Cannock inspection and Testing 2

Total questions: 19

Worksheet time: 38mins

Name
Class
Date
1.

OSG gives the maximum stable value of Ze for a TT installation as

a)

100 ohms

b)

21 ohms

c)

0.8 ohms

d)

200 ohms

2.

Safe isolation should be carried out by

a)

A Skilled person

b)

An engineer

c)

The home owner

d)

The client

3.

Which type of earthing system relies on a separately supplied earth, usually the sheathing on the cable

a)

TT

b)

TN-S

c)

TN-C-S

d)

IT

4.

Which of the following would not be one of the human senses to use during the

initial verification of an addition to a lighting circuit:

a)

smell

b)

taste

c)

sight

d)

hearing

5.

The person carrying out inspection and testing must have

a)

An On site guide

b)

A Megger

c)

Sound knowledge and experience relevant to the installation being inspected

d)

A decent van

6.

The top surface of a consumer unit should be protected from ingress of dust to a standard of

a)

IP4X

b)

IP2X

c)

IPX4

d)

IPX2

7.

A visual inspection is necessary

before testing to check whether

a)

The ZS is within the maximum allowed

b)

Switch gear is accessible

c)

The insulation resistance is acceptable

d)

RCD testing is acceptable

8.

Which of the following is not permitted for use as an earth electrode

a)

Multiple earth rods

b)

Earth Rod

c)

Metal water mains pipes

d)

Earth plates

9.

Which one of the following does not need to be checked for compliance during the visual inspection of an installation

a)

Routing of cables in safe zones

b)

Connection of single pole devices in line conductors only

c)

Presence of fire barriers

d)

End to End test on a Ring circuit

10.

The purpose of the test button of a residual current device is to check the

a)

Earth electrode resistance

b)

Continuity of the earthing conductor

c)

Mechanical operation of the RCD

d)

Earth fault loop impedance

11.

select the sequence in which these tests should be conducted for a new installation:

- 1. functional 2. insulation resistance 3. polarity 4. continuity of final ring conductors

5. continuity of protective conductors

a)

5,2,3,4,1

b)

1,2,3,4,5

c)

5,4,2,3,1

d)

1,5,3,2,4

12.

An earth fault loop impedance test Zs performed on a ring circuit would record

a)

The resistance of the line conductor, the resistance of the cpc and the external loop

b)

The resistance of the protective conductor

c)

The external loop impedance

d)

The resistance of the protective conductor and the line conductor

13.

During an external loop impedance test, the main earthing conductor should be

a)

Disconnected

b)

Connected

c)

Insulated

d)

Short circuited

14.

The prospective short-circuit current between line and neutral is measured at 850 A. The maximum balanced prospective short-circuit current level between lines on a three phase system, as a rule of thumb, can be assumed to be approximately

a)

0.85 kA

b)

0.85 kA

c)

2.4 kA

d)

1.7 kA

15.

Which of the following tests would not normally be required during initial verification of an electrical installation

a)

Continuity of main bonding conductors

b)

Verification of voltage drop

c)

RCD testing

d)

Prospective fault current

16.

Instrument calibration certificates are normally valid for

a)

2 years

b)

1 year

c)

90 days

d)

5 years

17.

Control gear and interlocks should be operated when carrying out

a)

Earth loop impedance

tests

b)

Functional testing

c)

Polarity testing

d)

RCD testing

18.

Which of the following should accompany the inspection and test certificate

a)

Copies of minor works certificates

b)

Copies of the inspection and test schedules

c)

Invoices for any remedial work carried out

d)

Two copies of test results

19.

The type of certificate issued after installing an additional socket outlet

within an existing installation would be a

a)

Minor Works Certificate

b)

Installation Certificate

c)

Periodic Test Certificate

d)

Verification and Test Certificate