Space

e)

None of the Above

38.

during its swing, any door in a means of egress shall leave not less than _____of the required width of an aisle, corridor, passageway, or landing unobstructed

a)

1/2

b)

1/3

c)

1/4

d)

2/3

e)

None of the Above

39.

There shall be reentry mechanism every ____ that provide a way out of the exit stairway

a)

2 floors

b)

3 floors

c)

4 floors

d)

5 floors

e)

None of the Above

40.

The elevation of the floor surfaces on both sides of a door shall not vary by more than ____?

a)

1.2cm

b)

1.5cm

c)

1.15cm

d)

1.3cm

e)

None of the Above

41.

Thresholds at doorways shall not exceed ____ in height

a)

1.2cm

b)

1.5cm

c)

1.15cm

d)

1.3cm

e)

None of the Above

42.

Raised thresholds and floor level changes in excess of ___ doorways shall be beveled with a slope not steeper than 1 in 2

a)

10mm

b)

5mm

c)

6mm

d)

9mm

e)

None of the Above

43.

Total cumulative occupant load assigned to the stair width for less than 2000 persons (in mm)

a)

1200mm

b)

1120mm

c)

1000mm

d)

1150mm

e)

None of the Above

44.

Total cumulative occupant load assigned to the stair width for more than 2000 persons (in mm)

a)

1420mm

b)

1500mm

c)

1450mm

d)

1520mm

e)

None of the Above

45.

maximum height between landings for existing stairs

a)

3600mm

b)

2550mm

c)

3660mm

d)

2880mm

e)

None of the Above

46.

Curved stairs shall be permitted as a component in a means of egress provided that the depth of tread is not less than ____ at a point ____ from the narrowest end of the tread.

a)

290mm ; 310mm

b)

250mm ; 300mm

c)

240mm; 320mm

d)

280mm ; 305mm

e)

None of the Above

47.

Curved stairs shall be permitted as a component in a means of egress provided that the smallest radius is not less than _____

a)

half the stair width

b)

twice the stair width

c)

thrice the stair width

d)

a third of the stair width

e)

None of the Above

48.

Spiral Stairs: riser height and tread depth

a)

160mm;180mm

b)

200mm;200mm

c)

180mm;280mm

d)

170mm;250mm

e)

None of the Above

49.

Spiral Stairs: at the outer side of the stairways, an additional ____ of width shall be provided clear to the other handrail

a)

260mm

b)

265mm

c)

250mm

d)

275mm

e)

None of the Above

50.

Which side is the outer handrail of descending users for spiral stairs?

a)

depends on orientation

b)

left

c)

right

d)

diagonal

e)

None of the Above

51.

every tread less than 25cm shall have a nosing or an effective projection of approximately ____over the level immediately below.

a)

30mm

b)

25mm

c)

12.7mm

d)

23mm

e)

None of the Above