wayground logo

Free Printable Worksheets

NEW

Font size

S
M
L
XL
Worksheets

Review unit 6 part-3

Total questions: 64

Worksheet time: 16hrs 0mins

Name
Class
Date
1.

In a snap action overload relay, what happens to the bimetallic strip when heated?

a)

Form into a curved disc

b)

Form into a plate disc

c)

Form into a spiral disc

d)

Form into a straight disc

2.

What happens to a bimetallic temperature switch with snap action if it will be used to make or break large currents needing fast overload response?

a)

The respond quickly

b)

The strip is bonded together

c)

They arc and burn

d)

They are fast to react

3.

Refer to figure below. Identify the operating mechanism of magnetic starter?

a)

Clapper type

b)

Horizontal action type

c)

Bell crank type.

d)

Mechanical Linkage

4.

Refer to figure below. Identify the operating mechanism of magnetic starter?

a)

Clapper type

b)

Horizontal action type

c)

Bell crank type

d)

Mechanical Linkage

5.

Refer to figure below. Identify the operating mechanism of magnetic starter?

a)

Clapper type

b)

Horizontal action type

c)

Bell crank type.

d)

Mechanical Linkage

6.

Using the table , what will be the NEMA starter size for a single phase motor with 15 HP and 240 V?

a)

2

b)

3

c)

4

d)

5

7.

Using the table in Figure 33, what will be the NEMA starter size for a single phase motor with 7 1/2 HP and 208 V?

a)

2

b)

3

c)

4

d)

5

8.

Using the table in Figure 33, what will be the NEMA starter size for a 3 phase motor, 200 HP and 480 V?

a)

2

b)

3

c)

4

d)

5

9.

Using the table in Figure 33, what will be the NEMA starter size for a 3 phase motor, 50 HP and 240 V?

a)

2

b)

3

c)

4

d)

5

10.

Refer the schematic diagram below .what is the eliminate used to keep the start button is holding circuit?

a)

magnetic starter coil

b)

Overload contacts

c)

Auxiliary contact

d)

Latching relay

11.

Refer the schematic diagram below .What will happen if button Start is pressed and released?

a)

MC coil energized ,MC1 contact close and after released MC coil de-energized

b)

MC coil energized ,OL contact open and after released MC coil de-energized

c)

MC coil energized and the circuit remains energized after released

d)

MC coil energized and de-energized

12.

A motor is controlled by a magnetic starter but stops because of an overload, what must be done to operate the motor again?

a)

Keep pressing the start button until the motor runs again

b)

Press the stop and start button repeatedly

c)

Press the start button immediately after the motor stop

d)

Remove the cause of overload and reset the overload contactor

13.

What type of control circuit shown in figure below?

a)

Two-wire control circuit

b)

three-wire control circuit

c)

four-wire control circuit

d)

double -wire control circuit

14.

What type of control circuit, which provides a low voltage release and low voltage protection?

a)

Two-wire control circuit

b)

three-wire control circuit

c)

four-wire control circuit

d)

double -wire control circuit

15.

What type of control circuit which provides a low voltage release but not low voltage protection?

a)

Two-wire control circuit

b)

three-wire control circuit

c)

four-wire control circuit

d)

double -wire control circuit

16.

What does a two wire control circuit provides?

a)

High voltage release and high voltage protection

b)

Low voltage release but not low voltage protection

c)

Low voltage release and low voltage protection

d)

High voltage release but not low voltage protection

17.

What type of control circuit, the control circuit looses power and magnetic starter will de-energized low voltage release?

a)

Two-wire control circuit

b)

three-wire control circuit

c)

four-wire control circuit

d)

double -wire control circuit

18.

What type of control circuit, the coil will dropout and cannot be reset until the voltage returns and stat button is depressed?

a)

Two-wire control circuit

b)

three-wire control circuit

c)

four-wire control circuit

d)

double -wire control circuit

19.

What type of control circuit shown in figure below?

a)

Two-wire control circuit

b)

three-wire control circuit

c)

four-wire control circuit

d)

double -wire control circuit

20.

The start push button is pushed and released, what will happen if the control circuit loses power and restores after a while?

a)

The motor will energize and re-energize

b)

The overload contact will open

c)

The motor will de-energize and re-energize

d)

The motor will de-energize and remain de-energized

21.

Refer to figure below. What will happen if PB2 is pressed and released?

a)

M1 coil will energize and remains energize

b)

M1 coil will energize and then de-energize

c)

M1 coil will de-energize and then energize

d)

M1 coil will energize

22.

What type the circuit that purpose of accomplishing small movements of the driven machine?

a)

Reversing circuit

b)

Jogging circuit

c)

Latching circuit

d)

Interlocking circuit

23.

What type the circuit that used to move machinery small distances at a time example overhead travelling crane?

a)

Reversing circuit

b)

Jogging circuit

c)

Latching circuit

d)

Interlocking circuit

24.

What is the function of PB2 in the circuit?

a)

Serves as the holding circuit

b)

To increase the speed if the driven motors

c)

To keep the equipment running after it is pressed and released

d)

To make small movements on the driven machine

25.

What types of interlocks used in the forward/reversing magnetic starter?

a)

Mechanical

b)

Electrical

c)

Mechanical and electrical

d)

Jogging starter

26.

Refer the figure below. What part of the circuit form electrical interlocks?

a)

F2 & R2

b)

R1 & F1

c)

F2 & R1

d)

R2 &F1

27.

Where is the mechanical interlock located in forward/ reverse motor control circuit that will prevent short circuit Refer the figure above?

a)

At coil F and coil R

b)

At push button PB2 and PB3

c)

At contact F2 and R2

d)

At contact F1 and R1

28.

Refer the figure . What part of the circuit Prevent the motor to run revers when the motor run forward?

a)

F2

b)

F1

c)

R2

d)

R1

29.

Refer the figure . What part of the circuit Prevent the motor to run forward when the motor run reversed?

a)

F2

b)

F1

c)

R2

d)

R1

30.

Refer the figure below. What will happen if Pressed PB2 (Froward)?

a)

F coil will energize , F2 contact closed and F1 contact open the motor run forward

b)

R coil will energize , R2 contact closed and R1 contact open the motor run Reverse

c)

F coil will energize , R2 contact closed and R1 contact open the motor run forward

d)

R coil will de-energize , R2 contact closed and R1 contact open the motor run forward

31.

Refer the figure . What will happen if Pressed PB3 (Reverse)?

a)

F coil will energize , F2 contact closed and F1 contact open the motor run forward

b)

R coil will energize , R2 contact closed and R1 contact open the motor run Reverse

c)

F coil will energize , R2 contact closed and R1 contact open the motor run forward

d)

R coil will de-energize , R2 contact closed and R1 contact open the motor run forward

32.

Refer the figure above. What keeps the forward contactor coil energize after PB2 pressed and released?

a)

F2

b)

F1

c)

R2

d)

R1

33.

Refer the figure . What keeps the Reverse contactor coil energize after PB3 pressed and released?

a)

F2

b)

F1

c)

R2

d)

R1

34.

Refer the figure. Where is the mechanical interlocks located?

a)

F2 & R2 auxiliary contacts

b)

R1 & F1 auxiliary contacts

c)

At F & R contactors coil

d)

R2 &F1 auxiliary contacts

35.

What is the function of the mechanical interlock?

a)

Allows coils F & R to energizing at the same time

b)

Allows de-energizing coils F & R at the same time

c)

Prevents Coils F & R from energizing at the same time

d)

Acts as a holding circuit for Coils F & R

36.

All approved enclosures, boxes and fittings used in hazardous area are called________

a)

Weather proof

b)

Totally Enclosures

c)

Explosive proof

d)

Fire proof

37.

What is the type of conduits used in hazardous locations?

a)

Conduit explosion proof

b)

Flexible meatal conduit

c)

Rigid metal conduit

d)

Electrical meatal tube

38.

Refer the Figure, what is the Parts A, B and C?

a)

A-Seal B- Flexible Fitting C- Flexible Connection

b)

A-Coupling B- Flexible conduit C- Rigid Fittings

c)

A-Seal B-Rigid conduit C- Flexible Fittings

d)

A-Connector B- Flexible conduit C- Flexible Fittings

39.

Refer the Figure . In hazardous area, conduit must be threaded with a standard conduit cutting of _________________inch taper per foot.

a)

½

b)

¾

c)

1

d)

11/2

40.

What must be used to prevent the passage of gas, vapor or flames from one part of the motor control to another through the conduit

a)

Nipple

b)

Threaded reducer

c)

Seals

d)

Explosion proof fittings

41.

In hazardous locations, the conductor must enter the motor through fittings what type of the fittings?

a)

explosion proof rigid fitting

b)

explosion proof Flexible fittings

c)

weather proof rigid fitting

d)

weather proof Flexible fittings

42.

The NEC specified that all boxes and fittings threaded connections must be joined with____________________________

a)

At more five threads engaged

b)

At least five threads engaged

c)

At more six threads engaged

d)

At least seven threads engaged

43.

In hazardous area, what will happen to the lighting fixture if it is replaced by incorrect bulb with higher wattage?

a)

will not operate

b)

break

c)

overheats

d)

nothing will happen

44.

What is the least number of threads must be engaged when making threaded connection of all boxes and fittings?

a)

Five

b)

Six

c)

Three

d)

Four

45.

Why are seals installed on conduit in Hazardous area?

a)

To support conduit in place where it is installed

b)

To allow flammable gas to move from one location to another

c)

To make motor terminations in Hazardous areas

d)

To prevent the passage of flame from one part to another

46.

It is approach or process that you must perform when troubleshooting and finding faults quickly.

a)

disassembly

b)

logical

c)

visual

d)

actual

47.

The power circuit severe faults such as short or ground trip the circuit breaker or blown the fuse, another faults are most likely have tripped the

a)

Relay Control

b)

Timer relay

c)

Overload

d)

magnetic contactor

48.

What is the most probable cause for a circuit breaker to trip?

a)

open circuit

b)

loose connection

c)

Short circuit or ground fault

d)

low voltage

49.

Having a correct voltage in the power supply, where the fault does lies if the magnetic contactor does not energize.

a)

power circuit

b)

control circuit

c)

motor

d)

transformer

50.

If the overload contact does not tripped and the motor control contactor does not energize the fault is probably somewhere in

a)

power circuit

b)

control circuit

c)

motor

d)

transformer

51.

When the control circuit fuse is open, you must check for

a)

loose connection

b)

short circuit

c)

open circuit

d)

power supply

52.

Where does the fault lies if the correct voltage reaches the motor terminal as you press the start button on the control panel?

a)

magnetic contactor main contacts

b)

motor

c)

overload device

d)

magnetic contactor coil

53.

What will happen if there is an overheating of motor stator?

a)

overload device trips

b)

circuit breaker trips

c)

control fuse blows

d)

main disconnect switch opens

54.

What is the symptoms if the motor excessive vibrations?

a)

Fan broken

b)

Shaft bent

c)

Bearing dry

d)

Loose foundation

55.

What is the symptom if the motor not start when energized?

a)

Fan broken

b)

Circuit breaker trips

c)

Bearing dry

d)

Loose foundation

56.

What is the symptom if the motor may be overheating?

a)

Shaft bent

b)

open circuit

c)

Loose foundation

d)

Poor ventilation

57.

What is the Cause the motor to get hotter?

a)

Shaft bent

b)

open circuit

c)

Loose foundation

d)

Lack of lubrication

58.

Lack of lubrication and poor motor ventilation can cause what?

a)

Motor will run quietly

b)

Motor performance will improve

c)

Motor will rotate at faster speed

d)

Motor will overheat

59.

What is the Cause the motor higher temperature and increase frication’s?

a)

Low voltage

b)

Bearing dry

c)

Loose foundation

d)

Shaft bent

60.

What is the possible causing poor intermittent connection or open circuit and motor not operate?

a)

open circuit

b)

loose connection

c)

short circuit

d)

low voltage

61.

What could be the probable cause when the overload device trips?

a)

Fuse blown

b)

loose termination

c)

excessive current

d)

open circuit

62.

What test or fault finding technique are you going to use to check the main contacts of an isolated magnetic contactor if it is working correctly?

a)

short circuit test

b)

current test

c)

continuity test

d)

voltage test

63.

Where will be the fault in a three-wire control circuit if you press the start button the motor runs but as you depressed it the motor stops?

a)

overload device

b)

magnetic contactor holding contact

c)

magnetic contactor coil

d)

start push button contact

64.

Motors mechanical faults includes

a)

stator windings, leads faults

b)

open, shorted terminals

c)

rotor, shaft, bearing, fan failures

d)

grounded motor winding