Total questions: 53

Worksheet time: 13hrs 15mins

Name
Class
Date
1.

How much value of secondary current of a transformer with 3 Ampere passing in the primary winding and 200 volts if there is 100 volts in the secondary winding?

a)

Is = 3 A

b)

Is = 5A

c)

Is = 0.166A

d)

Is = 6A

2.

Refer to the figure below, if the step-down transformer has a 3:1 ratio, what is the value of secondary voltage and current?

a)

110V , 2A

b)

80 V, 1.5A

c)

120V, 1A

d)

220V, 1A

3.

What is the voltage applied on the load?

a)

1000 Volts

b)

500 Volts

c)

250 Volts

d)

65.5 Volts

4.

Refer to figure below. What is the load current of transformer?

a)

3 A

b)

2 A

c)

6 A

d)

1 A

5.

Refer to figure below. What is the primary voltage of this circuit and load power?

a)

200 V

b)

50 V

c)

500 V

d)

300 V

6.

Power factor is defined as______________________

a)

The property of a device or component to store an electrostatic charge

b)

The ratio of true power to apparent power

c)

The electrical property of a circuit that oppose any change in the current flowing in it

d)

The force that moves free electrons along the conductor

7.

What is called the states how much reactive load the circuit contains?

a)

True power

b)

Reactive power

c)

Apparent power

d)

Power factor

8.

When there is an inductive load, some of the power supplied is not used to do work. This wasted power is called?

a)

True power

b)

Reactive power

c)

Apparent power

d)

Power factor

9.

When there is a resistive load, the power supplied is used to do work. This type of power is called?

a)

True power

b)

Reactive power

c)

Apparent power

d)

Power factor

10.

The power factor of the Capacitive load is__________________

a)

11

b)

0.0

c)

0.1

d)

1.0

11.

The power factor is Large when reactive power is_________________

a)

Zero

b)

Low

c)

High

d)

1.0

12.

The power factor is Small when reactive power is_________________

a)

Zero

b)

Low

c)

High

d)

1.0

13.

The power factor of the resistive load is__________________

a)

11

b)

0

c)

0.1

d)

1.0 (100%)

14.

The power factor is calculated by the following formula

a)

PF = True Power / Reactive Power

b)

PF = True Power x Reactive Power

c)

PF = True Power / Apparent Power

d)

PF = True Power x Apparent Power

15.

What is unit of apparent power measured?

a)

Watt

b)

VAR

c)

Volte amperes (VA)

d)

All of above

16.

What is unit of True power measured?

a)

Watt

b)

VAR

c)

Volte amperes (VA)

d)

All of above

17.

What is unit of Reactive power measured?

a)

Watt

b)

VAR

c)

Volte amperes (VA)

d)

All of above

18.

The apparent power is the sum of ________________

a)

Active and reactive power

b)

Active and apparent power

c)

Reactive and apparent power

d)

Active and true power

19.

The formula used to calculate the active/true power in single phase transformer is_________________

a)

Active Power = V x I x tan θ

b)

Active Power = V x I x PF

c)

Active Power = V x I x sin θ

d)

Active Power = V / I x cos θ

20.

What is the power factor value of a transformer with apparent power 100 VA and true power 90 watt?

a)

1.11

b)

0.11

c)

0.9

d)

90

21.

How much is the active power of a transformer with apparent power 100 VA and power factor 0.9 ?

a)

100 watts

b)

100 vars

c)

90 watts

d)

90 vars

22.

Refer to the figure below has an induction motor calculate the apparent power and line current. Given P = 49.2 W, PF = 0.7(70%) lagging

a)

100.23 VA ,1.5 A

b)

70.23 W ,0.59 A

c)

70.23 VA ,0.59 A

d)

100.23 W ,5.5 A

23.

A welding transformer draws 100A at 200 V. a wattmeter Shows is taking 16 KW of power .Calculate the power factor

a)

0.7

b)

0.8

c)

0.9

d)

1.0

24.

If a 240V circuit has a measured power of 86.4 W, and a power factor of 0.8 lagging, what is the circuit’s apparent power and line current?

a)

100.23 VA ,0.5 A

b)

108 VA ,0.45 A

c)

108 W ,0.45 A

d)

95 VA , 1.5 A

25.

If a transformer supplied 120 V output to a load with a true power of 48.6 W and a power factor of 0.9 lagging, what is the circuit’s apparent power and line current?

a)

54 VA ,0.45 A

b)

108 VA ,0.45 A

c)

108 W ,0.45 A

d)

95 VA , 1.5 A

26.

If an equipment transformer draws 50 A at 110 V and wattmeter readings show the transformer is taking 5170 W, what is the power factor?

a)

0.8

b)

0.7

c)

0.94

d)

1.0

27.

Refer to the figure below; calculate the apparent power and line current. Given P = 49.2 W, PF = 0.9 (90%) lagging.

a)

53.66 VA, 0.35 A

b)

54.66 VA, 0.45 A

c)

55.66 VA, 0.55 A

d)

56.66 VA, 0.65 A

28.

In a transformer, what should power out equal to?

a)

Power rated

b)

Rated capacity

c)

Nameplate data

d)

Power input

29.

How are power transformer rated?

a)


V

b)

VAR

c)

KVA

d)

Watts

30.

It is the amount of power the transformer can deliver without overheating

a)

Rated capacity

b)

Rated voltage

c)

Rated current

d)

Rated output

31.

It is the ampacity of winding conductor in transformer ________________

a)

Rated capacity

b)

Rated voltage

c)

Rated current

d)

Rated output

32.

It is the type and thickness of winding insulation in the transformer _______

a)

Rated capacity

b)

Rated voltage

c)

Rated current

d)

Rated output

33.

It is the ability to dissipate heat in the transformer __________________

a)

Rated capacity

b)

Rated voltage

c)

Rated current

d)

Rated power

34.

The power ratings for transformer and AC __________________ since most ac circuit have reactive load.

a)

True power

b)

Reactive power

c)

Apparent power

d)

Power factor

35.

What is the difference between the power applied to the primary, and the output at the secondary of a transformer.

a)

Power rated

b)

Rated capacity

c)

Power output

d)

Power loss

36.

What is the difference between the power applied to the primary, and the output at the secondary of a transformer.

a)

Power rated

b)

Rated capacity

c)

Power output

d)

Power loss

37.

Why transformer is rated in VA?

a)

Because most Ac circuits have resistive loads

b)

Because most Ac circuits have Capacitive loads

c)

Because most Ac circuits have Reactive loads

d)

Because most Dc circuits have resistive loads

38.

Why transformer is rated in VA?

a)

Because most Ac circuits have resistive loads

b)

To ensure the winding are able to carry the additional current for reactive load

c)

Because most Ac circuits have active loads

d)

To ensure the winding are able to carry load

39.

The apparent power is the of ________________

a)

Active power + Reactive power

b)

Active power X Reactive power

c)

Active power - Reactive power

d)

Active X true power

40.

Refer to figure shown transformer polarity. What is the relationship between primary and Secondary in Part (A)?

a)

Diagonally opposite

b)

Directly opposite

c)

Parallel opposite

d)

series opposite

41.

Refer to figure shown transformer polarity. What is the relationship between primary and Secondary in Part (B)?

a)

Diagonally opposite

b)

Directly opposite

c)

Parallel opposite

d)

series opposite

42.

The terminal leads of the transformer secondary winding are labelled as:

a)

X1 & X2

b)

S1 & S2

c)

H1 & H2

d)

P1 & P2

43.

Refer to the figure below, how are the secondary transformer windings connected and what is the output across 1-2, 2-3, 1-3.

a)

Parallel, V1-2 = 60V, V2-3 = 60V, V1-3 = 120V

b)

Series, V1-2 = 60V, V2-3 = 220V, V1-3 = 220V

c)

Parallel, V1-2 = 120V, V2-3 = 60V, V1-3 = 60V

d)

Series, V1-2 = 60V, V2-3 = 60V, V1-3 = 120V

44.

What is the output voltage between X1 and X4 if the primary voltage at terminal H1and H2 is 100 volts and H3and H4 is 100 volts?

a)

25 volts

b)

200 volts

c)

50 volts

d)

100 volts

45.

What is the total voltage of a single phase transformer with two secondary winding connected in parallel, voltage rate 100V each?

a)

50 volts

b)

0 volt

c)

100 volts

d)

200 volts

46.

What type of polarity is shown in figure below?

a)

Parallel

b)

Series

c)

Additive

d)

Subtractive

47.

What is the total voltage of a single phase transformer with two secondary winding connected in series, voltage rate 100 volts each?

a)

50 volts

b)

200 volts

c)

0 volt

d)

100 volts

48.

Refer to the figure. How are the secondary transformer windings connected and what is the output across 1-2, 2-3, 1-3:

a)

Series, V1-2 = 48V, V2-3 = 96V, V1-3 = 96V

b)

Parallel, V1-2 = 96V, V2-3 = 48V, V1-3 = 48V

c)

Parallel, V1-2 = 48V, V2-3 = 48V, V1-3 = 96V

d)

Series, V1-2 = 48V, V2-3 = 48V, V1-3 = 96V

49.

Refer to figure below , what is the turn ratio if the primary winding and secondary winding are connected as shown in the figure.

a)

1:1

b)

2:1

c)

1:2

d)

4:1

50.

If the H1 and X1 are of diagonally opposite, the transformer polarity is:

a)

Parallel

b)

Subtractive

c)

Additive

d)

Series

51.

Refer to figure shown. What is the turn ratio if the primary winding and secondary winding are connected as shown in the figure.

a)

4:1

b)

1:1

c)

1:2

d)

2:1

52.

Refer to figure below , what is the turn ratio if the primary and the secondary winding are connected as shown in the figure.

a)

1:2

b)

2:1

c)

4:1

d)

1:1

53.

Which type of polarity is shown in the figure?

a)

Parallel

b)

Additive

c)

Series

d)

Subtractive