Chapter 12: Water-Based Fire Suppression Systems

Total questions: 159

Worksheet time: 1hrs 20mins

Name
Class
Date
1.

Most fires in sprinkler equipped structures are controlled by the operation of:

a)

four to six sprinklers

b)

three to four sprinklers

c)

one or two sprinklers

d)

all available sprinklers

2.

Fire loss data reveals that in buildings equipped with automatic sprinklers, about ____% of all fires were controlled or extinguished by the system?

a)

75%

b)

89%

c)

98%

d)

94%

3.

The pipe schedule table method is limited to:

a)

all known hazards

b)

occupancies with no known risks

c)

occupancies under a certain size

d)

light and ordinary hazards

4.

The minimum waterflow required for an automatic sprinkler system depends on the hazard being protected, the occupancy classification, and:

a)

fuel load condition

b)

water supply

c)

system maintenance

d)

occupancy load

5.

Which of the following is a factor that determines the minimum waterflow required for an automatic sprinkler system?

a)

Types of heads on the system

b)

Hazard being protected

c)

Area being protected

d)

Proximity to the water supply

6.

When a fire is not controlled in a building that is sprinkler equipped, which of the following is most likely the cause?

a)

Improper maintenance

b)

Weather condition

c)

Combustible debris

d)

Age of the sprinkler system

7.

When heat from a fire affects thermally sensitive devices such as fusible links, the sprinklers:

a)

closest to the fire activate automatically

b)

farthest from the fire activate automatically

c)

all activate automatically

d)

need manual activation

8.

Which sprinkler system consists of interconnected cross mains that provide multiple routes for water to reach any point in the system?

a)
  1. Looped system

b)
  1. Gridded system

c)
  1. Primary system

d)
  1. Traditional system

9.

Which sprinkler system is a common design because of its advantage of water flow from multiple directions?

a)

gridded system

b)

traditional systems

c)

primary systems

d)

looped systems

10.

Which are vertical sections of pipe that connect the underground supply to the rest of the piping system?

a)

system risers

b)

cross mains

c)

branches

11.

Which sprinkler system is a wet pipe system that uses the sprinkler system to circulate water for a non fire protection building services?

a)

Circulating closed loop sprinkler system

b)

Multicycle sprinkler system

c)

Antifreeze sprinkler system

d)

Combined dry pipe system

12.

Which sprinkler system is designed to be operated repeatedly in response to a detection device?

a)

Combined dry pipe and preaction sprinkler system

b)

circulating closed loop sprinkler system

c)

multicycle sprinkler system

d)

antifreeze sprinkler system

13.

Which type of sprinkler system is continually charged with water under pressure that discharges immediately when heat from a fire activates one or more sprinklers?

a)
  1. Deluge

b)
  1. Preaction 

c)
  1. Wet-pipe

d)
  1. Dry-pipe

14.

Which type of sprinkler system is continually charged with air that may or may not be under pressure and operates when a sprinkler opens due to a thermally sensitive device activating?

a)

dry pipe system

b)

wet pipe system

c)

preaction sprinkler system

d)

deluge sprinkler system

15.

Which type of sprinkler system is continually charged with compressed air and is typically used in areas where freezing temperatures are likely to occur?

a)

dry pipe sprinkler system

b)

wet pipe system

c)

preaction sprinkler system

d)

deluge sprinkler system

16.

Which sprinkler system would be MOST likely to be used in special circumstances where an additional level of protection against false activation is required?

a)

multicycle sprinkler system

b)

circulating closed loop sprinkler system

c)

combined dry pipe and preaction sprinkler system

d)

antifreeze sprinkler system

17.

Which type of sprinkler system consists of open sprinklers attached to unpressurized dry pipes and activates when a detection device in the protected area senses a fire?

a)

wet pipe system

b)

dry pipe system

c)

deluge sprinkler system

d)

preaction sprinkler system

18.

All sprinklers discharge water simultaneously in a:

a)

deluge sprinkler system

b)

preaction sprinkler system

c)

dry-pipe sprinkler system

d)

circulating closed loop sprinkler system

19.

Which type of sprinkler is normally provided in a deluge sprinkler?

a)

open

b)

pendant

c)

institutional

d)

upright

20.

Which method of determining the arrangement of pipes for sprinkler systems provides a cost effective design and can be used on all types of hazards?

a)

manufacturer recommendations

b)

pipe schedule tables

c)

estimation formulas

d)

hydraulic calculations

21.

Which type of indicator valve is used in an automatic sprinkler system as an underground gate valve that has a hollow metal post attached to the valve housing?

a)
  1. Post indicator valve assembly (PIVA)

b)
  1. Post indicator valve (PIV)

c)
  1. Outside stem and yoke (OS&Y)

d)
  1. Wall post indicator (WPIV)

22.

Which operating valves in an automatic sprinkler system are located on the riser and used to flow water for testing and waterflow alarm?

a)
  1. Main control valves

b)
  1. Check valves

c)
  1. Drain valves

d)
  1. Alarm test valves

23.

Which operating valve is used to drain water from piping when pressure is relieved in the pipe; may be main drain or auxiliary valves?

a)

alarm-test valves

b)

check valves

c)

drain valves

d)

trim valves

24.

Which operating valve may be globe, ball, or gate vales and used primarily as drains and test valves?

a)

trim valves

b)

drip check valves

c)

drain valves

d)

check valves

25.

Which operating valve is used for drains and to keep water from freezing in pipes and damaging them?

a)

Drip check or drip ball valves

b)

Trim valves

c)

Drain valves

d)

Check valves

26.

What is the purpose of a main waterflow control valve?

a)

Turn off or isolate the water supply to the system

b)

Monitor waterflow for billing purposes

c)

Allow sprinkler water to flow back into the water supply

d)

Prohibit waterflow from being turned off

27.

Which operating valves in an automatic sprinkler system are used to limit the flow of water in one direction?

a)

Drain valves

b)

Check valves

c)

Inspector valves

d)

Alarm test valves

28.

Which valve is usually a globe valve and may sometimes be found at a remote location within a sprinkler system?

a)

Main control valve

b)

Inspector's test valve

c)

Main drain valve

d)

Firefighter's valve

29.

The indicating control valve should be examined to verify that it is:

a)

left in a partially open position

b)

opened fully and secured

c)

closed

d)

open at all times

30.

In which type of sprinkler installation is the sprinkler mounted in a ceiling with the body of the sprinkler above the plane of the ceiling?

a)

Flush

b)

pendant

c)

recessed

d)

upright

31.

In which type of sprinkler installation is the sprinkler recessed and covered with a removable decorative plate that releases when exposed to a specific level of heat?

a)

concealed

b)

recessed

c)

pendant

d)

flush

32.

Which sprinkler is mounted horizontally from a wall and the water is distributed in an arc over a protected area?

a)

Sidewall

b)

Upright

c)

Pendant

d)

Flush

33.

In which type of sprinkler installation is the sprinkler installed upward from a line so that water is discharged up against the deflector?

a)

Upright

b)

Pendant

c)

Sidewall

d)

Flush

34.

In which type of sprinkler installation is the sprinkler installed downward from the branch line so that water flowing from the sprinkler strikes the deflector and is distributed over the protected area?

a)

pendent

b)

concealed

c)

recessed

d)

upright

35.

Which type of sprinkler is a type of spray sprinkler capable of producing characteristics large water droplets and that is listed for its capability of providing fire control of specific high challenge fire hazards?

a)

control mode specific application

b)

early suppression fast response

c)

quick response extended coverage

d)

standard spray

36.

Which type of sprinkler is designed to direct 40 to 60 percent of its discharge in a downward direction?

a)

Old Style/

Conventional

b)

Residential

c)

Early Suppression Fast-Response (ESFR)

d)

Special

37.

Which sprinkler system is designed to cover an area greater than 15 feet?

a)

Extended coverage

b)

Nozzle

c)

Open

d)

Corrosion-Resistant

38.

Which sprinkler system is design with an open orifice and no thermal plug?

a)

Open

b)

Quick-response early suppression

c)

Residential

d)

Nozzle

39.

Which sprinklers system is designed to suppress fires in high-challenge hazards such as warehouses?

a)

Early suppression fast response

(ESFR)

b)

Quick response early suppression

(QRES)

c)

Standard

d)

Open

40.

Which sprinkler system is designed to provide increased life safety in residential occupancies and has a larger area of coverage?

a)

Quick-response early suppression

(QRES)

b)

Quick-response extended coverage (QREC)

c)

Old-style/

Conventional

d)

Nozzle

41.

Which sprinkler system is designed for fast response where life safety is the primary concern?

a)

Residential

b)

Nozzle

c)

Special

d)

Standard

42.

Which sprinkler system is constructed of stainless steel and installed in areas containing acids or caustic materials?

a)

Corrosion-resistant

b)

Dry

c)

Institutional

d)

Standard

43.

Which sprinkler system is designed with no removable parts and made for use in jails and hospitals?

a)

Institutional

b)

Corrosion-resistant

c)

Dry

d)

Intermediate

44.

Which sprinkler system takes longer to activate and designed to use in general occupancies?

a)

Standard

b)

Residential

c)

Nozzle

d)

Open

45.

Which sprinkler requires a special water-discharge pattern and used in water-spray fixed systems?

a)

Nozzle

b)

Special

c)

Standard

d)

Residential

46.

Which sprinkler system is specially painted by the manufacturer?

a)

Ornamental/

decorative

b)

Pilot line detector

c)

Standard

d)

Residential

47.

For sprinkler activation, thermocouples can be fusible links, glass bulbs, and _______.

a)

chemical pellets

b)

alarms

c)

detecting valves

d)

smoke detectors

48.

A specific application sprinkler is activated based on the maximum temperature and the anticipated _________.

a)

rate-of-heat release

b)

rise-of-rise release

c)

rate-of-temperature release

d)

rate-of-activation release

49.

Which detection and activation device sends an electronic impulse to the fire control panel and the sprinkler waterflow control valve when an abnormal situation is detected?

a)
  1. Electronic heat detector 

b)
  1. Manually activated system

c)
  1. Primary activation sensor 

d)
  1. Waterflow alarm

50.

Which detection devices sounds a warning when a sprinkler activates and water begins to flow in the facility?

a)

waterflow alarm

b)

electronic heat detector

c)

specific application sprinkler

d)

sprinkler activation

51.

Which detection device depends on human intervention to operate the sprinkler system?

a)

waterflow alarm

b)

manually activated system

c)

electronic heat detector

d)

specific application sprinkler

52.

Thermally sensitive devices such as fusible links keep most sprinklers closed and when heat from a fire affects these devices:

a)

sprinklers closest to the fire activate automatically

b)

sprinklers farthest from the fire activate automatically

c)

all sprinklers activate automatically

53.

Which thermocouple has its own sprinkler color coding?

a)

fusible link

b)

glass bulbs

c)

chemical pellets

d)

water valves

54.

Which sprinkler color is classified as ordinary with 135-170 degree temperature rating?

a)

Uncoded or Black

b)

White

c)

Blue

d)

Orange

55.

Which sprinkler color coding is intermediate with 175-225 degree temperature rating?

a)

Black

b)

White

c)

Red

d)

Blue

56.

Which sprinkler color coding is high with 250-300 degree temperature rating?

a)

White

b)

Blue

c)

Red

d)

Green

57.

Which sprinkler color coding is extra high with 325-375 degree temperature rating?

a)

White

b)

Blue

c)

Red

d)

Orange

58.

Which sprinkler color coding is very extra high with 400-475 degree temperature rating?

a)

Green

b)

Orange

c)

Red

d)

Blue

59.

Which sprinkler color coding is ultra high with 500-575 degree temperature rating?

a)

Orange

b)

Green

c)

Red

d)

Blue

60.

Which class of standpipe system is primarily for use by firefighters trained in handling large handlines?

a)
  1. Class I

b)
  1. Class IV

c)
  1. Class II

d)
  1. Class III

61.

Which class of standpipe system provides both 1½-inch and 2½-inch hose connections for use by both building occupants and firefighters?

a)

Class I

b)

Class II

c)

Class III

d)

Class IV

62.

Fire department personnel cannot depend on which class of standpipe system for fire control operations?

a)

Class I

b)

Class II

c)

Class III

d)

Class IV

63.

Which class of standpipe system is primarily designed for use by buildings occupants who are trained in its use or by the fire department personnel?

a)

Class I

b)

Class II

c)

Class III

d)

Class IV

64.

Which standpipe system has both hose connections for large handlines for fire department personnel and also connections for smaller handlines for use by trained building occupants?

a)
  1. Class I

b)
  1. Class II

c)
  1. Class III

d)
  1. Class IV

65.

Which of the following is a component of standpipe and hose fire suppression systems?

a)

operating valves

b)

pressure-regulating devices

c)

controllers

d)

pumps

66.

Which type of standpipe and hose system contains air or nitrogen under pressure and is permanently attached to a water supply?

a)

manual wet

b)

automatic wet

c)

automatic dry

d)

manual dry

67.

Which type of standpipe and hose system contains water in the system at all times and is attached to a water supply capable of supplying the system demand at all times?

a)
  1. Manual wet

b)
  1. Automatic dry

c)
  1. Manual dry

d)
  1. Automatic wet

68.

Which type of standpipe and hose system maintains water from a domestic fill connection to detect leaks in the system?

a)

Manual wet

b)

Manual dry

c)

Automatic dry

d)

Automatic dry

69.

Which type of standpipe and hose system is not connected to a domestic water supply and relies on the fire department to provide water through FDC?

a)
  1. Automatic wet

b)
  1. Manual dry

c)
  1. Manual wet

d)
  1. Automatic dry

70.

Which of the following is a component of standpipe and hose fire suppression systems?

a)

Dry-pipe sprinkler system

b)

Water-spray fixed system

c)

Water-mist system

d)

Pressure-regulating device

71.

Which of the following may reduce water supply requirements for standpipe systems?

a)

installed automatic sprinkler systems

b)

fire rated construction

c)

fire watch personnel

d)

safety security system

72.

The amount of water required for a standpipe system depends on the occupancy, height of the building, and the _________.

a)

total number of standpipes

b)

total number of sprinklers

c)

total number of occupants

d)

total number of exits

73.

The current NFPA 14 minimum requirement for residual pressure is ______ psi at the fire hose outlet.

a)

100

b)

80

c)

130

d)

144

74.

What should the inspector consult for the minimum requirements for stand-pipe occupancies?

a)

local fire code

b)

building code

c)

manufacturer recommendations

d)

safety data sheets

75.

What is the purpose of pressure regulating devices?

a)
  1. Regulate water volume for conservation

b)

Prevent pressures that make fire hose difficult or dangerous to handle

c)
  1. Maintain constant water temperature

d)
  1. Increase pressures to enhance water flow

76.

Which category of pressure-regulating devices is preferred for managing excessive pressure and is considered to be the most reliable method of pressure control?

a)

Pressure blocking devices

b)

Pressure control devices

c)

Pressure restricting devices

d)

Pressure reducing devices

77.

Which pressure regulating device is preferred for managing excessive pressure and have uses a spring mechanism?

a)

pressure-restricting device

b)

pressure-control device

c)

pressure-reducing device

d)

pressure-relieving device

78.

What is the primary purpose of the fire department connections (FDC) as part of automatic sprinkler systems?

a)

Boost the pressure of the water supply

b)

Filter impurities from the primary water supply

c)

Reduce the flow rate of the primary water supply

d)

Monitor the temperature of the water supply

79.

Large buildings having ____ or more zones require an FDC for each zone.

a)

2

b)

3

c)

1

d)

4

80.

What is the main function of a fire pump?

a)

Increase the pressure of the water that flows through it

b)

Regulates water temperature for sprinklers

c)

Provide circulation for pressure relieving devices

d)

Support the flow direction of water

81.

Which is the most common type of fire pump and it cannot be used to supply water from a static supply source?

a)

Horizontal Split-Case

b)

Vertical Split-Case

c)

Vertical Inline

d)

End Suction

82.

Which fire pump is useful for lifting water and the pump impellers are located within the water supply source?

a)

Vertical inline

b)

End suction

c)

Vertical turbine

d)

Horizontal split-case

83.

The advantages of a end suction pump are the ease of installation, simplified piping arrangement, and _______.

a)

compact space

b)

ability to lift water

c)

ease of maintenance

d)

reduced pipe strain

84.

Which method of driving a fire pump is more complex and requires batteries to start?

a)
  1. Steam turbine

b)
  1. Electric motor 

c)
  1. Diesel engine

d)
  1. Gasoline engine

85.

Which method of driving a fire pump is more expensive and requires maintenance such as testing weekly by running it for at least 30 minutes?

a)

Electric motor

b)

Gasoline engine

c)

Diesel engine

d)

Steam turbine

86.

Most fire pumps are designed to start when:

a)

manually activated

b)

are in pressure occurs in the fire suppression system

c)

the fire suppression system approaches failure

d)

a drop in pressure occurs in the fire suppression system

87.

Which is the most common method for driving a fire pump?

a)
  1. Steam turbine

b)
  1. Electric motor

c)
  1. Gasoline engine

d)
  1. Diesel engine

88.

Which of the following is an item that a diesel engine controller monitors?

a)

Low engine oil pressure

b)

Duty cycle

c)

Time/use ratio

d)

Low engine coolant temperature

89.

Which pump driver provides steam pressure to drive both horizontal and vertical split-case pumps directly?

a)

steam turbine

b)

diesel engine

c)

electric motor

d)

end suction

90.

Which of the following drivers is MOST likely to be used where a driver independent of the local electrical power supply is needed?

a)

Carnot engine

b)

Diesel engine

c)

Gasoline engine

d)

Electric motor

91.

The MOST likely reason that a sprinkler or standpipe system would need a fire pump is that the available water source:

a)

does not have an adequate pressure to meet fire suppression system

b)

has an adequate pressure to meet fire suppression system

92.

The pressure at which the pressure switch is set to start the fire pump must be _____ the pressure in the system.

a)

lower than

b)

higher than

c)

the same as

93.

Which type of centrifugal pump used as a stationary fire pump has advantages that include ease of installation as a replacement pump, the compact space required for the pump, and the ease of maintenance of the pump and driver?

a)

vertical inline

b)

end suction

c)

vertical turbine

d)

horizontal split case

94.

Which type of centrifugal pump used as a stationary fire pump is almost always driven by an electric motor that sits on top of the pump and has the advantage of being compact?

a)

Vertical inline

b)

Horizontal split case

c)

End suction

d)

Vertical split case

95.

Which type of centrifugal pump is used as a stationary fire pump is the most common type of fire pump found in stationary fire suppression systems?

a)

Horizontal split case

b)

Vertical split case

c)

Vertical incline

d)

End suction

96.

The current practice is to locate fire hose valves so that any part of the floor is within:

a)
  1. 160 ft. of standpipe hose connection

b)
  1. 30 ft. of the standpipe hose connection

c)
  1. 60 ft. of the standpipe hose connection

d)
  1. 130 ft. of the standpipe hose connection

97.

Standpipe hose connections can be located no more than ____ feet from floor level.

a)

12

b)

6

c)

30

d)

10

98.

The spacing for residential sprinklers is a maximum of ______ square feet per sprinkler.

a)

144

b)

12

c)

6

d)

30

99.

In a standpipe system, the actual hose connections can be located no more than:

a)

6 feet from floor level

b)

5 feet from floor level

c)

10 feet from floor level

d)

15 feet from floor levle

100.

What is the maximum distant for a residential sprinkler from a wall?

a)

6 ft

b)

12 ft

c)

144 ft

d)

30 ft

101.

Which type of sprinkler is designed to provide increased life safety in hotels, motels, and similar residential occupancies?

a)

Control mode specific application

b)

Early suppression fast response

c)

Residential

d)

Quick response extended coverage

102.

Which type of sprinkler is designed to suppress fires in high challenge areas such as warehouses?

a)

Control mode specific application

b)

Early suppression fast response

c)

Extended coverage

d)

Quick response early suppression

103.

The water supply requirements for residential sprinklers are

a)

the same as those for standard sprinklers

b)

greater than those for standard sprinkler systems

c)

less than those standard for sprinkler systems

d)

either less than or greater than those for standard sprinkler systems

104.

Which type of sprinkler is designed for fast response in residential occupancies where life safety in the room of origin is the primary concern?

a)

residential

b)

special

c)

standard spray

d)

nozzle

105.

Which of the following is the primary concern of residential sprinkler system installed according to NFPA13?

a)

property conservation

b)

initial cost

c)

environmental conservation

d)

life safety

106.

Residential system standards address life safety by working to prevent ______.

a)

flashover

b)

evacuation

c)

sprinkler system failure

d)

mechanical issues

107.

Which fixed fire suppression system discharges water over the area to be protected through an arrangement of pipes and nozzles and has components that are similar to an automatic sprinkler systems?

a)

water spray fixed system

b)

foam water system

c)

standpipe and hose system

d)

residential sprinkler system

108.

Water mist fire suppression systems are designed to be operated at ______ pressures than standard sprinkler system.

a)

higher

b)

lower

c)

the same

109.

Which fixed fire suppression system is considered a replacement for fixed fire suppression systems that uses halogenated hydrocarbon agents?

a)

water mist system

b)

foam water system

c)

automatic sprinkler system

d)

water spray fixed system

110.

Water-mist fire suppression systems that utilize air cylinders that have not been discharged should be emptied and tested:

a)

every seven years

b)

every twelve years

c)

every three years

d)

five years since their last tests

111.

Which fixed fire suppression system is designed to be operated at considerably higher pressures than standard sprinkler systems?

a)

water mist system

b)

water spray fixed system

c)

foam water system

d)

automatic sprinkler system

112.

Which fixed fire suppression system is commonly employed to protect Class B fire hazards and may also be used to suppress vapors created by flammable liquid spills?

a)

Foam water system

b)

Automatic sprinkler system

c)

Water spray fixed system

d)

Water mist system

113.

Who is responsible for servicing functions such as lubricating control valve stems and cleaning strainers on a water mist system?

a)

Owner/occupant or fire protection equipment company

b)

Fire marshal

c)

Fire inspector

d)

General contractor

114.

Standpipe systems should undergo hydrostatic testing:

a)

every 5 years

b)

every year

c)

every 2 years

d)

every 3 years

115.

What should an inspector consult for minimum requirements in standpipe-protected occupancies?

a)

Code used in the local jurisdictions

b)

International fire code

c)

Manufacturer recommendations

d)

Safety Data Sheets

116.

Which of the following designates the fire department connection (FDC)?

a)

A raised letter sign on a plate or fitting reading STANDPIPE

b)

A metal post that says OPEN / SHUT

c)

Two nozzles connected to a building

d)

An open drain designated by every exit

117.

How often should the proportioner in a foam water system be tested to verify that it is properly mixing the foam water solution and creating the specified concentration?

a)

Annually

b)

Semiannually

c)

Monthly

d)

Weekly

118.

Which type of sprinkler system is designed to prevent accidental water discharge by requiring two separate events before water is released?

a)

wet pipe system

b)

dry pipe system

c)

deluge sprinkler system

d)

preaction sprinkler system

119.

Which device in a fire protection system is responsible for automatically opening to allow water flow when a fire is detected?

a)

Check valve

b)

Sprinkler head

c)

Drain valve

d)

Alarm test valve

120.

Which of the following actions is performed on all water-based fire extinguishing systems when the installation is complete?

a)

Preacceptance testing

b)

Acceptance testing

c)

Routine inspection

d)

Plans review

121.

During which phase must the contractor submit any changes, alterations, or substitutions for review and approval as meeting or exceeding the original water-based fire suppression system design?

a)

Plans review

b)

Routine inspections

c)

Acceptance testing

d)

Preacceptance inspections

122.

Who is responsible for ensuring that the inspection, testing, and maintenance requirements for NFPA® 25 for water-based fire suppression systems are performed?

a)

Fire Chief

b)

Local building organization chair

c)

Owner/occupant

d)

Private inspector

123.

Select what the inspector will review during the plans review stage?

a)

Notice Pipe Hangers

b)

Occupancy, Hazard, and Construction Type

c)

Correct sprinkler design

d)

Fire and building code

e)

Permit documentation

124.

Inspectors should consult ______ for specific inspection and testing requirements before witnessing a test for water-based suppression systems.

a)

NFPA 25

b)

NFPA 13

c)

NFPA 80

d)

NFPA 72

125.

An inspector should first verify that all valves controlling water supplies to the sprinkler system are ______ at all times.

a)

open

b)

closed

126.

What should an inspector do after observing the pressure drop when the main drain is open?

a)

Take a picture

b)

Tap the gauge

c)

Close the 2-inch main drain slowly

d)

Close the 2-inch main drain quickly

127.

The inspector should inspect the fire suppression sprinkler cabinet located near the waterflow control valve to verify that the:

a)

sprinkler cabinet is locked and not accessible

b)

required number of replacement sprinklers is available

c)

required documentation and receipts are in the cabinet

d)

supplementary portable extinguishers are in the cabinet

128.

In fire suppression sprinkler systems designed for one- and two-family dwellings, the water supply source:

a)

is generally the same as the domestic water supply

b)

must be a separate source from the domestic water supply

c)

must have both a primary and secondary supply

d)

is generally a water tank on premises

129.

Residential sprinklers operate _________ standard sprinklers.

a)

slower than

b)

more quickly

c)

the same as

130.

________ is the distortion of a material caused by the repeated heating of a fusible link to near its operating temperature.

a)

Conductivity flow

b)

Cold flow

c)

Water flow

d)

Heat flow

131.

How often should building management personnel make a visual inspection of standpipe and hose fire suppression systems?

a)

At least once a week

b)

At least once every six months

c)

At least once a month

d)

At least once a day

132.

For standpipe and hose fire suppression systems, all water supply valves must be:

a)

unlocked in the open position

b)

locked in the closed position

c)

locked in the open position

d)

unlocked in the closed position.

133.

When inspecting the standard pressure proportioner, inspectors should verify:

a)

ball drip valves are open and operable

b)

waterflow valve is open

c)

the strainers are not obstructed

d)

the pressure vacuum is operational

134.

What should you look for while inspecting bladder tank proportioners?

a)

The presence of foam around the bladder

b)

Strainers are not obstructed

c)

Pressure vacuum is operational

d)

Ball drip valves are open

135.

What should you inspect for line proportioners?

a)

Strainers and pressure vacuum vent

b)

Waterflow valve and foam around bladder

c)

Ball drip valves are open

d)

Gauges are not obstructed

136.

Discharge outlets in dry systems should be _______.

a)

open

b)

closed

137.

Dry-pipe systems are hydrostatically tested every ______.

a)

5 years

b)

12 years

c)

year

d)

quarter

138.

The recommended inspection frequency for fire pump operation is _______.

a)

weekly

b)

monthly

c)

yearly

d)

quarterly

139.

Which NFPA standard contains specific inspection and testing requirements for water-based fire suppression systems?

a)

NFPA 70E

b)

NFPA 101

c)

NFPA 25

d)

NFPA 13

140.

Reviewing records and witnessing inspections and tests is MOST likely the responsibility of:

a)

piping engineer

b)

the engineer

c)

the installation contractor

d)

the inspector

141.

During which phase will an inspector compare the components of a system to those show on the plans or listed in the construction documents?

a)

Plans review

b)

Acceptance testing

c)

Preacceptance inspections

d)

Routine inspections

142.

Ensuring correct hanger spacing is essential when inspecting fire protection systems to:

a)

improve system efficiency during testing

b)

increase system pressure for better performance

c)

enhance aesthetic appearance of the system

d)

prevent damage to the system during operation

143.

As part of the maintenance requirements of NFPA25, standpipe and hose fire suppression systems must be flow and hydrostatic tested:

a)

every 3 years

b)

every 12 years

c)

every 5 years

d)

every 7 years

144.

The inspector should verify that the FDC is not blocked and is free of obstruction, the swivels rotate freely, and then:

a)

caps are in place

b)

caps have a nearby lockbox

c)

required number of replacement sprinklers is available

d)

caps do not use any type of keys

145.

When inspecting stationary fire pumps, which test is used to check for obstructions?

a)

Static pressure test

b)

Temperature test

c)

Flow test

d)

Air test

146.

While maintaining a minimum required residual pressure in the system, a water supply must be able to deliver the required volume of water to:

a)

the lowest point in the plumbing system

b)

the highest or most remote sprinkler in a structure

c)

the nearest fire hydrant to the structure

d)

the central water distribution point

147.

With a foam-water fire suppression sprinkler system, the valves:

a)

must be locked in the open position

b)

may be in the open or closed position

c)

are only during maintenance

d)

must always be in the closed position

148.

When inspecting a dry-pipe sprinkler system, the air pressure gauge should read approximately ___. (550)

a)

the same as the water pressure

b)

the same as recorded on the previous test

c)

three times atmospheric pressure

d)

half the gauges full-scale pressure

149.

Which sprinkler system has a delay of 30-60 seconds because air is being released from the pipe? (505)

a)

Wet-pipe

b)

Dry-pipe

c)

Deluge

d)

Multicycle

150.

Every sprinkler system should be equipped with a main control valve located between the ___.

(Pg. 509)

a)

riser and the branches

b)

source of water supply and the sprinkler system

c)

cross mains and the riser

d)

fire department connection and the rise

151.

Select all of the waterflow control valves:

a)

Outside stem and yoke (OS&Y)

b)

Post indicator valve (PIV)

c)

Wall post indicator valve (WPIV)

d)

Post indicator valve assembly (PIVA)

e)

Alarm-test valve

152.

Select all the operating valves:

a)

Alarm-test valve

b)

Check valve

c)

Drain valve

d)

Drip/drip ball valve

e)

Trim valve

153.

What is the name of the device for measuring temperature in which two electrical conductors of dissimilar metals such as copper and iron are joined at the point where heat is applied? (516)

a)

thermocouple

b)

waterflow alarm

c)

electronic heat detector

d)

pilot line detector

154.

NFPA 25 mandates ____ main drain tests. (548)

a)

quarterly

b)

monthly

c)

yearly

d)

weekly

155.

What is the first step to perform a main drain test?

a)

Observe and record the pressure

b)

Have representative open main drain

c)

Observe and record pressure drop

d)

Have representative close 2 in. drain slowly

156.

For dry-pipe systems, the system's air pressure is maintained at ____ psi. (550)

a)

15-20

b)

20-25

c)

30-35

d)

35-40

157.

When planning an alarm trip test on a dry-pipe system, the inspector should be aware that this procedure can take from ______ hours to complete. (550)

a)

2-4

b)

6-8

c)

1-2

d)

5

158.

There should be at least ___ inches of clearance between sprinklers and stored materials. (553)

a)

18

b)

16

c)

12

d)

20

159.

In water mist systems, what are the pressure ranges for low _____, intermediate _____, and high _____ pressure psi?

a)

175 or less, 175-500, 500 or more

b)

125 or less, 125-400, 400 or more

c)

175 or less, 175-1000, 1000 or more

d)

150 or less, 150-500, 500 or more