WorksheetsFINALS - ME LAWS ETHICS CONTRACTS CODES AND STANDARDS
Total questions: 60
Worksheet time: 45mins
A special system discharging of a foam made from concentrates. Either mechanically or chemically over the area to provide protection.
Foam extinguishing system
HalogenatedeE Extinguishing system
Carbon dioxide extinguishing system
Deluge system
A fire extinguishing system using one or more atoms of an element from the halogen chemical series, fluorine, chlorine, bromine and iodine.
Foam extinguishing system
Halogenated extinguishing system
Carbon dioxide extinguishing system
Deluge system
An alarm caused by mechanical failure, malfunction, improper installation of lack or proper maintenance, or an alarm activated by cause that cannot be determined
Mechanical alarm
Unintended fire alarm
Smoke alarm
Nuisance alarm
Standpipe system providing 2 and ½ inch (64mm) hose connections to supply water for use by fire departments and those trained in handling heavy fire streams.
Class I systems
Class II systems
Class III systems
Class IV systems
Standpipe system providing 1 and ½ inch (38mm) hose connections to supply water for use of primarily by the building occupants or by fire department during initial response
Class I systems
Class II systems
Class III systems
Class IV systems
Standpipe system providing 1 and ½ inch (38mm) hose connections to supply water for use of primarily by the building occupants and 2 ½ in (65mm) hose connection to supply larger volume of water for use by fire departments and those in handling heavy fire streams
Class I systems
Class II systems
Class III systems
Class IV systems
A solution of water and potassium carbonate based chemical, potassium acetate based chemical or a combination thereof, fanning and extinguishing agent.
Halogenated extinguishing agent
Foam extinguishing agent
Wet Chemical extinguishing agent
Manual wet agent
The responsible for the maintenance of a particular fire protection system
Fire tender
Fire man
Impairment coordination
Bureau of fire protection
A system or a part of a system that can transmit and receive signals without the aid of wire
Wireless protection system
Automatic protection system
Computerize protection system
Laser alarm system
A dry standpipe system that does not have a permanent water supply attached to the system. It requires water from a fire department pumper to be pumped into the system through the fire department connection in order to supply the system demand
Manual dry
Manual wet
Bulk storage
Deluge
A wet standpipe connected to a water supply for the purpose of
maintaining water within the system but to which does not have a water
supply capable of delivering the system demand attached to the system. It
requires water from a fire department pumper (or like that) to be pumped
into the system through the fire department connection in order to supply
the system demand.
Manual dry
Manual wet
Bulk storage
Deluge
Sprinkler system shall have pressure zones so that sprinkler heads will not be subjected to pressure that is.
More than 175 psi
Less that 100 psi
More than 150 psi
Less than 150 psi
All structures occupied for the manufacture of storage of articles of cellulose nitrate ( pyroxylin ) plastic shall be equipped with an approved automatic fire extinguishing sprinkler system capable of discharging.
1.66 gal/min/sq. ft.
1.45 gal/min/sq. ft.
2.00 gal/min/sq. ft.
2.50 gal/min/sq. ft.
Dry chemical extinguishing system shall be inspected and tested for proper operation at how many months interval?
3 months
4 months
6 months
12 months
Foam extinguishing system shall be provided in buildings used as:
Call center venue
Malls
Offices
Maintenance aircraft hangars
Overhead foam water sprinkler system proved closed head foam water sprinkler in aircraft servicing area of minimum water solution rate of:
0.25 gal/min/sq. ft. of floor area
0.61 gal/min/sq. ft. of floor area
0.30 gal/min/sq. ft. of floor area
0.50 gal/min/sq. ft. of floor area
For wet pipe foam water sprinkler systems, at what temperature is the sprinkler head quick response?
50 deg. F
37 deg. F
75 deg. F
100 deg. F
High pressure cylinders shall be weighed and the date of hydrostatic test shall be verified at:
3 months
4 months
6 months
12 months
Carbon dioxide extinguishing system shall be inspected and tested for proper operation at how many months interval?
3 months
4 months
6 months
12 months
Dry standpipe (Class I or III) shall be limited to:
8 storey building
More than 8 storey
Less than 8 storey building
4 storey building
Wet standpipe (class I or III) shall be limited to
8 storey building
More than 8 storey
Less than 8 storey building
4 storey building
Underground buildings shall be equipped throughout with what class automatic wet or manual wet stand pipe?
Class I
Class II
Class III
Class IV
Elevators are required for how many storey buildings?
4 storey
3 storey
5 storey
5 storey and above
A special system discharging a foam made from concentrates, either mechanically or chemically, over the area to provide protection.
Foam extinguishing system
Halogenated extinguishing system
Wet-chemical extinguishing agent
Dry-chemical extinguishing agent
A fire-extinguishing system using one or more atoms of an element from the halogen chemical series fluorine, chorine, bromine and iodine.
Foam extinguishing system
Halogenated extinguishing system
Wet-chemical extinguishing agent
Dry-chemical extinguishing agent
A solution of water and potassium-carbonate-based chemical. Potassiumacetate-based chemical or combination thereof, fanning an extinguishing agent.
Foam extinguishing system
Halogenated extinguishing system
Wet-chemical extinguishing agent
Dry-chemical extinguishing agent
Any flexible plan building or open plan building in which the travel distance of how many meters to exits must have approved and supervised sprinkler systems?
Exceeds 46m distance
Exceeds 40m distance
With 30m distance
More than 30m distance
All building shall be protected throughout by an approved, supervised sprinkler system except in buildings where all guest suites door opening directly outside at the street or grade level or exterior exit access in buildings up to and including:
3 storey in height
2 storey in height
10 storey in height
5 storey in height
All business occupancy buildings over what height shall be provided with automatic sprinkler system?
15 m high
20 m high
10 m high
12 m high
Fire extinguishers should be installed in plain view, in an accessible spot near room exits, which provides an escape route. It should be located away from fire hazards and installed at what height above the floor?
1,500 mm
2,000 mm
1,200 mm
3,000 mm
Sprinkler system shall have pressure zones so that sprinkler heads will not be subjected to pressure that is more than.
150 psi
250 psi
175 psi
100 psi
Carbon dioxide extinguishing system shall not be installed in areas normally occupied by:
machineries
Flammable gases
Persons (people)
Heavy equipment
The age limit of a horizontal return tubular. Flue or cylinder boiler having a longitudinal lap joint and operating a pressure in excess of 0.345MPa or 3.45 Bar gage shall be how many years?
30 years
50 years
40 years
25 years
When boilers are replace or new boilers are installed in either existing or new buildings, aminimum height of at least how many mm shall be provided between the top of the boiler proper and the ceiling?
2,130 mm
4,500 mm
1,230 mm
3,120 mm
What is the minimum height from any highest point of any valve stem and the ceiling for new boiler installation if it is a single installation or self contained boiler?
915 mm
2,130 mm
1,025 mm
550 mm
A compressor or portion of a condensing unit supported from the ground shall rest on a concrete or other approved base extending _______ above the adjoining ground.
More than 5 inches
Not less than 3 inches
Not more than 3 inches
Not less than 5 inches
Permanent gravity ventilation openings of ____ net free area opening directly to the outside of the building or extending to the outside of the building by continuous duct.
Not less than 5 sq.ft.
Not less than 2 sq.ft.
Not less than 4 sq.ft.
Not less than 3 sq.ft.
A mechanical exhaust system arranged to provide a complete change of air in such a rom or space of at least every how many minutes to discharge to the outside of the building?
20 min
30 min
10 min
45 min
Ducting used for conveying air at temperatures not exceeding what
temperature to or from occupancy through other than heating or air
conditioning systems such as ventilation for human usage, domestic
kitchen range exhaust, bathroom exhaust ducts and domestic types
clothes dryer exhaust ducts
121 deg C
100 deg C
150 deg C
95 deg C
Spaces provided with natural ventilation shall have minimum permanent wall opening of how many percent of the net occupied area?
7%
4%
10%
8%
For naturally ventilated spaces without direct wall opening the the outdoors (interior room) except through adjoining rooms, the opening between rooms shall be permanently unobstructed and shall have free area of not less than how many percent of the occupied area?
7%
4%
10%
8%
Determine the outdoor air rate required for a single zone AC unit serving an interior 2000 sq.ft . meeting/conference room with a design occupancy of 100 people. Note: the system supplies and returns are from the ceiling.
450 cfm
500 cfm
620 cfm
300 cfm
LPG are mixture of hydrocarbons liquefy under pressure for efficient transportation, storage and use. LPG are generally composed of ethylene, propane, propylene, butane, isobutene and butylenes. However commercially they
( LPG ) are classified as mixtures
Propane and butane
Propylene and isobutene
Ethylene and Propane
Propane and Propylene
It is defined as a petroleum distillate having a flash point not below 22.8 deg. C as determined by Abel tested which is equivalent to 22.8 deg. C as an illuminant when burned in a wick lamp.
Diesoline
Butane
Kerosene
Gasoline
Which of the following mixture of air and gasoline vapors are explosive?
1.3% to 6.0%
1.0% to 4.0%
1.0% to 5.0%
1.3% to 2.0%
It is a solid infusible, cellular residue left after fusible bituminous coals are heated in the absence of air, above temperatures at which active thermal composition of the cost occurs.
Wood
Hugged fuel
Coke
Water gas
They are frequently described as “paraffinic”, “ naphthelic ”, or mixed base,” according to the physical characteristics.
Crude oils
Gaseous fuels
Premium oil
LPG
Standard railings shall be at least what height from the upper surface of the top of the rail to the floor level?
At least 1000 mm
At least 1500 mm
At least 1200 mm
At least 900 mm
Work rooms (referring to maintenance shop and machine room) shall be at what height from the floor to ceiling?
At least 3000 mm
At least 4000 mm
At least 4500 mm
At least 1500 mm
The maximum number of persons working or will be working shall not exceed 1 person per how many square meters?
10
12
20
15
Foundation mass should be how many times the weight of the machinery it is supposed to support?
3 to 5 times
2 to 3 times
5 to 7 times
10 to 20 times
Foundation mass should be how many times the weight of the machinery it is supposed to support if the unbalance forces produced by the machine can be calculated to dampen vibration?
3 to 5 times
2 to 3 times
5 to 7 times
10 to 20 times
The weight of the machine plus the weight of the foundation should be distributed over a sufficient soil area which is large enough to cause a bearing stress with the safe bearing capacity of the soil with factor of safety equivalent to:
4
5
6
10
Machine foundation should be isolated from floor slabs or building footings at what distance around its perimeter to eliminate transmission of vibration.
20 mm
12 mm
25 mm
18 mm
Foundation bolts of specified size should be used and surrounded by a pipe sleeve with an inside diameter of at least how many times the diameter of anchor bolt.
3 times
Twice
4 times
1.5 times
Any boiler which does exceed any of the following: 405 mm inside diameter and 1065 mm overall length of outside to outside heads at center.
Portable boiler
locomotive
Miniature boiler
Power boiler
A closed vessel intended for use in heating water or for application of heat to generate steam or other vapor to be used externally to itself.
boiler
Steam generator
Boiler or steam generator
None of these
A vessel in which pressure is obtained from an external sources, or from an indirect application of heat.
Unfired pressure vessel
Locomotive power boiler
Pressure vessel
Low pressure boiler
Any boiler or unfired pressure vessel constructed, installed, placed in operation but subjected to annual inspection.
Existing installations
Hot water boiler
New boilers
Reinstalled boilers
A boiler in which that has been inspected and declared unsafe to operate or disqualified stamped and marked indicating its rejection.
Second hand
Condemned
Reinstalled
Unfired