Air supplies and fire pump math

Total questions: 18

Worksheet time: 9mins

Name
Class
Date
1.

The purpose of the air maintenance device is to provide a _________ air supply to the system

a)

Regulated and filtered

b)

Regulated and restricted

c)

Warm and moist

d)

Regulated and full flow

2.

The purpose of the fast fill valve on an air maintenance device is to ______?

a)

Repressurise the system quickly

b)

Allow the system to trip more quickly

c)

Drain the system quicker

d)

Fill the system with water when testing

3.

One reason nitrogen is used in lieu of air is________?

a)

It puts out the fire quicker

b)

It’s cheaper

c)

It helps prevent corrosion

d)

It plugs leaks in the system piping

4.

The “cut in” pressure on a pressure switch is when______?

a)

The valve trips

b)

The air compressor starts

c)

The fire reaches the test connection

d)

The compressors stops

5.

When installing a tank mounted compressor with isolation pads, it’s important to______?

a)

Torque all bolts to 90lbs

b)

Draw the bolts tight to keep the compressor from moving

c)

Not to draw the bolts too tight

d)

Use a thread locking compound on all bolts

6.

The minimum pipe size for an air supply is?

a)

1”

b)

Half the size of the riser pipe

c)

1/2”

d)

3/4”

7.

In a differential dry valve, the regulator on the air maintenance device should set?

a)

10 psi above the trip pressure

b)

At 30 pounds

c)

At 40 pounds

d)

20 psi above the trip pressure

8.

The air supply piping for a dry valve should be installed

a)

Below the clapper

b)

Above the priming water level

c)

In the intermediate chamber

d)

Vertical

9.

The air supply shall repressurize the system within

a)

30 minutes

b)

30 minutes and 60 minutes for refrigerated spaces

c)

20 minutes

d)

According the manufacturers recommendations

10.

Multiple dry systems can be maintained by a single air maintenance device

a)

True

b)

False

11.

The “peak” flow of a 1000 gpm Pump should flow?

a)

1000 gpm

b)

3 hose streams

c)

1500 gpm

d)

15000 gpm

12.

If your 1500 gpm fire pump is flowing at 40%, how many gpm’s are you flowing?

a)

600 gpm

b)

1900 gpm

c)

1100 gpm

d)

2250 gpm

13.

If suction pressure is 45psi and discharge pressure is 162, what is the net pressure of the fire pump?

a)

207 psi

b)

116 psi

c)

.443

d)

117 psi

14.

At pump output is rated for 100 feet of head or about?

a)

22 psi

b)

43 psi

c)

75 psi

d)

116 psi

e)

231 psi

15.

A pump output is rated for 150 feet of head or about?

a)

65 psi

b)

68 psi

c)

346.5 psi

d)

94 psi

16.

The net pressure of a horizontal split case pump is 67 psi, the discharge pressure is 179 psi, what is the suction pressure?

a)

102 psi

b)

246 psi

c)

43 feet of head

d)

112 psi

17.

The Local 669 JATC Training Director is

a)

Charles Ketner

b)

Brian Dunn

c)

Kevin Watson

d)

Brian Fischer

18.

The end of the first quarter for WCC is?

a)

January 1

b)

December 31

c)

March 1

d)

March 31