NCCER Electrical 3 Module 5

Total questions: 35

Worksheet time: 18mins

Name
Class
Date
1.

Types of fault current include overloads, short circuits, ground faults, and _____.

a)

transient faults

b)

symmetrical faults

c)

asymmetric faults

d)

arc faults

2.

Overcurrent protection is covered in _____.

a)

NEC Article 240

b)

NEC Article 310

c)

NEC Article 314

d)

NEC Article 334

3.

One of the first signs of worn motor bearings is MOST likely to be a(n) _____.

a)

short circuit

b)

ground fault

c)

continuous overload

d)

arc fault

4.

Equipment intended to interrupt current at fault levels must have an interrupting rating at

nominal circuit voltage that is at least _____.

a)

equal to the current available at the line terminals of the equipment

b)

125% of the current available at the line terminals of the equipment

c)

150% of the current available at the line terminals of the equipment

d)

200% of the current available at the line terminals of the equipment

5.

For 480V circuits, the arc current seldom exceeds _____.

a)

20% of the available bolted fault current

b)

40% of the available bolted fault current

c)

60% of the available bolted fault current

d)

80% of the available bolted fault current

6.

A conductor with failed insulation contacts the metal edge of a grounded metal wireway.
This is known as a(n) _____.

a)

overload

b)

ground fault

c)

short circuit

d)

arc fault

7.

The voltage rating of a fuse _____.

a)

is always the same as the circuit voltage

b)

can be lower than the circuit voltage but never higher

c)

can be higher than the circuit voltage but never lower

d)

depends upon its capability to close a circuit under an overcurrent condition

8.

The type of fuse used to prevent nuisance tripping from temporary motor overloads and surge
currents is a(n) _____.

a)

dual-element, time-delay fuse

b)

Edison-base plug fuse

c)

GE-base single-element fuse

d)

non-time-delay fuse

9.

UL Class R fuses have a short circuit interrupting rating of up to _____.

a)

10,000A

b)

50,000A

c)

100,000A

d)

200,000A

10.

Which of the following is within the basic scope of Underwriters Laboratories?

a)

Proper selection of fuses

b)

Safety

c)

Functional performance of fuses

d)

Reliability of fuses

11.

A device that is designed to withstand numerous trip and reset cycles without replacement
and can be thermal, magnetic, or solid-state is a(n) _____.

a)

single-element relay

b)

overload relay

c)

fast-acting fuse

d)

Edison-base fuse

12.

Which of the following is TRUE with regard to circuit breakers?

a)

Under normal conditions, the current flow bypasses the spring and latching mechanism.

b)

Once a breaker trips, it must be replaced.

c)

After a breaker trips, it will automatically reset itself.

d)

Circuit breakers rarely include a thermal element.

13.

A 500A circuit breaker has a frame size of _____.

a)

500A

b)

1,000A

c)

1,200A

d)

2,000A

14.

What is the frame size of a 30A circuit breaker?

a)

3A

b)

30A

c)

100A

d)

1,000A

15.

Circuit breakers are classified by _____.

a)

manufacturer

b)

color coding

c)

the smallest ampere rating of its range

d)

the largest ampere rating of its range

16.


Which of the following is TRUE with regard to circuit breaker interrupting capacity ratings?

a)

NEMA tests are certified by unbiased reviewers.

b)

UL tests now include NEMA ratings.

c)

The interrupting capacity of a circuit breaker is the same for all voltage levels.

d)

UL tests are self-certification.

17.

If a 120V feeder for nonmotor loads feeds a continuous load rated at 20A and a
noncontinuous load at 25A, what size overcurrent protective device should be selected?

a)

40A

b)

50A

c)

60A

d)

70A

18.

If a continuous load on a branch circuit is measured at 12A, the overcurrent protection should
be sized at _____.

a)

8A

b)

10A

c)

12A

d)

15A

19.

A feeder circuit with no motor load has a continuous load of 16A and a noncontinuous load
of 10A. The feeder overcurrent protective device should be sized at _____.

a)

12A

b)

24A

c)

26A

d)

30A

20.

Which of the following is commonly referred to as motor branch circuit protection?

a)

Component protection

b)

Overvoltage protection

c)

Short circuit protection

d)

Overcurrent protection

21.

When tripped, the circuit breaker handle moves _____.

a)

to the On position

b)

to the Off position

c)

halfway between the On and Off positions

d)

to the Reset position

22.


The recommended method of determining short circuit currents is the _____.

a)

momentary impedance method

b)

peak duty method

c)

symmetrical duty method

d)

point-to-point method

23.

The magnetic portion of a standard circuit breaker _____.

a)

provides an instantaneous trip for high levels of current

b)

protects the circuit from heat damage generated by lower level currents

c)

prevents the device from tripping due to a short circuit

d)

provides a trip delay for high levels of current

24.

The thermal portion of a standard circuit breaker _____.

a)

provides an instantaneous trip for high levels of current

b)

protects the circuit from heat damage generated by lower level currents

c)

prevents the device from tripping due to a short circuit

d)

provides a trip delay for high levels of current

25.

A single-element fuse _____.

a)

provides an instantaneous trip for high levels of current

b)

protects the circuit from heat damage generated by lower level currents

c)

prevents the device from tripping due to a short circuit

d)

provides a trip delay for high levels of current

26.

Worn motor bearings are the most likely to result in a___.

a)

continuous overload

b)

short circuit

c)

ground fault

d)

arc fault

27.

A high level short circuit may exceed___.

a)

50A

b)

500A

c)

5,000A

d)

50,000A

28.

Accidental contact between an electrical conductor and a grounded enclosure is called___.

a)

overload

b)

short circuit

c)

ground fault

d)

arc fault

29.

Most arcing faults begin as___.

a)

ground faults

b)

temporary overloads

c)

sustained overloads

d)

short circuit

30.

A plug fuse with a hexagonal cap has a maximum amperage rating of ___.

a)

15A

b)

20A

c)

25A

d)

30A

31.

Under normal operation and at currents near its

ampere rating, a fuse operates as a _____.

a)

diode

b)

resistor

c)

conductor

d)

heat sink

32.

UL classifies low-voltage fuses as those operating

at _____.

a)

24V or less

b)

60V or less

c)

120V or less

d)

600V or less

33.

A standard circuit breaker frame size is _____.

a)

100A

b)

300A

c)

750A

d)

1,500A

34.

The interrupting capacity of a circuit breaker is

based on its rated _____.

a)

capacitance

b)

power factor

c)

resistance

d)

voltage

35.

A feeder circuit with no motor load has a

continuous load of 10A and a noncontinuous load

of 5A. The feeder overcurrent protective device

should be sized at _____.

a)

10A

b)

15A

c)

17.5A

d)

18.75A