NLC FINAL TRANSFORMER

Total questions: 56

Worksheet time: 28mins

Name
Class
Date
1.

Which of these statements about a wye-wye bank is true?

a)

The “lighter” transformer is larger in KVA than the other two

b)

The industry standard is to leave the x2 idle when connecting the coils in parallel

c)

Each of the three transformer provides one hot leg to deliver three-phase power

d)

When connecting wye-wye, you must float the wye point

2.

Which piece of test equipment checks the transformer coil for insulation damage?

a)

Turns ratio tester ( TTR)

b)

Continuity test

c)

Transformer last check

d)

Megger

3.

System - 12,000

Nameplate - HV 12,000/20,800Y ---LV 120/240

KVA - 15 and 25

Service - 120/240 - 3 phase

If connected properly, what will the voltage be between lighter x1 and power x1?

a)

120 volts

b)

416 volts

c)

208 volts

d)

240 volts

4.

The phase current is 1.73 times higher than a coil current in a _____ connection bank

a)

Wye

b)

Delta

c)

Y

d)

Neutral

5.

Which arrow is pointing at the pressure relief valve?

a)

A

b)

B

c)

C

d)

D

6.

Which of these definitions best explains impedance?

a)

The direction of current flow through the two coils

b)

It is the process by which oil circulates, cooling the core/coil assembly

c)

Expressed in percentage, it is the comparison of the number of turns between the windings

d)

Total opposition to current flow, caused by the transformer itself

7.

Which of these connections is the correct one?

a)

A

b)

B

c)

C

d)

D

8.

The system voltage is 1.73 times higher than the coil voltage in a ___ system

a)

Wye

b)

Delta

c)

Neutral

d)

Phased

9.

If connected correctly, using transformers of different______ will work electrically but can cause

confusion for lineworkers who may need to work on the transformer bank in the future.

a)

Polarity

b)

Circuit voltages

c)

Kva ratings

d)

Transformer voltage ratings

10.

System - 12,000

Nameplate - HV 12,000/20,800Y ---LV 120/240

KVA - 15 and 25

Service - 120/240 - 3 phase

Where will the x2 on the "power" transformer connect?

a)

Leave idle

b)

System neutral ( N)

c)

Conductor ( P)

d)

Conductor ( H)

11.

Which of these statements refers to a wye connection?

a)

Each transformer’s x1 connects to another transformer’s x2

b)

H1s connect to phases, and H2s connect together and may or may not be grounded

c)

Each transformer’s h1 connects to another transformer’s H2

d)

X1 connects to x3 “ all the way around

12.

Which of the following statements about tap changers is true?

a)

The tap changer is a no-load manual switch connected to the secondary coil

b)

The tap changer is a load manual switch connected to the primary coil

c)

Each tap raises or lowers the secondary voltage by 2.5% or 4.5%

d)

If a tap is raised, the number of turns in the secondary coil is reduced

13.

What are "H1A" and "H1B"?

a)

The low- voltage bushings on a padmount transformer

b)

The primary bushings on a padmount transformer

c)

The primary bushings on a pole-bolted transformer

d)

The secondary bushings on an overhead transformer

14.

Study each of the above connections carefully and choose the correct one.

a)

A

b)

B

c)

C

d)

D

15.

In a delta-wye bank, what would be a typical hot leg-to-neutral voltage?

a)

120

b)

208

c)

416

d)

480

16.

In a wye-wye bank, which of the following would be a typical hot leg-to-hot leg voltage?

a)

277

b)

240

c)

120

d)

208

17.

Which transformer nameplate rating will allow the connection to be made on a system voltage of 14,400/24,900?

a)

24,900GRDY/ 14,400

b)

14,400

c)

14,400 GRDY / 8,320

d)

12,470/ 14, 400Y

18.

Which of the nameplate ratings matches the connection in the image?

a)

7,200/ 12,470Y

b)

7,200 GRDY/ 12,470

c)

12,000

d)

12,470GRDY/ 7,200

19.

Choose the statement below that best reflects the points of termination.

a)

The secondary bushings have more insulation than the primary bushings

b)

The labeling of the secondary bushings changes based on polarity

c)

The H2 bushings is always on the left when facing tha transformer

d)

The H1 bushing is always on the right when facing the transformer

20.

Which of these transformers is "additive"?

a)

12,000- 15 kVA

b)

2,400/ 4,160Y- 250 kVA

c)

7,200/ 12,470Y- 250 kva

d)

7,200/ 12, 470Y- 15 kVA

21.

What does "non-PCB" refer to?

a)

The epoxy-live material used to coat and insulate the winding

b)

The lack of a harmful substance in the newer insulating fluids

c)

The old askarel- impregnated paper between the layers of widings

d)

The direction that the primary winding is wrapped around the care

22.

Which of these have fuses that are located internally but operated externally?

a)

Conventional tramsformer

b)

Pole-mounted tramsformer

c)

Padmount transformer

d)

CSP transformer

23.

Which of these transformers is "subtractive"?

a)

When facing the transformer, X1 bushing in on the right

b)

When facing the transformer, x1 bushing is on the left

c)

The other end of the primary winding in the case ground

d)

Whem facing the transformer, the h2 bushing is on the right

24.

Which of these transformers is "subtractive"?

a)

12,000- 10 KVA

b)

7,200/12,470- 37.5 KVA

c)

2,400/ 4,160- 15 kVA

d)

2,400/ 4160- 150 kVA

25.

A standard transformer cools itself by:

a)

CCirculating fluld through an oil pump

b)
  • Relying on the ambient air temperature

c)
  • Circulating oil by convection

d)
  • Releasing pressure through the relief valve

26.

The primary windings:

a)
  • Have larger conductors than the secondary

b)
  • Use thin, laminated sheets of aluminum

c)
  • Have smaller sized wire than the secondary

d)
  • Are coated with silicon to improve efficiency

27.

Changing the number of turns in the coils will:

a)

Increase the efficiency of the transformer

b)

Induce more direct current

c)

Affect the amount of induced voltage

d)

Maximize convection

28.

Select the true statement about transformer identification.

a)
  • A CSP is protected internally by a current-limiting fuse

b)
  • A CSP is protected internally by a voltage-limiting fuse

c)
  • Bay-O-Net fuses are used in padmount transformers to isolate between HIA
    and H1B

d)
  • A transformer can be fed only from the primary bushings

29.

In relation to windings, what do A, B, C, and D refer to?

a)
  • The points where the core/coil assembly mounts to the inside of the case

b)
  • A and B are the primary winding ends; C and D are secondary winding ends

c)
  • The ends of the high-voltage windings where they connect to the breaker

d)
  • The ends of the secondary windings, where they attach to the low-voltage
    terminals

30.

Which statement below about KVA is true?

a)
  • An average-size home will draw a peak load of less than 1 KVA

b)
  • The KVA refers to the voltage rating of the input winding

c)
  • When transformers are banked together, the bank's rating is the sum of the individual transformers

d)

The kVA number refers to the amperage rating of the transformer

31.

Select the term that refers to the comparison of turns between the windings.

a)
  • Turns ratio

b)
  • Induction

c)
  • Step up or step down, depending on the source

d)

Polarity

32.

Which of these statements about transformers is true?.

a)
  • The primary side is the load side or customers side

b)
  • A transformer works only on direct-current systems, not alternating-current systems

c)
  • The primary side connects to the source; the secondary side connects to the load

d)
  • Transformers step the current down to a consumable level

33.

What is the purpose of the core?

a)

Concentrate the magnetic lines of flux, Improving efficiency

b)
  • Provide the connection between the two windings

c)
  • Malntain the form of the concentrically wound colls

d)
  • Suspend and isolate the colls inside the transformer

34.

Select the true statement about conventional transformers.

a)
  • They use an external fused device to protect against fault current

b)
  • They sometimes come with a red light to Indicate abnormal loading conditions

c)
  • They have secondary breakers connected between the windings and the primary
    bushings

d)
  • They rely on internal cutouts for surge suppression

35.

Which of these statements about padmount transformers is true?

a)

They are normally fed from the load side

b)

They are physically attached to a conductor using hangar bolts

c)
  • They receive their feed from an underground conductor

d)
  • They connect directly to an overhead conductor

36.

A coll of wire will become energized if it is placed close to another coil of wire attached to a source of power. What is this phenomenon called?

a)
  • Capacitance

b)
  • Induction

c)

Convection

d)

Mutual reactance

37.

Which of the following is determined by the direction that the secondary coll is wrapped in relation to the primary coil?

a)
  • Whether or not the voltage is stepped up or stepped down

b)

Turns ratio

c)

Impendece

d)

Polarity

38.

What is the most popular material for the windings?

a)
  • Amorphous steel

b)

Silicon-oriented steel, or electrical steel

c)

Aluminum

d)

Copper

39.

Which of these is a CSP?

a)

A

b)

B

c)

C

d)

D

40.

What is the turns ratio of a 7,200/12,470 transformer, with an output of 120/240?

a)

1:30

b)

1:60

c)

15:1

d)

30:1

41.

Which of these statements about a wye-delta bank is true?

a)

If they come with only two secondary bushings, then the secondary must be connected delta

b)

Use the phrase "Alley-Cat, Bad-Dog" when paralleling the windings

c)

The "power"-leg-to-hot leg voltage is 240 in a 120/240, three-phase service

d)

The "power" transformer is larger in kVA than the other two

42.

If the transformer has only one number for a primary coil voltage rating, the transformer:

a)

Should be used on wye systems only

b)

Should be used for delta connections only

c)

Can be used only for open banks

d)
  • Should be used for phase-to-ground connections only

43.

Which of these statements regarding non-standard connections is true?

a)
  • You can get 120/208 from single-phase delta

b)
  • To complete a three-phase connection, you must ground at the x2 only

c)
  • It's possible to get two 120/208 three-phase services from one delta-delta bank

d)
  • A delta or wye can be grounded one time at any coil terminal and still operate properly

44.

In a delta-delta bank, what would be a typical hot leg-to-ground voltage?

a)

120

b)

208

c)

277

d)

480

45.

Which kind of secondary service voltage requires the wye point on the primary to be floated?

a)

240/416

b)

277/480

c)

120/208

d)

240/480

46.

Which one of these banks is connected correctly?

a)

A

b)

B

c)

C

d)

D

47.

Which of these service voltages on a work order require "Alley-Cat, Bad-Dog"?

a)

240

b)

240/480

c)

120/208

d)

120/240

48.

Which of these statements about a delta-wye is true?

a)

You must tie the wye point on the primary

b)

The H1s all tie together but do not connect to neutral

c)

The x2 bushings from each transformer tie together and connect to neutral

d)

Only one x2 in the entire bank is connected to neutral

49.

In a wye-delta bank, which of the following would be a typical hot leg-to-hot leg voltage?

a)

120

b)

240

c)

416

d)

277

50.

Which of these statements abeut utilities' preferences is true?

a)

Three-phase transformers are preferred because they have multiple applications

b)

It's easier and less expensive to replace one single-phase unit in a bank

c)
  • Utilities find that it's easier to install three single-phase transformer units

d)
  • Using a three-phase transformer unit is more economical

51.

Which of these images shows the proper connection, based on the following work order?

Work Order:

System - 7,200/12,470

Nameplate - HV 7,200/12,470Y ---LV 120/240

KVA - 25 and 37.5

Service - 120/240 - 3 phase

a)

A

b)

B

c)

C

d)

D

52.

Which transformer nameplate rating will allow the connection to be made on a system voltage of 4,160/7,200?

a)

7,200/12,470Y

b)

4,160GRDY/ 2,400

c)

7,200GRDY/ 12,400

d)

2,400GRDY/ 4,160

53.

Can a transformer with two primary bushings be connected phase-to-ground?

a)

Yes, two-bushing transformers with the smaller number listed first may be connected phase-to-ground

b)

Yes, all transformers with two primary bushings are designed to accept phase-to-ground connections

c)
  • No, only transformers with one voltage listed can be connected wye

d)
  • No, any transformer with two primary bushings must be connected delta only

54.

Which transformer nameplate rating will allow the connection to be made on a system voltage of 2,400/4,160?

a)

7,200GRDY/4,160

b)

1,387/2,400Y

c)

4,160/7,200Y

d)

2,400GRDY/1,387

55.

Work Order:

System - 12,000

Nameplate - HV 12,000/20,800Y ---LV 120/240

KVA - 15 and 25

Service - 120/240 - 3 phase

If connected properly, what will the voltage be between power x1 and power x3?

a)

208 volts

b)

240 volts

c)

120 volts

d)

0 volts, because that it where the bank ties together

56.

What is the most important part of the transformer

a)

Name plate

b)

Polarity

c)

KVA

d)

Coil