EL0018 - Topic 6 CCC
Authored by Matt G
Other
University
Used 31+ times

AI Actions
Add similar questions
Adjust reading levels
Convert to real-world scenario
Translate activity
More...
Content View
Student View
10 questions
Show all answers
1.
MULTIPLE CHOICE QUESTION
5 mins • 1 pt
What is the minimum distance required to AVOID derating between two 4mm2 single core cables installed on a perforated horizontal cable tray?
(Use Figure 1 in AS 3008)
8mm
4mm
2mm
16mm
2.
MULTIPLE CHOICE QUESTION
5 mins • 1 pt
What is the ambient air temperature that AVOIDS derating?
45°C
35°C
40°C
25°C
Answer explanation
AS 3008 - 3.5.3 & Table 27(1)
40°C
3.
FILL IN THE BLANKS QUESTION
5 mins • 1 pt
A single core cable is installed in an underground wiring enclosure at a depth of 1m. What is the derating factor?
(a)
Answer explanation
AS 3008 - Table 28(2)
4.
FILL IN THE BLANKS QUESTION
5 mins • 1 pt
A twin + earth TPS cable is installed bunched on a surface with 3 other circuits. What is the derating factor for the circuits?
(a)
Answer explanation
AS 3008 Table 22
4 Circuits in total
0.65 derating factor
5.
MULTIPLE CHOICE QUESTION
5 mins • 1 pt
Select the normal operating temperature for V-90 TPS cable
90°C
75°C
105°C
70°C
Answer explanation
AS 3008 Table 1
V-90 Cable is normally used at 75°C
6.
MULTIPLE CHOICE QUESTION
5 mins • 1 pt
Select the term that refers to Maximum Demand
IB
IN
IZ
Answer explanation
AS 3000 2.5.3.1
7.
MULTIPLE CHOICE QUESTION
5 mins • 1 pt
What is the minimum size of the protective earthing conductor for a 95mm2 Aluminium XLPE single core cable installed underground?
25mm2
95mm2
35mm2
16mm2
Answer explanation
AS 3000 Table 5.1