sEEdlak ESAID Practice Quiz

Total questions: 100

Worksheet time: 41mins

Name
Class
Date
1.

considered as being  concrete, bricks, or tile walls

(a)  

2.

An appliance which is fastened or otherwise secured at specific location.

(a)  

3.

The best to fight flammable gases/ liquids

a)

Class A Fire Extinguisher

b)

Class B Fire Extinguisher

c)

Class C Fire Extinguisher

d)

Class D Fire Extinguisher

4.

a system which will automatically furnish lighting and/or power to specified areas and/or equipment when there is a failure of the normal supply

(a)  

5.

Which of the following does not belong to the Coverage or Scope of PEC

a)

Airfields

b)

Carnivals

c)

Recreational Vehicles

d)

Electric Generating Plants

e)

None of the Above

6.

Characterized by the use of the terms shall be permitted or shall not be required

(a)  

7.

Characterized by the use of the terms shall or shall not

(a)  

8.

Give the three kinds of electrical installation NOT covered by the PEC. Use the format: answer 1, answer 2, answer 3

(a)  

9.

They are informational only and are not enforceable as requirement of the Code.

(a)  

10.

Check all the different Referral Codes of the PEC

a)

National Building Code

b)

Fire Code of the Philippines

c)

Structural Code

d)

Philippine Grid Code

e)

National Electrical Code

11.

The electrical plan ,if required, shall be submitted in _ copies.

a)

2

b)

3

c)

5

d)

6

12.

The duly registered electrical contractor shall have a PCAB License for _ Amp Main and above

a)

100

b)

225

c)

200

d)

175

13.

Check all the different sheet sizes of standard electrical plan

a)

760 mm by 1000 mm

b)

600 mm by 900 mm

c)

30" by 40"

d)

24" by 36 "

14.

How high is the title block should be from the bottom of the sheet?

(a)  

15.

Which of the following does not belong to the Guidelines for Approval?

a)

Wire bending and connection space

b)

Arcing effects

c)

Specific Use

d)

Electrical Insulation

16.

A certain residential house has a llighting load of 1.760 kVA and a n appliance load of 10 A at 220 V, single phase, two wires, 60Hz. The total current in amperes if all loads are used at the same time

(a)  

17.

  A circuit when one electrical circuit controls another electrical circuit through a relay.

(a)  

18.

This may be connected ahead of the main service

(a)  

19.

Listed Equipment must be installed or used in accordance with

a)

the blue print

b)

the electrician

c)

any instructions included in listing or labeling

d)

any instructions provided by the manufacturer or equipment

20.

Which of the following shall be shown for the electrical drawing of a single family dwelling? Check all that apply

a)

floor plan

b)

location plan

c)

one line diagram

d)

computation of illumination

21.

intermittent operation in which the load conditions are regularly  recurrent.

(a)  

22.

surrounded by a case, housing, fence, or wall(s) that prevents persons from accidentally contacting energized parts.

(a)  

23.

the case or housing of apparatus, or the fence or walls surrounding an installation to prevent personnel from accidentally contacting energized parts or to protect the equipment form physical damage.

(a)  

24.

action requiring personal intervention for its control.

(a)  

25.

a complete lighting unit consisting of a lamp or lamps together  with the parts designated to distribute the light, to position and protect the lamps and ballast (where applicable), and to connect the lamps to the power supply.

(a)  

26.

a compartment or chamber to which one or more air ducts are connected and that forms part of the air distribution system.

(a)  

27.

1.    When there is no terminal box, meter, or other enclosure, the point of connection is considered to be the point of entrance of the _______ into the building.

a)

ungrounded conductors

b)

service conductors

c)

neutral conductors

d)

service drop

28.

  the point of connection between the facilities of the serving utility and the premises wiring.

(a)  

29.

constructed so that moisture will not enter the enclosure under specified test conditions.

(a)  

30.

1.    In cases where service has been cut off for more than ____ year, a new certificate of final electrical inspection shall be required before reconnection.

a)

one

b)

one and a half

c)

two

d)

three

31.

1.    The conductors and equipment &/ or devices required or permitted by the Code shall be acceptable, only if

a)

listed

b)

identified

c)

approved

d)

labelled

32.

the minimum headroom of working spaces about service equipment, switchboards, panel boards or motor control centers.

a)

1500 mm

b)

1900 mm

c)

2000 mm

d)

2200 mm

33.

1.    The Code is not intended as a design specification nor an instruction manual for (a)   persons.

34.

   It is the intent of PEC that factory-installed internal wiring or the construction of equipment need not to be inspected at the time of installation of the equipment except

a)

To test for continuity

b)

to detect alteration

c)

to test for durability

d)

all of these

35.

The Philippine Electrical Code covers electric conductors, optical fiber cable, and equipment installed within or on, to or from premises requiring electrical installation except; (Check all that apply)

a)

aircraft

b)

motor vehicles

c)

railway rolling stock

d)

watercraft vehicles

36.

The current amperes that a conductor can carry continuously under the conditions of use without its temperature rating.

(a)  

37.

  an enclosure that is designed for either surface mounting or flush mounting and is provided with a frame, mat, or trim in which a swinging door or doors are or can be hung.

(a)  

38.

all circuit conductors between the service equipment, the source of separately derived system, or other power supply source, and the final branch-circuit overcurrent device.

(a)  

39.

the highest current at rated voltage that a device is intended to interrupt under standard test conditions

(a)  

40.

For the dwelling unit having a  floor area of not more than 50 square meters with a total load not exceeding 3,680 VA, a drawing sheet of size

a)

600 mm by 900 mm

b)

760 mm by 1000 mm

c)

500 mm by 760 mm

d)

297 mm by 420 mm

41.

   In the schedule of loads for motor circuits, which of the following is not included?

a)

Type of motor

b)

Motor's manufacturer

c)

Motor as numbered or identified in the power layout

d)

Number of phases

42.

1.    A wiring method included in the Code is recognized as being a(n) ______ wiring method.

a)

expensive

b)

efficient

c)

suitable

d)

cost-effective

43.

Connection of conductors to terminal parts shall ensure a thoroughly good connection without damaging the conductors and shall be made by means of

a)

splices

b)

pressure connectors

c)

solder lugs

d)

all of these

44.

Sufficient access and ____ shall be provided and maintained about all electrical equipment to permit ready and safe operation and maintenance of such equipment.

a)

ventilation

b)

working space

c)

cleanliness

d)

circulation

45.

the largest stranded conductor permitted to be connected to terminals by means of upturned lugs is ___ mm2

a)

8

b)

4

c)

5.5

d)

6.5

46.

When normally-enclosed the parts are exposed for inspection or servicing, the working space, if in a passageway or general open space shall be suitably______

a)

accessible

b)

open

c)

guarded

d)

enclosed

47.

1.    Electrical equipment provided with ventilating openings shall be installed so that walls or other obstructions do not prevent the ____ of air through the equipment.

a)

movement

b)

release

c)

free of circulation

d)

none of these

48.

The circuit conductors between the final overcurrent device protecting the circuit and the outlet

(a)  

49.

A type of branch circuit that supplies one utilization equipment

a)

General Purpose Branch Circuit

b)

Appliance Branch Circuit

c)

Individual Branch Circuit

d)

Multi wire Branch Circuit

50.

A point at which energy is divided among feeders or branch circuits or combination of both, and where over current devices are usually loaded

(a)  

51.

classified in accordance with the maximum permitted ampere rating or setting of the branch circuit

(a)  

52.

On what branch circuit does one cord and plug connected utilization equipment with maximum rating of 80% of branch circuit ampere rating belong? Check all that apply

a)

15 & 20 A Branch Circuit

b)

30 A Branch Circuit

c)

40 & 50 A Branch Circuit

d)

Above 50 A Branch Circuit

53.

a point in the wiring at which current is taken to supply utilization equipment

(a)  

54.

A contact device installed at the outlet for the connection of an attachment plug

(a)  

55.

refers to the circuit conductor between the service equipment and the branch circuit over current device.

(a)  

56.

originate a distribution center other than the service equipment or generator switchboard and supply one or more other distribution panel boards, branch circuit panel boards, or branch circuit

(a)  

57.

TRUE OR FALSE. The Feeder Interrupt Rating shall not be lower than required to supply the computed load and before the application of any adjustment or correction factors, shall have an allowable ampacity not less than the non-continuous load plus 125% of the continuous load

a)

TRUE

b)

FALSE

58.

a string of outdoor lights suspended between two points

(a)  

59.

A 15 A or 20 A branch circuit shall be permitted to supply lighting units and other utilization devices. The rating of any one cord- and plug connected appliances shall not exceed a certain percentage of the branch circuit rating. What is the percentage?

a)

80%

b)

70%

c)

90%

d)

50%

60.

Branch circuit within 75 mm of ballast in a ballast compartment shall have a rated insulation temperature NOT less than what value?

a)

90 deg C

b)

60 deg C

c)

120 deg C

d)

75 deg C

61.

Where receptacles are connected to a 30 A branch circuit, the maximum allowable cord- and plug connected load shall NOT be more than ____amperes,

a)

30

b)

16

c)

24

d)

20

62.

The minimum feeder load allows for show-window lighting expressed in volt-amperes per linear foot shall be

a)

300

b)

200

c)

150

d)

225

63.

Communication wires and cable shall be separated by at least what distance from service drops of electric light and power conductors that are NOT installed in raceway or in a cable?

a)

150 mm

b)

175 mm

c)

250 mm

d)

300 mm

64.

Which of the following is a standard classification for a branch circuit supplying several loads? Check all that apply.

a)

20 A

b)

25 A

c)

30 A

d)

50 A

65.

A  3-phase, 4-wire , wye connected, power system used to supply power to _______ loads may necessitate that the power system design allow for the possibility of high harmonic neutral currents.

a)

continuous

b)

linear

c)

nonlinear

d)

non-continuous

66.

A multiwire branch circuit shall supply on _____.

a)

only one utilization equipment

b)

ungrounded conductors that are opened simultaneously

c)

line to neutral loads

d)

all of these

67.

Voltage shall not exceed 600 volts between conductors on branch circuits supplying only ballasts for electric-discharge lamps in tunnels with a height of not less than ____mm

a)

3700

b)

4600

c)

5500

d)

6500

68.

The feeder conductor ampacity shall not be less than that of the service -entrance conductors where the feeder conductors carry the total load supplied by service- entrance conductors with an ampacity of ______or less.

a)

100 A

b)

60 A

c)

55 A

d)

30 A

69.

Total voltage drop on both feeders and branch circuit to the farthest outlet to provide reasonable efficiency of operation shall not exceed

a)

5%

b)

3%

c)

10%

d)

7%

70.

Open conductors on insulators shall be covered when they are within _____mm of a building.

a)

1,000

b)

2,000

c)

3,000

d)

4,000

71.

Running open wiring on insulators, MI or MC cable, messenger- supported wiring, conductos in raceway, and other approved means on the outdoor building surfaces is permitted for circuits operating at a maximum of _____ volts nominal.

a)

600

b)

750

c)

1000

d)

3000

72.

Power conductors on poles, below communications conductors shall maintain a spacing distance of _____ mm

a)

600

b)

650

c)

700

d)

750

73.

The vertical clearance above the roof level shall be m,aintained for a distance not less than ____ mm in all directions from the edge of the roof.

a)

600

b)

700

c)

800

d)

900

74.

In general, a building or other structure served shall be supplies by only ____ service (s).

a)

1

b)

more than 1

c)

3

d)

4

75.

Service conductors shall have vertical clearance of not less than_____ mm above the roof surface

a)

2200

b)

2400

c)

2600

d)

2800

76.

(a)   mm² is the minimum size of aluminum or copper clad aluminum conductors, used as service entrance conductors.

77.

. Bored holes in wood members for cable or raceway-type wiring shall be bored so that the edge of the holes is not less than ___ mm from the nearest edge.

a)

30

b)

45

c)

40

d)

35

78.

the conductors and equipment delivering energy from the serving utility to the wiring system of the premises served

(a)  

79.

a structure that stands alone or that is cut off adjoining structures by fire walls with all openings therein provided by approved fire doors

(a)  

80.

The following are exceptions under special conditions except. Check all that apply

a)

Fire Pumps

b)

Parallel Power Standby Systems

c)

Emergency systems

d)

Optional Standby Systems

e)

Series Power Standby Systems

81.

Service conductors made up in the form of a cable

(a)  

82.

The conductors from the service point to the service disconnecting means

(a)  

83.

the overhead service conductors from the last pole or other aerial support to and including splices, if any, connecting to the service-entrance conductors at the building or other structure.

(a)  

84.

The underground service conductors between the street main, including any risers at a pole or other structure or from transformers, and the first point of connection to the service entrance conductors in a terminal box or meter or other enclosure, inside or outside the building wall.

(a)  

85.

the point of connection between the facilities of the serving utility and premises wiring

(a)  

86.

The raceway that encloses the service entrance conductors

(a)  

87.

The necessary equipment usually consisting of circuit breakers or switches, and fuses, and their accessories, connected to the load end of service conductors to a building or other structures, or an otherwise designated area, and intended to constitute the main control and cutoff of the supply.

(a)  

88.

the service conductors between the terminals of the service equipment and a point usyally outside the building, clear of building walls, where joined by tap or splice to the service drop.

a)

Service Drop

b)

Service- Entrance Conductors

c)

Service Equipment

d)

Service Raceway

89.

Service drop conductors not in excess of 600 volts shall have a minimum clearance of ___ feet over over residential property and driveways and those commercial areas not subject to truck traffic.

a)

10

b)

12

c)

14

d)

16

90.

When re-routing conduit, it may be necessary to increase the wire size, if the distance is greater in order to

a)

account current drop

b)

allow for possible resistance drop

c)

compensate for voltage drop

d)

account for ampacity drop

91.

The minimum size service lateral to a branch circuit limited load is ___ copper

a)

#8

b)

#10

c)

#12

d)

#14

92.

Of the two to six service disconnecting means in a panel, only a disconnect used for a___________  is permitted  to be remote from the other disconnects.

a)

control wiring

b)

elevator panels

c)

a water pump intended for fire protection

d)

supply to across the line starting

93.

Give the minimum vertical clearance from finished grade of a service drop conductor installed between buildings on residential properties and driveways.

a)

1500 mm

b)

3000 mm

c)

3500 mm

d)

4000 mm

94.

When the voltage between service conductors does not exceed 300 V and the roof has  a slope of not less than 100 mm, the clearance can be reduced to

a)

900 mm

b)

1000 mm

c)

1200 mm

d)

1500 mm

95.

The maximum clearance for service drops over buildings

a)

7 feet

b)

8 feet

c)

9 feet

d)

10 feet

96.

. Service conductors passing over roofs must have a clearance over the roof which they pass of

a)

2000 mm

b)

2200 mm

c)

2400 mm

d)

2600 mm

97.

refers to the circuit conductor between the service equipment and the branch circuit overcurrent device.

(a)  

98.

Service using copper conductors shall have sufficient capacity and shall NOT be smaller than ___ sq mm.

a)

6.0

b)

8.0

c)

10.0

d)

12.0

99.

In case of conflict about the Interpretation of PEC, which body is authorized to render the final decision?

(a)  

100.

Expand the acronym CAPS. Type in ( C___, A_______, P_____, S____)

(a)