1. A 230 V single phase circuit supplying a pump motor is protected by a 20 A type C circuit breaker to BS EN 60898. The minimum value of fault current to ensure compliance with the thermal and shock requirements is:
a) 20 A
b) 140 A
c) 100 A
d) 200 A
2.
MULTIPLE CHOICE QUESTION
3 mins • 1 pt
2. Given that the fault current on a 16A BS 88 fuse is 60A, the corresponding disconnection time is:
a) 0.5 s
b) 1 s
c) 3 s
d) 10 s
3.
MULTIPLE CHOICE QUESTION
3 mins • 1 pt
3. From the time/current characteristic for a 30A BS 3036 fuse, the approximate current required to operate this device at a time of 5 s is:
a) 30 A
b) 66 A
c) 87 A
d) 180 A
4.
MULTIPLE CHOICE QUESTION
3 mins • 1 pt
4. A 15A protective device to BS3036 when carrying a fault current of 180A has an operating time of:
a) 0.4 s
b) 0.2 s
c) 0.1 s
d) 5 s
5.
MULTIPLE CHOICE QUESTION
3 mins • 1 pt
5. A 30A protective device to BS1361 when carrying a fault current of 200A will operate in:
a) 0.2 s
b) 4 s
c) 0.4 s
d) 5 s
6.
MULTIPLE CHOICE QUESTION
3 mins • 1 pt
6. The symbol used to denote the operating current of the device protecting a circuit against overload is:
a) lb
b) l2
c) ln
d) lz
7.
MULTIPLE CHOICE QUESTION
3 mins • 1 pt
7. A 230 V 30 A radial circuit is protected by a BS 3036 device. If the value of earth loop impedance for the circuit is 2.3Ω, disconnection under Line/earth fault condition will occur in:
a) 2 s
b) 4 s
c) 3 s
d) 5 s