
Definitions PI S95
Presentation
•
Professional Development
•
Professional Development
•
Hard
L F
Used 6+ times
FREE Resource
4 Slides • 44 Questions
1
TERMS S-95
Accessibility
As defined in NFPA admitting close approach: not guarded by locked doors, elevation, and other effective means.
Some text here about the topic of discussion
2
Alarm Notification Appliance
A fire alarm system component, such as a bell, horn, speaker, light, text, display or vibration device that issues an audible, tactile, and /or visual alert.
Some text here about the topic of discussion
3
Multiple Choice
ACCESSIBILITY
A fire alarm system component, such as a bell, horn, speaker, light, text display or vibration device that issues an audible, tactile, and/or visual alert.
As defined in NFPA admitting close approach: not guarded by locked doors, elevation, and other effective means
A signal indicating an emergency requiring immediate action, such as a signal indicative of fire
4
Multiple Choice
: An alarm signal transmitted by a fire alarm system which failed to function as designed as a result of improper installation, improper maintenance, malfunction, or other factor. Examples of unwarranted alarms are alarms resulting from improper smoke detector placement, improper detector setting for installed location, lack of system maintenance, and control panel malfunction. It is important to know that the alarm verification feature reduces the number of unwarranted alarms
UNWARRANTED ALARM
SHALL
WARRANTED ALARM
SIGNAL ALARM
5
Multiple Choice
A signal initiated by the fire alarm system or device indicative of a fault in a monitored circuit or component
SMOKE ALARM
TROUBLE SIGNAL
ALARM
FALSE ALARM
6
Multiple Select
When was the FIRE CODE adopted?
it was adopted in July 2008 vastly changed the requirements for the supervision of all fire alarm systems. The code prior only required supervision for Interior Fire Alarm Systems.
July 2008
In July 2008 and requires require a Certificate of Fitness holder (C of F).
7
Multiple Choice
Fire Alarm Systems installed in New York City are subject to the regulations enforced by the FDNY.
True
False
8
Multiple Choice
An approved fire alarm system might typically be found in assembly occupancies (e.g. theaters, school auditoriums), business occupancies, education occupancies, factories, malls, hotels, etc. Any approved fire alarm system must be supervised by a Certificate of Fitness holder depending upon the nature of the occupancy and/or the type of fire alarm system.
True
False
9
Multiple Select
ARCS
(Auxiliary Radio Communications System)
In-Building Emergency Radio Communication Systems. ARC system is a wireless two-way building communication system for Fire Department use only
A facility that receives alarm signals from a protected premises and retransmits or otherwise reports such alarm signals to the Fire Department
10
Multiple Choice
Look at the table in the image is the information provided accurate that any approved fire alarm system without voice communication system must be under supervision of an S-95 Certificate of Fitness holder. A fire alarm system may include but not limit to one/some of the following systems: 1. Standpipe fire pump 2. Sprinkler booster fire pump 3. Standpipe (limited-service fire pump)
True
False
11
Multiple Select
A fire alarm system may include but not limit to one/some of the following systems:
1. Standpipe fire pump 2. Sprinkler booster fire pump
3. Standpipe (limited-service fire pump)
4. Other (specify) 5. Emergency voice/alarm communication system 6. Fire Department communication system 7. Carbon monoxide alarms and detectors 8. Automatic sprinkler systems 9. Alternative automatic fire-extinguishing system
10. Automatic fire alarm systems 11. Manual fire alarm systems 12. Manual and automatic fire alarm systems 13. Emergency alarm systems (gas detection system) 14. Smoke control systems
15. Fire command center 16. Post-fire smoke purge systems 17. Sub-systems (Range hood, halon and FM200 etc.) 18. Auxiliary Radio Communication System (ARCS)
12
Multiple Choice
Certificate of Fitness holders should ensure that their respective premises have fire alarm systems approved by the FDNY.
True
False
13
Multiple Choice
Fire alarm systems are required in many premises as part of a fire protection system. The new Fire Code has expanded the requirements for fire alarm systems which include but are not limited to the following buildings: • OFFICE BUILDINGS • SHELTERS • HOSPITALS • MARINAS • COMMERCIAL • HOTELS • MOTELS • SCHOOLS • APARTMENT BUILDINGS which may be high-rise or low-rise, or as specified in New York City Building Code section 309.1.
True
False
14
Multiple Choice
A Fire Alarm System is a system consisting of components and circuits arranged to monitor and annunciate the status of fire alarm and supervisory signalinitiating devices, and to initiate the appropriate response to these signals. See Image
True
False
15
Multiple Select
3. COMPONENTS OF THE FIRE ALARM SYSTEM ARE
3.1 FIRE ALARM CONTROL PANEL (FACP)
3.2 THREE Supervisory Signals:
A3.2.3 Trouble Signals:
TYPES OF SIGNALS INITIATED BY FACP3.2.1
Fire Alarm Signal:3.2.2
16
Multiple Choice
Note: The FDNY is not dispatched to respond to trouble signals. Trouble signals are not indicative of a fire condition.
True
False
17
Multiple Choice
LAMP TEST: This function is used on some FACP’s to check the condition of the light emitting diodes (LEDs) on the FACP. REMOTE ANNUNCIATOR PANEL: A remote annunciator panel when installed shall function for visual notification of alarm, supervisory or trouble conditions only.
True
False
18
Multiple Choice
3.3 SUB-SYSTEM A Sub-System is an activating (voluntary or required) system installed in a specific area or floor for a specific purpose in a building that has a required (mandated) base building fire alarm system.
True
False
19
Multiple Choice
All Sub-Systems include but are not limited to the following: Halon, FM200, Water Mist, Pre-Action, Range Hood, Carbon Dioxide, Foam system, Dry Chemical, Smoke Detection, Clean Air Agents or Thermostatic Systems shall be subject to Fire Department inspection and test for issuance of Letter of Approval for such Sub-System(s).
True
False
20
Multiple Choice
4. IN CASE OF AN ALARM 4.1 ACKNOWLEDGE SWITCH OR BUTTON An acknowledge button, also abbreviated as (ACK) is used to acknowledge alarm, trouble or supervisory conditions. The sequence and procedures may differ in This book is provided to the public for free by the FDNY. 17 every fire alarm system; however, it is important for the C of F holder, when present and practical, to report to the FACP location whenever the alarm is activated.
True
False
21
Multiple Choice
4.2 ALARM SILENCE SWITCH OR BUTTON The alarm silence switch is used to silence the building audible and visual devices (such as sirens, bells or gongs) after an evacuation is complete while the source of alarm is being investigated. Never reset the fire alarm system until the condition is verified by the FDNY personnel. Depending on the configuration of the alarm system, this function will either silence the system's notification appliances completely, or will silence only the audible alarm, with strobe lights continuing to flash. However, the silence switch does not prevent a signal from being transmitted to a FDNY approved central station company. Audible silence allows for easier communication for emergency responders while responding to an alarm.
True
False
22
Multiple Choice
4.3 SYSTEM RESET SWITCH OR BUTTON This switch is used to reset the fire alarm system after an alarm condition has been clean. All initiating devices should return to normal condition after manually resetting. If an initiating device is still in alarm after the system is reset, such as smoke detectors continuing to sense smoke, or a manual pull station still in an activated position, another alarm will be generated. Most trouble and supervisory conditions will clear automatically when conditions are returned to normal. After a fire alarm is reset, the fan usually requires restarting from a separate “fan restart” button or key switch
True
False
23
Multiple Choice
CENTRAL STATION
A facility that receives alarm signals from a protected premises and retransmits or otherwise reports such as alarm signals to the Fire Department
station company that has been issued a valid certificate of operation from FDNY.
Signal indicating an emergency requiring immediate action such as a signal indicative of fire.
24
Multiple Choice
DEFINED FIRE ALARM SYSTEM
A facility that receives alarm signals from a protected premises and retransmits or otherwise reports such alarm signals to the Fire Department
fire alarm system or any sub-system thereof that automatically transmits signals to the department or a central station and that is installed in premises which are required to have a fire alarm system.
A fire alarm system or any sub-system thereof that automatically transmits signals to the department or a central station and that is installed in premises which are required to have a fire alarm system
25
Multiple Choice
ALARM NOTIFICATION APPLIANCE:
In-Building Emergency Radio Communication Systems. ARC system is a wireless two-wa
A central station company that has been issued a valid certificate of operation from FDNY.
A fire alarm system component, such as a bell, horn, speaker, light, text display or vibration device that issues an audible, tactile, and/or visual alert.
A signal indicating an emergency requiring immediate action, such as a signal indicative of fire
26
Multiple Choice
Alarm Signal
A signal indicating an emergency.
A signal indicating an emergency requiring immediate action, such as a signal indicative of fire.
A central station company that has been issued a valid certificate of operation from FDNY.
27
Multiple Choice
DESIGNATED REPRESENTATIVE
A person or entity designated by the subscriber who shall be responsible for receiving notifications from the central station company concerning the status of the protective signaling system at the protected premises and who is authorized to take action with respect to such system.
A fire alarm system or any sub-system thereof that automatically transmits signals to the department or a central station and that is installed in premises which are required to have a fire alarm system.
A person or entity designated by the subscriber who shall be responsible for receiving notifications from the central station company concerning the status of the protective signaling system at the protected premises and who is authorized to take action with respect to such system
28
Multiple Select
FIRE ALARM CONTROL UNIT (FACP, FCS):
FIRE ALARM CONTROL UNIT
A system component that receives inputs from automatic and manual fire alarm devices and is capable of supplying power to detection devices and transponder(s) of off-premises transmitter(s). The control unit is capable of providing a transfer of power to the notification appliances and transfer of condition to relays of devices
A fire alarm system or any sub-system thereof that automatically transmits signals to the department or a central station and that is installed in premises which are required to have a fire alarm system.
29
Multiple Choice
FIRE ALARM SIGNAL
A signal initiated by a fire alarm-initiating device such as a manual fire alarm box (pull station), automatic fire detector, water-flow switch, or other device whose activation is indicative of the presence of a fire or fire signature.
Any system, including any interconnected fire alarm sub-system, of components and circuits arranged to monitor and annunciate the status of fire alarm or supervisory signal-initiating devices
Approved devices, equipment and systems or combinations of systems used to detect a fire, activate an alarm, extinguish or control a fire, control or manage smoke and products of a fire or any combination thereof, including fire extinguishing systems, fire alarm systems, sprinkler systems and standpipe systems
30
Multiple Choice
FIRE ALARM SYSTEM
Any system, including any interconnected fire alarm sub-system, of components and circuits arranged to monitor and annunciate the status of fire alarm or supervisory signal-initiating devices
The person responsible as designated by the owner for ensuring that proper safety precautions are taken when a fire protection system is out of service
System including any inter -connected fire alarm sub-system
31
FIRE PROTECTION SYSTEM:
Approved devices, equipment and systems or combinations of systems used to detect a fire, activate an alarm, extinguish or control a fire, control or manage smoke and products of a fire or any combination thereof, including fire extinguishing systems, fire alarm systems, sprinkler systems and standpipe systems.
Subject | Subject
Some text here about the topic of discussion
32
INITIATING DEVICE
A system component that originates transmission of a change-of-state condition, such as in a smoke detector, manual fire alarm box, or supervisory switch.
Subject | Subject
33
Multiple Choice
SMOKE DETECTOR MAINTENANCE
Work, including, but not limited to, repair, replacement, and service, performed to ensure that equipment operates properly
Indicates a mandatory requirement
indicates a mandatory requirement. To add and or remove?
34
Multiple Choice
Shall
Indicates a mandatory requirement.
A signal indicating an emergency requiring immediate action, such as a signal indicative of a fire.
35
Multiple Choice
FIRE ALARM SYSTEM:
Any system, including any interconnected fire alarm sub-system, of components and circuits arranged to monitor and annunciate the status of fire alarm or supervisory signal-initiating devices
The person responsible as designated by the owner for ensuring that proper safety precautions are taken when a fire protection system is out of service.
A system component that originates transmission of a change-of-state condition, such as in a smoke detector, manual fire alarm box, or supervisory switch
36
Multiple Choice
Approved devices, equipment and systems or combinations of systems used to detect a fire, activate an alarm, extinguish or control a fire, control or manage smoke and products of a fire or any combination thereof, including fire extinguishing systems, fire alarm systems, sprinkler systems and standpipe systems
INITIATING DEVICE
FIRE PROTECTION SYSTEM
IMPAIRMENT COORDINATOR
37
Multiple Choice
A system component that originates transmission of a change-of-state condition, such as in a smoke detector, manual fire alarm box, or supervisory switch
INITIATING DEVICE
SMOKE DETECTOR MAINTENANCE:
NUISANCE ALARM
OUT OF SERVICE SYSTEM
38
Multiple Choice
PLENUM
The open space that carries air between the ceilings and floor above
A fire protection system that is not fully functional; or whose operation is impaired or is otherwise not in good working order
The open space that carries air between the ceilings and floor above.
Any alarm caused by mechanical failure, malfunction, improper installation, or lack of proper maintenance, or any alarm activated by a cause that cannot be determined
39
Multiple Choice
A fire protection system that is not fully functional; or whose operation is impaired or is otherwise not in good working order
SHALL
OUT OF SERVICE SYSTEM
SMOKE DETECTOR MAINTENANCE:
40
Multiple Choice
Any alarm caused by mechanical failure, malfunction, improper installation, or lack of proper maintenance, or any alarm activated by a cause that cannot be determined
NUISANCE ALARM
OUT OF SERVICE SYSTEM
PROTECTED PREMISES
SINGLE-STATION SMOKE ALARM
41
Multiple Choice
An assembly incorporating the detector, the control equipment, and the alarm-sounding device in one unit, operated from a power supply either in the unit or obtained at the point of installation.
PLENUM
PROTECTED PREMISES
SINGLE-STATION SMOKE ALARM
42
Multiple Choice
A fire protection system that is not fully functional; or whose operation is impaired or is otherwise not in good working order
OUT OF SERVICE SYSTEM
SINGLE-STATION SMOKE ALARM
SHALL
SMOKE DETECTOR MAINTENANCE
43
Multiple Choice
A building, occupancy or structure located in the city that is equipped with a fire alarm system that transmits an alarm signal to the department or a central station that monitors such system for the purposes of reporting fire alarms to the department, whether or not the installation of such system on the premises is required by law
SINGLE-STATION SMOKE ALARM
PROTECTED PREMISES
SMOKE ALARM
SMOKE DETECTOR
44
Multiple Choice
A single-or multiple-station alarm responsive to smoke and not connected to a fire alarm system
SINGLE -STATION SMOKE ALARM
SMOKE ALARM
SMOKE DETECTOR
45
Multiple Choice
A signal initiated by the fire alarm system or device indicative of a fault in a monitored circuit or componen
SMOKE ALARM
TROUBLE SIGNAL
SMOKE DETECTOR
SMOKE
46
Multiple Choice
An alarm signal transmitted by a fire alarm system which failed to function as designed as a result of improper installation, improper maintenance, malfunction, or other factor. Examples of unwarranted alarms are alarms resulting from improper smoke detector placement, improper detector setting for installed location, lack of system maintenance, and control panel malfunction. It is important to know that the alarm verification feature reduces the number of unwarranted alarms
TROUBLE SIGNAL
UNNECESSARY ALARM
UNWARRANTED ALARM
47
Multiple Choice
A certificate issued by the commissioner to a person engaged in the business of performing smoke detector cleaning and testing, which authorizes such person to engage in such business and supervise the performance of such cleaning and testing by certificate of fitness holders.
TROUBLE SIGNAL
SMOKE DETECTOR MAINTENANCE COMPANY CERTIFICATE
UNNECESSARY ALARM
UNWARRANTED ALARM
48
Multiple Choice
A signal initiated by the fire alarm system or device indicative of a fault in a monitored circuit or component
TROUBLE SIGNAL
UNWARRANTED ALARM
UNNECESSARY ALARM
TERMS S-95
Accessibility
As defined in NFPA admitting close approach: not guarded by locked doors, elevation, and other effective means.
Some text here about the topic of discussion
Show answer
Auto Play
Slide 1 / 48
SLIDE
Similar Resources on Wayground
41 questions
TOEIC - Phrasal Verbs
Presentation
•
Professional Development
41 questions
Shopping, Restaurant and Direction
Presentation
•
University
47 questions
Formazione Capisquadra 2024 Trento
Presentation
•
Professional Development
43 questions
BITER ALERT!!!! Love, Dr. Parker
Presentation
•
Professional Development
44 questions
Polska w czasach stalinizmu
Presentation
•
KG
44 questions
Beyond CAE
Presentation
•
Professional Development
42 questions
30.6 STS Work and Machines Part1
Presentation
•
Professional Development
44 questions
Nine Ways to Stay Safe Online- CISA Lesson
Presentation
•
Professional Development
Popular Resources on Wayground
20 questions
STAAR Review Quiz #3
Quiz
•
8th Grade
20 questions
Equivalent Fractions
Quiz
•
3rd Grade
6 questions
Marshmallow Farm Quiz
Quiz
•
2nd - 5th Grade
20 questions
Main Idea and Details
Quiz
•
5th Grade
20 questions
Context Clues
Quiz
•
6th Grade
20 questions
Inferences
Quiz
•
4th Grade
19 questions
Classifying Quadrilaterals
Quiz
•
3rd Grade
12 questions
What makes Nebraska's government unique?
Quiz
•
4th - 5th Grade