GMJ 9189 PHASE 3 cold water MCQ part 2

Authored by Glen Johnson

Science

Professional Development

Used 8+ times

GMJ 9189 PHASE 3 cold water MCQ part 2
AI

AI Actions

Add similar questions

Adjust reading levels

Convert to real-world scenario

Translate activity

More...

    Content View

    Student View

10 questions

Show all answers

1.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

A pump is required to lift water to a storage cistern at height. A delivery rate of 5kg/s is required and the total length of pipework (including pipe valves and fittings) is 40m. Given a pump efficiency of 75%, what is the required power of the pump in watts?

1,765 watts

1,962 watts

2,609 watts

  2,995 watts

2.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

What should be fitted to the water supply feeding an accumulator to prevent the latter becoming damaged?

Strainer, check valve and pressure reducing valve

Strainer, check valve and gauge

Check valve, pressure relief valve and gauge

Check valve, water softener and regulating valve

3.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

If the mains pressure to an accumulator is 3 bar, then what would be the most suitable air charge pressure within the vessel?

3 bar

2.5 bar

1.5 bar

0.5 bar

4.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

An accumulator has a storage volume of 180 litres. If it feeds a bath tap with a flow rate of 11 litres per minute, how long will the accumulator assist in increasing the pressure before it starts to replenish?

11 mins

16 mins

18 mins

22 mins

5.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

A boosted cold water system is fitted with a break cistern at low level and a storage cistern at high level. The pump seems to have seized after ‘running dry’ for some time. What control component within the system is most likely to have failed and allowed this to happen?

Float operated valve within the storage cistern

Float operated level shut-off switch within the storage cistern

Float operated valve within the break cistern

Float operated low level shut-off switch within the break cistern

6.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

What piece of test equipment is most suitable to check the run current of a boost cold water pump during maintenance or fault-finding activities?

Voltmeter

Multi-meter

Low resistance Ohmmeter

Clip-on Ammeter

7.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

A CWSC is overflowing during off-peak periods. What is the most likely cause?

Blocked distribution pipe outlet

Faulty level switch

Split washer within FOV

Pressure reducing valve set too high

Access all questions and much more by creating a free account

Create resources

Host any resource

Get auto-graded reports

Google

Continue with Google

Email

Continue with Email

Classlink

Continue with Classlink

Clever

Continue with Clever

or continue with

Microsoft

Microsoft

Apple

Apple

Others

Others

Already have an account?