wayground logo

Free Printable Worksheets

Font size

S
M
L
XL
Worksheets

POWER PLANT

Total questions: 199

Worksheet time: 2hrs 40mins

Name
Class
Date
1.

What do you call the protective angle between the Overhead ground wire and the power cable in the Transmission tower

a)

shielding angle

b)

surge angle

c)

clearing angle

d)

arcing angle

2.

Disconnecting switch is provided for proper protection of electric substations and power plant. What is its main function.

a)

for protection of circuit breaker

b)

for maintenance purpose

c)

to break the system under fault

d)

for complete isolation

3.

The highest magnitude of fault current will determine the size of _________, while the lowest magnitude will determine the size of_____________.

a)

fuse, relay

b)

circuit breaker, isolator

c)

circuit breaker, relay

d)

relay, circuit breaker

4.

The PTs of a 220 kV transmission line have ratio of 132.76 kV: 66.375 V and are connected wye-wye. A voltmeter connected line to ground reads 66 V, what is the transmission line voltage?

a)

223.15 kV

b)

220.10 kV

c)

228.63 kV

d)

225.25 kV

5.

The transfer bus scheme has the following characteristics EXCEPT one. Which one of this?

a)

It allows better continuity of service as compared with the single bus

b)

It allows the disconnection of circuit breakers for maintenance without Interrupting the service

c)

It is more flexible

d)

It is more costly than that of the single bus system

6.

It is more costly than that of the single bus system

a)

Even with a circuit breaker failure, a station shutdown will not result.

b)

It gives more flexibility

c)

It reduces the likelihood of extended outages of any circuit due to circuit breaker trouble

d)

It permits breaker maintenance without feeder outage.

7.

A large electric power distribution system is protected against surges and faults by

a)

high-speed relays detecting the trouble

b)

protective gaps crossing drain cells

c)

protective relays operating without a time delay

d)

radio communication system using flow frequency

8.

Which of the following steps is used for isolating a circuit breaker for maintenance purposes?

a)

pull the substation fuses

b)

turn off the main generator

c)

open the disconnect switches

d)

ground the auxiliary contacts

9.

In a generating and distribution system, current balance is provided by protective zones which are

a)

monitored by differential relays

b)

used to eliminate reflections on short transmission lines

c)

used to trip all circuit breakers in the system

d)

isolated during fault by disconnect switches

10.

For protection of parallel feeders fed from one end the relays required are:

a)

Directional relay at both the ends.

b)

Non-directional relays at the source end and directional relays at the load end

c)

Directional relays at the source end and non-directional at the load end.

d)

Non-directional relays at both the ends

11.

If a fixed amount of power is to be transmitted over a certain length with fixed power loss, it can be said

a)

the volume of the conductor required is proportional to voltage only

b)

the volume of the conductor is inversely proportional to voltage and that of power factor of load

c)

the volume of conductor required is inversely proportional to the square of voltage and that of the power factor of load

d)

the volume of the conductor is proportional to square of the voltage and directly proportional to power factor of load

12.

Assuming the constant efficiency transmission, if the voltage is increased n times, the size of the conductor would be

a)

reduced to 1/n2 that of the original

b)

reduced to 1/n that of the original

c)

increased to n2 that of the original

d)

increased to n times that of the original

13.

In a distribution system, if the synchronous capacitors are to be used for improving the power factor, the correct location would be

a)

at the receiving end

b)

at the sending end

c)

in middle of the transmission line

d)

none of the above

14.

In limiting case, the maximum cost of the phase advancing plant that would justify its installation is when its working cost is

a)

less than the working cost of generating plant to give the same increase in power

b)

equal to working cost of the generating plant to give the less increase in power

c)

equal to the working cost of generating plant to give the same increase in power

d)

greater than the working cost of the generating plant to give more increase in power

15.

The synchronizing power developed in the parallel operation of the alternators will be maximum when

a)

the armature reactances equal to their resistances

b)

the armature have less reactances than their resistances

c)

the armature have more reactances than their resistances

d)

the resistances of armatures are zero

16.

The actual division of the total kW load between alternators in power plant running in parallel depends upon the

a)

voltage-load characteristic

b)

a and b both

c)

speed-load characteristic

d)

a or b

17.

Natural Uranium contains

a)

50% U235

b)

0.7% U235

c)

0.7% U235

d)

100% U235

18.

Which of the following will affect the transfer of the real power between the stations if they are interconnected?

a)

Reactance

b)

In-phase voltage boost

c)

Quadraturel voltage

d)

angular displacement between stations

19.

The size of the feeder is determined primarily by

a)

the voltage across the feeder

b)

the percentage variation of voltage in the feeder

c)

the current it is required to carry

d)

the distance over which the transmission is made

20.

If the voltage is increased n times, the current in the feeder is reduced to (for a given power delivered)

a)

sqr root n times of the original

b)

1/n times of the original

c)

1/n^2 times of the original

d)

1/ sqr root n times of the original

21.

In the d.c. three wire transmission system the cross-section of the neutral is generally

a)

⅓ of the outer conductors

b)

½ of the outer conductors

c)

¼ of the outer conductors

d)

equal to the outer conductors

22.

The Metal clad is related to

a)

Amplidyne

b)

Switchgear system

c)

Synchros

d)

Relays

23.

The power transmission capacity of the transmission line is

a)

inversely proportional to the square of the voltage

b)

inversely proportional to the voltage

c)

proportional to the square of the operating voltage

d)

proportional to the voltage

24.

Which of the following power plant has the maximum efficiency?

a)

MHD

b)

Atomic Reactor

c)

Hydro-electric power plant

d)

Thermal power plant

25.

The reactors used in most power station specially in HVDC is to limit the short circuit current in the alternators have very small resistance in comparison to reactance

a)

to improve power factor

b)

because the high resistance will not help to limit the short circuit current

c)

to avoid the energy waste

d)

because the high resistance will raise the temperature and insulation of reactor will be spoiled

26.

The earthing transformer is used

a)

to provide artificial neutral earthing where the neutral points of the three phase system are not accessible

b)

to avoid the harmonics in the transformers

c)

to improve the current capacity of the neutral wire

d)

none of the above

27.

To protect the power transformer (Y-Y, with neutral earthed) in power station against fault, the current transformer will have

a)

Delta-delta connection

b)

Star-star connection

c)

Star-delta connection

d)

Delta-star connection

28.

To protect the power transformer (Delta-delta) against fault, the current transformer will have

a)

Delta-delta connection

b)

Star-star connection

c)

Delta-star connection

d)

Star-delta connection

29.

Which of the following power system distribution gives the greater reliability?

a)

ring system of the distribution

b)

radial system of the distribution

c)

D.C. three wire system of the distribution

d)

A.C. three phase four wire system

30.

The diversity factor is defined as the

a)

Average demand / Maximum demand

b)

Sum of consumers maximum demand / Maximum load on the station

c)

Maximum load on the station / Sum of consumers maximum demand

d)

Average demand / Maximum load on the station

31.

The power intended to be available even under emergency condition is called

a)

spinning reserve

b)

firm power

c)

cold reserve

d)

hot reserve

32.

Which of the following generating stations has the minimum running cost?

a)

Nuclear power station

b)

Thermal power station

c)

Diesel power plant

d)

Hydro-electric station

33.

Overfluxing protection is recommended for

a)

auto-transformer of the power plant

b)

Distribution transformer

c)

generator transformer of the power plant

d)

station transformer of the power plant

34.

Which of the following statements is true if restricted earth fault protection is provided to star winding of the generator transformer

a)

in fact CTs are not required at all as the fault current is not very high

b)

one CT is provided in the neutral

c)

one Ct in each phase and fourth in the neutral are provided and their secondaries are connected in parallel

d)

two CTs are provided, one in R-phase and other Y phase with a CT in neutral

35.

in fact CTs are not required at all as the fault current is not very high

a)

improve impedance

b)

compensate line capacitive reactance

c)

compensate line inductive reactance

d)

improve line voltage

36.

High water level of a boiler drum can damage

a)

turbine and steam line

b)

turbine only

c)

boiler tubes

d)

none of the above

37.

Which of the following statements is true?

a)

Shunt reactors are used to reduce the line impedance

b)

Shunt reactors are used to eliminate line to ground capacitance

c)

Shunt reactors are used for power factors improvement.

d)

Shunt reactors are used to control the line voltage.

38.

When a stator neutral of a generator is earthed through a distribution transformer, the stator earth fault is detected through

a)

an over-current relay connected across the secondary of the transformer

b)

an under-voltage relay connected across the secondary of the transformer

c)

an over-voltage relay connected across the secondary of the transformer

d)

none of the above

39.

f high pressure heaters of steam cycle in power plant have high water level, what precaution shall be taken.

a)

bypass the heater from water side and close extraction value

b)

rip the boiler feed pump

c)

trip the boiler

d)

trip the turbine

40.

Which one of the following statements is not true?

a)

Corona loss and radio and TV interference with D.C. transmission is less

b)

Fault levels in an all a. c system are less than in an a. c system with a D.C. link operating

c)

Large systems may be interconnected with d. c link of small capacity

d)

Limitation on the critical length of underground cables for use in A. C no longer exists if D.C transmission by cables is used.

41.

Advantage of power system interconnection is

a)

Optimization of machine can be done properly

b)

Fewer machines are required as reserve for operation at peak loads

c)

Large size circuit breakers are required because of large short-circuit currents

d)

Machines of one system remain in step with machines of another system

42.

. Economic studies have shown that D.C. transmission is cheaper than a. c transmission for lengths

a)

beyond 1200 km

b)

beyond 600 km

c)

less than 100 mile

d)

below 300 km

43.

Governors for controlling the speed of power generation units provide

a)

A flat speed -load characteristics

b)

Speed is proportion with the load

c)

An increase of speed with increasing load

d)

A decrease of speed with increasing load

44.

When two identical generating units are operated in parallel on governor control, and one machine has a 5% governor droop and the other a 10 % droop , the machine with the greater governor droop will

a)

Share load equally with the other machine

b)

Tend to take the larger portion of load changes

c)

Tend to take the greater portion of load changes

d)

Tend to take the lesser portion of load changes.

45.

On load-frequency control installations, error signals are developed proportional to the frequency error. If frequency declines , the error signal will act to

a)

Increase impedance of the line

b)

Increase generator voltages

c)

Increase prime move input to the generators

d)

Reduce prime mover input to the generators

46.

When inter-connected power systems operate with tie-line bias, they will respond to

a)

Frequency changes only

b)

Tie-line load changes only

c)

Drooping voltage

d)

Both frequency & tie -line load changes

47.

When generating units in a power plant are loaded with equal incremental costs, the cost of generation is

a)

maximum

b)

minimum

c)

zero

d)

not affected

48.

Incremental heat - rate curves for thermal generating units are used to determine the

a)

Optimal cost

b)

fuel cost in P/hour

c)

none of the above

d)

values to which the units should be loaded to decrease the fuel costs to a minimum

49.

In economic operation of a power system , the effect of increased penalty factor between a generating plant and system load centre is

a)

To maintain power factor of the plan

b)

to decrease the load on the generating plant

c)

to increase the load on the plant

d)

to hold the plant load constant.

50.

Non-conventional source-based power plants are generally best suited for

a)

Island

b)

Working with the nearby power grid

c)

Operation with similar plants irrespective of length of connecting transmission system

d)

Isolated operation from the power grid

51.

Running cost of a hydro plant with respect to that of a thermal plant is

a)

Less

b)

Varying from installation to installation

c)

equall

d)

More

52.

Pick up the odd plant from the following

a)

Steam

b)

Tidal

c)

Hydro

d)

Nuclear

53.

Pick up the odd plant from the following:

a)

Wind turbine generator plant

b)

Tidal

c)

Steam

d)

Solar

54.

The role of the economiser is to pre-heat

a)

Air used for combustion

b)

Boiler feed water

c)

Pulverised coal

d)

provide clean air

55.

Superheater & reheater are used to

a)

decrease efluent

b)

heat air used for combustion

c)

heat boiler feed water

d)

improve the condition of steam

56.

Governor is used with the steam turbine to regulate

a)

Steam pressure

b)

Steam temperature

c)

Speed

d)

Power output

57.

Cooling of 500 MW turbo-generators is usually done by the following coolants

a)

Water only

b)

Nitrogen & hydrogen

c)

Carbon dioxide & hydrogen

d)

Hydrogen & water

58.

The specific speed of a hydro turbine depends on

a)

Actual speed

b)

Output power

c)

Actual speed ,head of operation & output power

d)

Head of operation

59.

The most common type of hydro turbine with a moderate value of the specific speed is

a)

Pelton

b)

Kaplan

c)

wind

d)

Francis

60.

Pumped storage hydroelectric plant can be operated with

a)

Upstream reservoir only

b)

downstream reservoir only

c)

with both as above

d)

none of the above

61.

Hydro-generators are usually

a)

Bipolar machine

b)

Salient pole machines

c)

Homopolar machines

d)

Round rotor machines

62.

Heavy water in a nuclear reactor is used for

a)

Moderation only

b)

Cooling and shielding radiation

c)

Moderation & shielding radiation

d)

Cooling & moderation

63.

The size and weight per unit power of a fast breeder reactor in comparison to a reactor of any of the thermal types is

a)

more or less the same

b)

Much less

c)

Much more

d)

always zero

64.

Compared to turbines in the conventional coal-fired thermal stations, nuclear power plant turbines use steam at

a)

lower pressure & temperature

b)

higher pressure & temperature

c)

higher power factor

d)

higher temperature & lower pressure

65.

Gas turbine temperature corresponds to

a)

Around 66000 deg C

b)

Around 1000 deg.C

c)

Superheated steam temperature of 550 deg.C

d)

Boiling water temperature of 100 deg.C

66.

Gas turbine works on

a)

Carnot cycle

b)

Rankine cycle

c)

Roel cycle

d)

Brayton cycle

67.

The HVDC converter

a)

Consumes as much reactive power as real power

b)

Consumes 50% of the real power

c)

Does not consume reactive power

d)

Is not economical

68.

A back to back HVDC link can be advantageous compared to AC primarily because

a)

It is costly

b)

Of stability considerations

c)

It is cheaper

d)

Of controlled power glow

69.

A 12-pulse bridge is preferred in HVDC because

a)

It results in better power factor

b)

cheaper

c)

Series connection of converters on D.C. side is better

d)

It eliminates certain harmonics

70.

Fault on a two terminal DC link is removed by

a)

Current chopping

b)

Breakers on DC side

c)

Current control of converters

d)

Breakers on AC side

71.

From the economic point of view , a power system should have a load factor

a)

zero

b)

About 0.12

c)

About 1

d)

About 0.5

72.

From the economic point of view , a power system should have a diversity factor

a)

Greater than one

b)

Always constant

c)

Much less than 1

d)

Nearly equal to but less than one

73.

Peak load hydro power plants compared to base load thermal plants have plant capacity factor

a)

Almost equal

b)

Much higher

c)

Always constant

d)

Much lower

74.

Run-of-river plants are used for

a)

Near base load

b)

Base load operation

c)

Regulating plan

d)

Peak load operation

75.

The two-part tariff is based on

a)

MVArH

b)

MW and MVar

c)

MW and MVA

d)

MWH and MVA

76.

SF6 gas has excellent heat transfer properties because of its:

a)

Low cost

b)

High gaseous viscosity.

c)

Higher molecular weight.

d)

Low density

77.

In order to have lower cost of electrical energy generation:

a)

The load factor and diversity factor should be high

b)

The load factor should be high but diversity factor low.

c)

The load factor and diversity factor should be low.

d)

The load factor should be low but diversity factor should be high.

78.

For stability and economic reasons we operate the transmission line with power angle in the range:

a)

60 deg to 75 deg.

b)

10 deg. to 25 deg.

c)

30 deg. to 45 deg.

d)

65 deg. to 80 deg.

79.

For an existing a. c. transmission line the string efficiency is 80%. Now if d.c. voltage is supplied for the same set up, the string efficiency will be:

a)

Less than 80%.

b)

100%.

c)

80%.

d)

More than 80%.

80.

Effect of increase in temperature in overhead transmission lines is to:

a)

Decrease the stress but increase the length.

b)

Decrease the strength and length.

c)

None of the above.

d)

Increase the strength and length.

81.

For economic operation, the generator with highest positive incremental transmission loss will operate at:

a)

The lowest negative incremental cost of production.

b)

The highest positive incremental cost of production.

c)

None of these

d)

The lowest positive incremental cost of production

82.

An alternator is delivering the load current; its percent regulation is found to be zero. The type of load it delivers is:

a)

Inductive

b)

Resistive

c)

Capacitive

d)

admittance

83.

The incremental transmission loss of a plant is:

a)

zero

b)

Negative always

c)

Positive always.

d)

Can be positive or negative.

84.

Load flow study is carried out for:

a)

System planning

b)

Stability studies

c)

Load frequency control

d)

Fault calculations

85.

If the penalty factor of a plant is unity, its incremental transmission loss is:

a)

10.0

b)

–1.0.

c)

1.0.

d)

Zero.

86.

If the load of an isolated generator is increased without increasing the power input to the prime mover

a)

The generator field current will increase.

b)

The generator will slow down.

c)

The generator will speed up.

d)

The generator voltage will increase.

87.

When alternative sources of energy are available to a power system, they should be Used in such a way that:

a)

Overall production cost is minimized

b)

The most efficient plants are always loaded to their maximum

c)

Thermal generation is held at a minimum

d)

Near at the load point

88.

In a thermal-electric generating plant, overall efficiency is improved when

a)

It is always loaded

b)

Boiler pressure is increase

c)

The difference between initial pressure and temperature and exhaust pressure and temperature are held at a maximum

d)

Load on the units is increased

89.

When load on a thermal unit is increased, fuel input

a)

Decrease

b)

Increase

c)

Does not change

d)

It is constant

90.

Incremental-heat-rate curves, for thermal generating units, are used to determine the

a)

Ramp rate

b)

Fuel cost in P per hour

c)

Values to which the units should be loaded to result in minimum fuel cost

d)

Cost per unit of electrical output

91.

When generating units are loaded to equal incremental cost:

a)

Losses are minimized

b)

Fuel cost is at a maximum

c)

Fuel cost is not affected

d)

Minimum fuel cost result

92.

One advantage of computer control of generating units is that:

a)

Incremental fuel costs

b)

Loading of the units will be frequently adjusted to maintain them at equal

c)

Var output of the unit is minimized

d)

All units under the control of the computer will be loaded to the same load

93.

If the fuel cost of one unit, operating in parallel with other units, is increased and it is desired to maintain fuel cost, the load on the unit will be

a)

Decrease

b)

Increase

c)

Held constant

d)

all of these

94.

In a power system using both hydro and thermal generation, the proportion of hydro generation can be increased by

a)

Increasing the field currents of the hydro generators

b)

Used water with high specific gravity

c)

Increasing the prize (gamma) of the water

d)

Reducing the prize of the water

95.

In economic operation of a power system, the effect of increased penalty factor between a generating plant and system load center is to

a)

none of these

b)

Increase load on the plant.

c)

Decrease load on the generating plant.

d)

Hold the plant load constant

96.

Governors for controlling the speed of electric generating units normally provide

a)

A decrease of speed with increasing load

b)

An increase of speed with increasing load

c)

A flat speed load characteristic

97.

Governors for controlling the speed of electric generating units normally provide

a)

A decrease of speed with increasing load

b)

A flat speed load characteristic

c)

An increase of speed with increasing load

98.

On load –frequency-control installation, error signals are developed proportional to the frequency error. If frequency decline, the error signal will act to

a)

Increase generator voltages

b)

Reduce prime mover input to the generators

c)

Increase prime mover input to the generators

99.

When to or more system operate on an interconnected basis, each system

a)

Should provide for its own reserve capacity requirement

b)

Can depend on the other systems for its reserve requirements

c)

Should operate in a “flat frequency” mode

100.

When interconnected power system operate with tie-line bias, they will respond to

a)

Frequency changes only

b)

Tie-line load changes only

c)

Both frequency and tie-line load changes

101.

A metering installation for a 115-kV tie point between two power system has 10000:5 current transformers in each phase and 600:1 potential transformers connected line to ground. Assuming unity power factor, the multiplying factor that should be used to determine the power in the circuit in kilowatts is

a)

207.8

b)

3600

c)

360

102.

Inadvertent energy accumulation between power system are normally balanced by scheduling compensating deliveries of power

a)

On week endsOn week ends

b)

During periods corresponding to those in which the inadvertent energy was accumulated.

c)

During off-pick periods

103.

Wired supervisory control system are

a)

More reliable than computer-based systems

b)

Limited by cost and complexity when many devices are to be controlled.

c)

Immune from induced electrical interference

d)

Less expensive when many devices are to be controlled

104.

SCADA systems require

a)

A separate communication channel for each RTU

b)

Continuous attendance at each remote station

c)

A mean of entering and retrieving data at the master unit

d)

Frequency-shift data channels to the RTU

105.

One of the factor affecting power system reliability is

a)

The nominal system transmission-voltage levels

b)

The ratio of hydro to thermal generation

c)

The available reserve capacity margin

106.

Spinning reserve is generating capacity that

a)

Is available by starting gas-turbine generating units

b)

Has the lowest fuel cost

c)

Is synchronous and online, with capacity in excess of existing loads

107.

The spinning reserve to be carried on a system is

a)

Determined by the amount of load on the system

b)

A policy matter

c)

Determined by the system operator (dispatcher)

108.

The risk affecting spinning-reserve requirement of a system, in addition to the most heavily loaded units, include

a)

The time of the daily peak load

b)

The net amount of imported power

c)

The net amount of exported power

109.

Spinning reverse should

a)

Be carried on the largest unit available

b)

Be reduced during off-peak hours

c)

Be divided among units at various locations on a system

110.

In the event of a major loss of generation in an interconnected area, a system operator should

a)

Open tie lines only as a last resort with power flowing out and declining frequency

b)

Immediately open tie lines to other system

c)

Open tie lines if power is flowing out of the system

111.

House units are sometimes provided at thermal power plants to

a)

Supply power to plant auxiliaries

b)

Provide for station and yard light

c)

Keep the station batteries charged

112.

Of the Lightning arresters sold in the market, which can handle much large surge current and excessive contamination of dirtstation arrester

a)

line arrester

b)

Distribution arrester

c)

station arrester

d)

intermediate arrester

113.

The Location of lightning arrester should be

a)

away from the transformer

b)

near from the disconnect

c)

near the circuit breaker

d)

near the transformer

114.

The choice between ac and dc transmission is determined by

a)

The operating voltage

b)

The size of the conductors

c)

Engineering and economic factors

115.

The ratio of the average load on the plant for the period of time considered to the aggregate rating of all the generating equipments

a)

Load factor

b)

Capacity factor

c)

Utilization factor

d)

Diversity factor

116.

The most economical size of a feeder is that size for which the annual cost of energy lost in the feeder equals the cost of interest and depreciation on the capital cost of the conductor material.

a)

Faraday’s Law

b)

Kirchoff’s Law

c)

Kelvin’s Law

d)

Law on Economics

117.

Minimum oil circuit breaker is preferred in

a)

High voltage

b)

Medium voltage

c)

low voltage

d)

Extra High voltage

118.

Breaking Capacity of circuit breakers is expressed in

a)

kV

b)

KAIC

c)

MVA

d)

AH

119.

Type of water wheels used in hydraulic plants

a)

reaction

b)

all of these

c)

impulse

d)

propeller

120.

Power plant curves or graphs showing the direct relationship of the peak load and the generated energy of the said plant

a)

none of the above

b)

modified load curve

c)

load curve/graph

d)

load duration curve

121.

The advantage of using static capacitor to improve the power factor is because they

a)

provide continuous charge of power factor

b)

are not variable

c)

are most loss free

d)

none of these

122.

Is an equipment which controls the gate or valve opening of the prime mover

a)

silicon controlled rectifier

b)

governor

c)

rheostat

d)

contactor

123.

Is the mechanism which is used for moving a removable circuit breaker unit to end from the connected, disconnected and test positions

a)

blocking device

b)

position changing system

c)

permissive control device

d)

notching device

124.

Is used to increase or decrease in one step, the value of feild excitation on a machine

a)

field changing contactor

b)

DC reclosing relay

c)

filed regulator

d)

tripping relay

125.

In a generating and distribution system, current balance is provided by protective zones which are

a)

used to trip all circuit breaker in the system

b)

monitored by differential relays

c)

used to eliminate reflections on short transmission lines

d)

isolated during fault by disconnect switches

126.

In switchgear application, the term “dead fronts” means that

a)

the front and rear panels are hinged

b)

no equipment is mounted on the front pane

c)

an access door is at the end of the structure

d)

energized parts are not exposed on the front panel

127.

Which of the following steps is used for isolating a circuit breaker in power stations for maintenance purposes?

a)

open the disconnect switches

b)

turn off the main generator

c)

ground the auxiliary contacts

d)

pull the substation fuses

128.

The ratio of the average load on the plant for the period of time to the aggregate rating of all generating equipment

a)

capacity factor

b)

maintenance factor

c)

Plant use factor

d)

power factor

129.

The ratio of the individual maximum demands of the systems to the overall maximum demand of the whole system

a)

utilization factor

b)

diversity factor

c)

load factor

d)

demand factor

130.

In parallel operation of alternator, if the excitation of one alternate is changed it will only change

a)

synchronizing power of the machine

b)

reactive power taken by the machine

c)

apparent power taken by the machine

d)

real power taken by the machine

131.

The maximum past or present demand, which are taken into account to establishing billings for the previous or subsequent periods

a)

diversity demand

b)

Seasonal Diversity

c)

Ratchet Demand

d)

meter demand

132.

The ratio of the maximum coincident total demand of a group of consumers to the sum of the maximum power demand of the individual consumers comprising the group both taken at the same point of supply for the same time.

a)

Plant use (Output) factor

b)

Non- Coincidence factor

c)

Utilization Factor

d)

Coincidence factor

133.

The ratio of the average load for a given period to the operating capacity in actual service only (for multi-set plant).

a)

Load factor

b)

Demand factor

c)

Capacity factor

d)

Diversity factor

134.

The product of the load factor (LF) and the demand factor (DF)

a)

Use Factor

b)

Plant factor

c)

Average factor

d)

Connected Load factor

135.

The water enters the spiral case from the penstock, passes through the stay ring guided by the stationary stay ring vanes, then through the movable wicket gates through the runner and into the draft tube through which it flows into a tailrace or tailwater reservoir. This type of hydraulic turbine is known as

a)

Axial flow turbine

b)

Impulse Turbine

c)

Propeller type

d)

Francis type

136.

It pertains to the units available, maintained at operating temperature and ready for service although not in actual operation.

a)

cold reserve

b)

Hot reserve

c)

spinning reserve

d)

Operating reserve

137.

It is the product of the Utilization factor (UF) and Load factor (LF).

a)

Connected Load factor

b)

Capacity factor

c)

Use Factor

d)

Average factor

138.

To produce one kW-hr a power plant burns 0.9 lb of coal with a heating value of 13,000 BTU per lb. What is the heat rate of the plant?

a)

11,700 BTU/kW-hr

b)

8,700 BTU/kW-hr

c)

6,250 BTU/kW-hr

d)

9,500 BTU/kW-h

139.

A 100 MW power plant has a heat rate of 2.88 x 10 6 calories per kW-hr. It is a base load plant and runs at full load 24 hrs a day. How many tons of coal is needed per day?

a)

830

b)

960

c)

625

d)

250

140.

The feedwater is usually heated before it is injected to the boiler for the following reason EXCEPT one. Which one is this?

a)

Derating types of preheaters permit the removal of dissolves gases from the feedwater

b)

Recover part of the flue gas heat which is otherwise lost to the atmosphere

c)

Increase the efficiency of the boiler

d)

Improves the overall performance of the plant

141.

An effective remover of dust, carbon particles and others from the flue gas of the power plant is called _____.

a)

Dust scrubber

b)

Soot blower and collector

c)

Mechanical collector

d)

Electrostatic Precipitator

142.

It is the modern equipment of removing sulfur content from the flue gas of the power plant.

a)

ESP

b)

EMS

c)

DAC

d)

FGD

143.

In fission, energy is produced when.

a)

Molecules combine

b)

Nuclear particles combine

c)

Chemical compound splits into its constituents

d)

Nuclear particles split

144.

In the list below which one is not a type of present day nuclear power plant.

a)

fast breeder reactor

b)

boiling water

c)

low pressure reactor

d)

fusion-fission reactor

145.

How does the output of the hydraulic turbine vary with the diameter of the blade?

a)

It varies directly as the cube of the diameter of the blade

b)

It varies directly as the two-thirds power of the diameter of the blade

c)

It varies directly as the diameter of the blade

d)

It varies directly as the square of the diameter of the blade

146.

A ten-year investigation of rivers potential gave an average water flow of 25 cm per second at the bottom and 90 cm per second at the surface. The average cross section at the same location is 80 sq. m. What is the average flow rate in cubic meter per hour?

a)

5,760

b)

57,500

c)

46,500

d)

165,000

147.

A power plant gets water from a dam from a height of 122.45 meters at the rate of 1,000 cubic meters per minute. If the output of the plant is 15,000 kW, what is the efficiency?

a)

80%

b)

75%

c)

65%

d)

70%

148.

An industry having a maximum demand of 1000 kW works for 320 days in a year, 8 hrs per day. Assuming that it works at full capacity all the time during working days, calculate the daily load factor.

a)

29.5 %

b)

33.3 %

c)

67 %

d)

56.2 %

149.

A 100 MW power station delivers 100 MW for 2 hrs, 50 MW for 6 hrs and is shut down for the rest of each day. It is also shut down for maintenance for 45 days each year. Calculate the annual load factor.

a)

78.5%

b)

20.83%

c)

56.9 %

d)

20.1 %

150.

A power station has a load cycle as follows: 260 MW for 6 hrs 200 MW for 8 hrs 160 MW for 4 hrs 100 MW for 6 hrs If the power station is equipped with 4 sets of 75 MW each, calculate the capacity factor

a)

76.5 %

b)

34.5 %

c)

61.1 %

d)

23.6 %

151.

The current loads of four circuits are as follows

Circuit no 1 = 25 Amperes

Circuit no 2 = 38 Amperes

Circuit no 3 = 18 Amperes

Circuit no 4 = 45 Amperes

If the diversity factor is 1.5. What is the minimum ampacity of the feeder conductor?

a)

126 Amperes

b)

84 Amperes

c)

152 Amperes

d)

189 Amperes

152.

The metering of a power customer was read and gave the following data:

KW-hr = 200,000, KVAR- hr.= 180,000, Maximum demand = 380 kW, Billing days = 3

What is the load factor?

a)

73%

b)

62%

c)

80%

d)

68%

153.

The power customer has four circuits of 220-volt three phase. The circuits have the maximum demand as follows:

Circuit no 1 = 35 Amperes

Circuit no 2 = 46 Amperes

Circuit no 3 = 72 Amperes

Circuit no 4 = 57 Amperes

The diversity factor is 1.5, the load factor is 50% and the power factor is 80%. What is the approximate kW demand of the customer?

a)

53 kW

b)

43 kW

c)

21 kW

d)

15 kW

154.

The power customer has four circuits of 220-volt three phase. The circuits have the maximum demand as follows:

Circuit no 1 = 35 Amperes , Circuit no 2 = 46 Amperes, Circuit no 3 = 72 Amperes, Circuit no 4 = 57 Amperes

The diversity factor is 1.5, the load factor is 50% and the power factor is 80%. Determine the maximum KVA demand of the customer?

a)

26.5

b)

80

c)

53

d)

46

155.

A Diesel station supplies the following loads to various consumers:

Industrial consumer = 1500 kw

Commercial estabkishment = 750 kw

Domestic power = 100 kw

Domestic light = 450 kw

If the maximum demand on the station is 2500 kw and the number of kwh generated per year is 45 x 10 5 , determine the diversity factor and load factor.

a)

21.1, 50.2%

b)

1.53, 65.7%

c)

97, 31.2%

d)

1.12, 20.5%

156.

A 100 MW coal fired power plant has an average heat rate of 9,500 BTU/ kWh. The plant load factor is 75%; the heating value of coal is 12,000 BTU/ lb. Calculate the amount of coal usage for one day

a)

1.425 x 10 6 lbs.

b)

2.235 x 10 5 lbs

c)

1.425 x 10 6 lbs.

d)

1.826 x 10 6

157.

A Power Plant has a maximum demand of 15 MW. The annual load factor and capacity factor are 50 % and 40%, respectively. Determine the reserve capacity of the plant.

a)

3750 kW

b)

5370 kW

c)

7350 kW

d)

3075 kW

158.

A diversity factor of 2.5 gives a saving of ___________ % in the generating equipment.

a)

25

b)

40

c)

60

d)

50

159.

A coal Thermal Power Plant has a boiler, turbine and alternator efficiencies of 35%, 86%, and 93% respectively. Coal with heating value of 12,000 BTU per lb cost P 1.5 per lb. What is the fuel cost in producing 1 kW?

a)

P 1.62 per kW

b)

P 1.52 per kW

c)

P 1.75 per kW

d)

P 1.9 per kW

160.

A certain coal fired power plant has a heat rate of 2.88 x 10 8 calories per kW-hr. Coal costs P 2,500 per Ton. How much is the fuel cost component of producing 1 kW-hr?

a)

P 1.25

b)

P 1.75

c)

P 2.50

d)

P 1.00

161.

A power station has a load cycle as under

260 MW for 6 hrs 200 MW for 8 hrs 160 MW for 4 hrs 100 MW for 6 hrs

If the power station is equipped with 4 sets of 75 MW each, calculate the daily fuel requirement if the calorific value of the oil used were 10,000 Kcal/kg and the average heat rate of the station were 2,860 Kcal/kW.

a)

1890 tons

b)

3452 tons

c)

1258.4 tons

d)

7641 tons

162.

A diesel generator set burns diesel with a heating value of 18,000 BTU per lb. The diesel engine has an efficiency of 30% and the alternator has an efficiency of 95%. Determine the fuel cost component of producing one kW-hr if diesel cost P 2.8 per lb.

a)

P 0.15

b)

P 1.86

c)

P 2.15

d)

P 3.28

163.

A proposed hydroelectric station has an available head of 30 m, a catchment area of 50 x 10 6 sq. m, the rainfall for which is 120 cm per annum. If 70% of the total rainfall can be collected, calculate the power that could be generated. Assume the following efficiencies: Penstock 95%, Turbine 80%, and Generator 85%.

a)

925 kW

b)

214 kW

c)

678 kW

d)

253 kW

164.

The load of an instrument transformer consisting of delicate moving elements of an ammeter, voltmeter and wattmeter is termed as

a)

Transformer power

b)

Instrument Impedance

c)

meter load

d)

burden

165.

At a 155 kV substation the PT ratio is 1000:1 and the CT ratio is 1200:5. The potential going into the wattmeter is 155 V. What is the MW indicated when the wattmeter reads 800 watts

a)

150 MW

b)

192 MW

c)

19.2 MW

d)

15.0 MW

166.

When alternative sources of energy are available to power system, they should be used in such a way that

a)

The most efficient plants are always loaded to their maximum

b)

Overall production cost is minimized

c)

Thermal generation is held at minimum

d)

Used Diesel Power plant

167.

n thermal electric generating plant, overall efficiency is improved when

a)

Increased the no. of generator

b)

Boiler pressure is increased

c)

The difference between initial pressure and temperature and exhaust pressure and temperature are held at a maximum

d)

Load on the units is increased

168.

One advantage of computer control of generating units is that

a)

All units under the control of the computer will be loaded to the same load

b)

It can control all equipment

c)

Var. output of the units are minimized

d)

Loading of the units will be frequently adjusted to maintain them at equal incremental cost

169.

The most economical cross section of a conductor is that which makes the interest on the capital outlay plus depreciation due to the conductor in the cable equal to the annual cost of energy loss.

a)

Ferranti law

b)

Vanderwhaals Law

c)

Mc Kevins Law

d)

Kelvins law

170.

Inadverent accumulations between power systems are normally balanced by scheduling compensating deliveries of power

a)

During periods corresponding to those in which the inadverent energy was accumulated

b)

On base load plant

c)

On weekends

d)

During off-peak load

171.

Spinning reserve is generating capacity that

a)

A policy matter

b)

Has the lowest fuel cost

c)

Is available by starting Gas- Turbine generating units

d)

Is synchronized and online, with capacity in excess of existing load

172.

Ferroresonance is a condition that may occur on

a)

Transformer

b)

Distribution line

c)

Capacitor

d)

Transmission line

173.

Subsynchronous resonance is a condition that may occu on

a)

Loss of load on transmission line

b)

Short transmission line

c)

Increase of load on line

d)

Long, heavily loaded line

174.

Heating value of coal largely depend on

a)

moisture content

b)

volatile matter

c)

size of coal particle

d)

ash content

175.

Power plant using coal work closely on which of the following cycle

a)

Brayton cycle

b)

Otto cycle

c)

Rankine cycle

d)

Binary vapour cycle

176.

Which of the following contributes to the efficiency of Rankine cycle in thermal power plant.

a)

Reheating of steam at intermediate stag

b)

Regeneration use of steam for heating boiler

c)

Used of high pressure

d)

All of these

177.

In steam turbine cycle, the lowest pressure occurs in

a)

Boiler

b)

Superheater

c)

Condenser

d)

Turbine inlet

178.

For low head and high discharge the hydraulic turbine used is.

a)

Jonvas

b)

Pelton wheel

c)

Francis type

d)

Kaplan

179.

Overall efficiency of Gas Turbine is

a)

equal to Rankine cycle efficiency

b)

equal to Carnot cycle efficiency

c)

More than Otto or Diesel cycle efficiency

d)

Less than Diesel cycle efficiency

180.

The function of moderator in Nuclear Reaction is

a)

to control the reaction

b)

to liberate excessive neutron

c)

to absorb excessive neutrons

d)

to accelerate the reaction

181.

During load shedding

a)

some loads are switch off

b)

some loads are switch off

c)

system frequency is reduced

d)

system voltage is reduced

182.

A low utilization factor for a plant indicates that

a)

plant is used for peak load

b)

plant is used for standby purpose only

c)

plant is under maintenance

d)

plant is used for base load only

183.

Which of the following relations is incorrect?

a)

Demand factor x Connected load = Maximum demand

b)

Load factor x Maximum load = Average load

c)

Capacity factor = Utilization factor x Load factor

d)

None of the above

184.

When paralleling a generating unit to a power system, if the synchroscope indicates that the incoming machine is running slower than the system:

a)

The synchronizing switch should be closed just after it indicates zero phase angle difference.

b)

The power input to the prime mover should be decreased slightly

c)

The field current should be increased

d)

The power input to the prime mover should be increased slightly

185.

When load on a thermal unit is increased, fuel input

a)

slightly decreased

b)

Does not change

c)

Decreased

d)

Increased

186.

When generating units are loaded to equal incremental cost:

a)

Fuel cost are not affected

b)

Minimum fuel cost result

c)

Fuel cost at a maximum

d)

efficiency decreased

187.

In a power system using both Hydro and thermal generation, the proportion of hydro generation can be increased by.

a)

Used salt water

b)

Increasing the price of water

c)

Reducing the price of water

d)

Increasing the field current of the Hydro generators

188.

Which of the following methods of generating electric power from the sea is more advantageous?

a)

Tidal power

b)

Ocean power

c)

Water power

d)

sea power

189.

The efficiency of a thermal power plant improves with.

a)

Use of high steam pressure

b)

Lower load on the plant

c)

increased quantity of coal burnt

d)

Larger quantity of water used

190.

A Gas turbine works on

a)

Rankine cycle

b)

Dual cycle

c)

Carnot cycle

d)

Brayton cycle

191.

Air standard efficiency of a diesesl engine depends on

a)

torque

b)

speed

c)

fuel

d)

compression ratio

192.

Most of the heat generated in internal combustion engine is lost in

a)

radiation

b)

lubricating oil

c)

cooling water

d)

exhaust gases

193.

Capital cost per MWh is highest in case of

a)

Hydroelectric

b)

Nuclear power plant

c)

Diesel engine

d)

steam power plant

194.

A diesel power plant is best suited as

a)

general purpose plant

b)

stand by power plant

c)

base load plant

d)

peak load plant

195.

A Nuclear Power plant is invariably used as a

a)

spinning reserve plant

b)

stand by plant

c)

peak load plant

d)

base load plant

196.

Economizers are used to heat

a)

steam

b)

feedwater

c)

boiler

d)

air

197.

Surge tank is provided for the protection of

a)

blade

b)

weir

c)

penstock

d)

intake pipe

198.

A generating station has a connected load of 43 MW an a maximum demand of 20 MW, the units genetrated being 61.5 x 10 6 per annum. Calculate. The load factor

a)

351. %

b)

17.9%

c)

76%

d)

64.8%

199.

For the same maximum demand, if the load factor is decreased the cost of energy is

a)

no relation

b)

not affected

c)

decreased

d)

increased