Search Header Logo
STANDPIPE AND HOSE SYSTEMS

STANDPIPE AND HOSE SYSTEMS

Assessment

Presentation

Specialty

Professional Development

Medium

Created by

Ray Denis

Used 22+ times

FREE Resource

1 Slide • 16 Questions

1

media

STANDPIPE SYSTEMS

2

Multiple Choice

All valves controlling connections to water supplies and

standpipes _____ be listed indicating valves

1

Shall

2

Must

3

Should

4

Shouldn't

3

Multiple Choice

A _____ standpipe system shall provide

2 1∕2 in. (65 mm) hose connections to supply water for use by

fire departments and those trained in handling heavy fire

streams

1

Class I

2

Class II

3

Class III

4

Class IV

4

Multiple Choice

Question image

The maximum pressure at any point in the system at any

time shall not exceed _____

1

175 PSI

2

200 PSI

3

350 PSI

4

450 PSI

5

Multiple Choice

Question image

For Class I and Class III systems, the minimum flow

rate for the hydraulically most remote standpipe shall be ______ through the two most remote

2 1∕2 in. outlets

1

250 GPM

2

500 GPM

3

750 GPM

4

100 GPM

6

Multiple Choice

Question image

The minimum flow rate for additional standpipes

shall be ______ per standpipe for buildings with

floor areas that do not exceed 80,000 ft2 per floor

1

150 GPM

2

200 GPM

3

250 GPM

4

500 GPM

7

Multiple Choice

Question image

Standpipes shall be at least ___ in size.

1

2.5in

2

4in

3

6in

4

8in

8

Multiple Choice

Question image

A _______ standpipe system shall provide either 1 1∕2 in.

(40 mm) hose stations to supply water for use by trained

personnel or a hose connection for the fire department during

initial response

1

Class I

2

Class II

3

Class III

4

Class IV

9

Multiple Choice

The horizontal portion of the

system piping that delivers the water supply for two or more

hose connections, and for sprinklers on combined systems,

on a single level.

1

Vertical Standpipe

2

Wet Standpipe

3

Combined Standpipe

4

Horizontal Standpipe

10

Multiple Choice

A standpipe system

containing water at all times that is attached to a water

supply capable of supplying the system demand at all times

and that requires no action other than opening a hose valve

to provide water at hose connections

1

Dry Standpipe

2

Manual Wet Standpipe

3

Automatic Wet Standpipe

4

Semiautomatic Dry Standpipe

11

Multiple Choice

Question image

A standpipe system that supplies

both hose connections and automatic sprinklers

1

Class II Standpipe

2

Combined Standpipe System

3

Wet Standpipe

4

Class III

12

Multiple Choice

Question image

A standpipe system with no permanently attached water supply that relies exclusively on the fire department connection to supply the

system demand

1

Class II Standpipe

2

Manual Wet Standpipe

3

Manual Dry Standpipe

4

Semiautomatic Dry Standpipe

13

Multiple Choice

Question image

A system that provides 1 1∕2 in.

hose stations to supply water for use by trained

personnel and 2 1∕2 in. hose connections to supply a

larger volume of water for use by fire departments

1

Class I Standpipe

2

Class II Standpipe

3

Class III Standpipe

4

Class IV Standpipe

14

Multiple Choice

A high-rise building is a building where the floor of an

occupiable story is greater than ____ above the lowest

level of fire department vehicle access

1

50ft

2

75ft

3

100ft

4

150ft

15

Multiple Choice

Question image

A standpipe system containing water at all times that relies exclusively on the fire department connection to supply the system demand

1

Manual Wet Standpipe

2

Manual Dry Standpipe

3

Automatic Wet Standpipe

4

Semi-Automatic Dry Standpipe

16

Multiple Choice

Question image

A ____ _____ test shall be performed at the low point drain

for each standpipe or the main drain test connection where

the supply main enters the building (when provided)

1

water flow

2

main drain

3

water discharge

4

tamper signal

17

Multiple Choice

Question image

Hydrostatic tests of not less than _______

pressure for 2 hours, or at 50 psi in excess of the

maximum pressure, where maximum pressure is in excess

of 150 psi, shall be conducted every 5 years on

manual standpipe systems and semi-automatic dry

standpipe systems, including piping in the fire department

connection

1

100 PSI

2

150 PSI

3

200 PSI

4

250 PSI

media

STANDPIPE SYSTEMS

Show answer

Auto Play

Slide 1 / 17

SLIDE