wayground logo

Free Printable Worksheets

Font size

S
M
L
XL
Worksheets

Solenoid Valves and Sensing Switches Quiz

Total questions: 102

Worksheet time: 56mins

Name
Class
Date
1.

A solenoid valve is an electro-mechanical device that, when energized or de-energized, performs which function?

a)

Measures fluid pressure

b)

Shuts off or allows fluid flow

c)

Increases fluid temperature

d)

Compresses instrument air

2.

When an electric current energizes the coil of a solenoid, what is produced?

a)

A magnetic field

b)

High-pressure air

c)

A chemical reaction

d)

A loud alarm

3.

In a de-energized solenoid valve as shown in Figure 2A, what component pushes the valve stem down to keep the valve closed?

a)

The core (armature)

b)

The spring

c)

The electric leads

d)

The inlet port

4.

According to the P&ID in Figure 3, what does 'AO/AFC' stand for?

a)

Actuator Open / Actuator Fails Closed

b)

Air Open / Air Fails Close

c)

Automatic Open / Automatic Fails Close

d)

Always Open / Always Fails Close

5.

In the emergency trip circuit (Figure 3), what happens to the solenoid valve ZV-010 when the temperature switch TS-010 trips at \bm{100^{\circ}C}?

a)

It energizes

b)

It de-energizes

c)

It throttles to 50%

d)

It sends a signal to the controller

6.

When the 3-way solenoid valve ZV-010 de-energizes, it closes the air supply (P) and opens which port to vent the actuator?

a)

Port A (Actuator)

b)

Port P (Pressure)

c)

Port E (Exhaust)

d)

Port D (Drain)

7.

In the circuit shown in Figure 5, what component is energized when the Level Switch LS1 is closed?

a)

The 110 Vdc power supply

b)

Relay R1

c)

Solenoid Valve ZV-1

d)

The 12 Vdc battery

8.

In Figure 5, what action directly causes the solenoid valve ZV-1 to energize?

a)

The level switch LS-1 opening

b)

The 12 Vdc supply turning on

c)

The relay contacts R1-1 closing

d)

The pressure exhausting from port E

9.

What is the condition of the solenoid valve coil during the normal operation of the ESD system shown in Figure 3?

a)

De-energized

b)

Normally closed

c)

Energized

d)

Bypassed

10.

Relays and solenoids are often used together in which type of systems?

a)

Process control loops

b)

Alarm and ESD systems

c)

Power distribution units

d)

Data acquisition systems

11.

A micro-switch is a single-pole, double-throw switch, which is abbreviated as what?

a)

SPST

b)

DPDT

c)

SPDT

d)

DPST

12.

In the dual-switch circuit of Figure 8, at what pressure will the 'H Alarm' activate?

a)

24 psi

b)

100 psi

c)

110 psi

d)

120 psi

13.

In Figure 8, when pressure reaches 110 psi, switch S2 activates, de-energizing the solenoid valve and turning on what?

a)

The 'Normal' green light

b)

The 'H Alarm'

c)

The 'HH Alarm'

d)

The booster pump

14.

Mercury switches are motion-based switches consisting of a sealed glass tube, contacts, and a small amount of what?

a)

Nitrogen

b)

Argon

c)

Liquid mercury

d)

Distilled water

15.

What is a known disadvantage of mercury switches?

a)

They are not very accurate

b)

They cannot handle high voltage

c)

They consume a lot of power

d)

Excessive vibrations can cause false connections

16.

The high-pressure sensing element shown in Figure 13 is made from what two components?

a)

A float and a stem

b)

A piston and spring

c)

A bulb and capillary

d)

A diaphragm and magnet

17.

A medium-range pressure sensing element is typically made from what?

a)

A large diaphragm

b)

A small piston

c)

Large bellows

d)

A capillary tube

18.

A low-range pressure sensing element is made from a (a)   .

19.

A temperature sensing element is made from what two primary components?

a)

RTD and thermocouple

b)

Piston and spring

c)

Bulb and capillary

d)

Float and magnet

20.

In a temperature sensing switch, an increase in temperature creates pressure in the bulb and capillary, which then acts on what component to activate the switch?

a)

The diaphragm

b)

The bellows

c)

The float

d)

The magnet

21.

What is the primary purpose of an ESD (Emergency Shutdown) system?

a)

To optimize process efficiency

b)

To protect plants and personnel from injury

c)

To log process variable data

d)

To control the final product quality

22.

ESD systems must be automatic because a process can go out of control faster than what can be taken?

a)

A data backup

b)

A product sample

c)

A pressure reading

d)

Corrective action

23.

During an emergency shutdown, control valves will fail into a safe position. What is the correct description of their action?

a)

All valves will close

b)

All valves will open

c)

Valves may open or close depending on their fail-safe design

d)

All valves will go into manual mode

24.

In the GOSP P&ID (Figure 20), which three process variables are monitored for the ESD system?

a)

Flow, Viscosity, and Density

b)

Pressure, Level, and Temperature

c)

pH, Conductivity, and Turbidity

d)

Vibration, Speed, and Torque

25.

The logic circuit in Figure 21 uses an AND gate. This means the plant will shut down if:

a)

Any one of the input signals is missing (goes to OFF)

b)

All of the input signals are missing

c)

At least two input signals are present (ON)

d)

The output signal is manually overridden

26.

In the wiring diagram of Figure 22, relay R7 will only energize if:

a)

At least one of the relays R1 to R6 is energized

b)

The 110 Vac power supply is on

c)

All six relays (R1 to R6) are energized

d)

Switch S1 is closed

27.

If the shipper pump bearing overheats (Figure 22), switch S4 opens, de-energizing relay R4. What is the immediate effect of R4 de-energizing?

a)

Relay R7 de-energizes because contact R4-1 opens

b)

Only the shipper pump stops

c)

An alarm sounds, but the plant continues to run

d)

Relay R3 energizes

28.

During an ESD initiated by the shipper pump, what is the fail-safe action of PCV-3?

a)

It closes to stop the flow to the flare

b)

It opens to vent gas to the flare

c)

It closes to stop the flow to the gas compression plant

d)

It throttles to control flare pressure

29.

In the ladder diagram (Handout 8.2-1), the low-level switches LS1 and LS2 are what type of switches?

a)

Normally Open

b)

Normally Closed

c)

Single Pole, Single Throw

d)

Double Pole, Double Throw

30.

During a 'Start Up or Empty Tank Condition,' which two indicator lights will be ON?

a)

L3 (High Indicator) and L4 (High High Indicator)

b)

L1 (LL Indicator) and L2 (Low Indicator)

c)

L5 (RUN Indicator) and L6 (STOP Indicator)

d)

L1 (LL Indicator) and L5 (RUN Indicator)

31.

During normal level conditions, what is the state of the Master Trip Relay R3?

a)

It is de-energized

b)

It is energized and latched through contact R3-A

c)

It is bypassed by the Trip Reset Switch

d)

It energizes and de-energizes with the level

32.

What happens when the level drops below the LOW LEVEL set point, causing LS2 to close?

a)

The system shuts down immediately

b)

Relay R1 energizes

c)

The Low Indicator light L2 turns ON

d)

The horn sounds

33.

A system shutdown is initiated when the level drops to the LOW-LOW LEVEL set point because:

a)

R1 energizes, causing contact R1-B to open and de-energize R3

b)

L1 turns on, which is wired to the shutdown circuit

c)

LS1 sends a direct signal to the solenoid valve

d)

R2 energizes, causing contact R2-B to open

34.

A system shutdown is initiated when the level rises to the HIGH-HIGH LEVEL set point because:

4 lines
35.

A system shutdown is initiated when the level rises to the HIGH-HIGH LEVEL set point because:

a)

LS4 sends a direct signal to the solenoid valve

b)

L4 turns on, which is wired to the shutdown circuit

c)

R2 energizes, causing contact R2-B to open and de-energize R3

d)

R1 energizes, causing contact R1-B to open

36.

What is the purpose of the "Trip Reset Switch"?

a)

To manually shut down the system in an emergency

b)

To test the indicator lights

c)

To bypass the level switches during maintenance

d)

To reset (re-energize) relay R3 after a fault has been cleared

37.

Activating the Bypass switch BP-1 will energize the solenoid valve, bypassing which two components?

a)

The low-level switches (LS1, LS2)

b)

The high-level switches (LS3, LS4)

c)

The level alarms and the master trip relay

d)

The RUN and STOP indicators

38.

During normal operation, the RUN indicator (L5) is ON. Which relay contact keeps it on?

a)

R1-A (Normally Open)

b)

R2-A (Normally Open)

c)

R3-C (Normally Open)

d)

R3-C (Normally Closed)

39.

The STOP indicator (L6) will be ON when:

a)

The system is running normally

b)

The Master Trip Relay R3 is de-energized

c)

The Bypass switch is activated

d)

The level is in a high alarm state

40.

In the GOSP system (Figure 22), if the HPPT pressure switch (S5) opens, what will happen?

a)

Only the HPPT section will shut down

b)

The entire GOSP system will shut down

c)

Only an alarm will sound

d)

The IPPT will take over the process

41.

What is the fundamental principle of this "fail-safe" ESD system?

a)

It requires two separate signals to shut down

b)

Any open circuit in the input permissive chain will shut the plant down

c)

It can only be shut down manually

d)

It automatically restarts after a trip

42.

What type of device is ZV 010 in Figure 3?

a)

A pressure transmitter

b)

A flow control valve

c)

A solenoid control valve

d)

A temperature switch

43.

In Figure 13, the movement of the piston is controlled by the increase and decrease in what?

a)

Temperature

b)

Level

c)

Pressure

d)

Flow

44.

Which of the following is a key point to remember about ESD systems?

a)

They are manual systems

b)

They must operate before damage is done

c)

They are only for protecting equipment

d)

They are only used during startup

45.

In Figure 20, what is the destination for the crude oil after it leaves the Shipper Pump?

a)

To Refinery

b)

To Flare

c)

To Gas Compression Plant

d)

To IPPT

46.

In Figure 21, the inputs to the AND gate are from what kind of devices?

a)

Transmitters

b)

Controllers

c)

Switches

d)

Indicators

47.

What is the power source for the relays R1 through R6 in Figure 22?

a)

110 Vac

b)

24 Vdc

c)

Instrument Air

d)

A backup battery

48.

In the ladder diagram, which relay is referred to as the "LL Relay"?

a)

R1

b)

R2

c)

R3

d)

R7

49.

Which relay is referred to as the "HH Relay"?

a)

R1

b)

R2

c)

R3

d)

R7

50.

What must happen for the Horn (rung I) to activate?

a)

Relay R3 must be energized

b)

Relay R3 must be de-energized

c)

Relay R1 must be energized

d)

Relay R2 must be energized

51.

The logic where a relay contact (R3-A) is used to keep its own coil (R3) energized is called a:

a)

Bypass circuit

b)

Seal-in or latching circuit

c)

Trip circuit

d)

Alarm circuit

52.

If the level is normal, but indicator L2 (Low Indicator) is ON, what is the most likely cause?

a)

Switch LS2 is stuck closed

b)

Switch LS1 has failed open

c)

Relay R3 has failed

d)

The bulb in L2 has burned out

53.

If the level is normal, but the system is shut down and the STOP light (L6) is on, what component should be checked first?

a)

The solenoid valve

b)

The Master Trip Relay (R3) and its control circuit

c)

The Low Level Switch (LS2)

d)

The High Level Switch (LS3)

54.

What is the function of FCV-1 in the GOSP diagram (Figure 20)?

a)

It controls the level in the HPPT

b)

It controls the flow of crude oil into the HPPT

c)

It controls the gas pressure leaving the HPPT

d)

It is a bypass valve for the shipper pump

55.

The core of a solenoid is also referred to as the:

a)

Spring

b)

Coil

c)

Armature

d)

Stem

56.

If pressure is normal in the circuit from Figure 7, the solenoid valve is energized through which contact of the switch?

a)

The NO (Normally Open) contact

b)

The COM (Common) terminal

c)

The NC (Normally Closed) contact

d)

The RET (Return) line

57.

The level sensing element in Figure A uses a float to operate what type of switch?

a)

Micro-switch

b)

Mercury Switch

c)

Pressure Switch

d)

Temperature Switch

58.

An ESD system is designed to perform a shutdown before what happens?

a)

The shift change occurs

b)

The process variable reaches its setpoint

c)

Damage is done to equipment or personnel

d)

The operator can intervene

59.

In Figure 20, what is the purpose of the "MIN. FLOW BYPASS" line?

a)

To flare excess gas

b)

To protect the pumps during low flow conditions

c)

To send crude oil back to the IPPT

d)

To provide a secondary path to the refinery

60.

In the GOSP wiring diagram (Figure 22), all the relay contacts R1-1 through R6-1 must be ________ for the system to run.

a)

Open

b)

Bypassed

c)

Closed

d)

De-energized

61.

In the ladder diagram, a low-low level trip is considered more critical than a low-level alarm because it:

a)

Only activates an indicator light

b)

Sounds a horn

c)

De-energizes the Master Trip Relay and shuts the system down

d)

Requires a manual reset

62.

What component is located at grid reference C,2 in the ladder diagram (Handout 8.2-1)?

a)

L2 Low Indicator

b)

LS2-Low Level switch

c)

R1-A contact

d)

LS3-High Level switch

63.

If the High-High Level Switch (LS4) fails in a closed position, what will happen?

a)

The system will immediately shut down

b)

The system will operate normally

c)

The High-High indicator L4 will be on continuously

d)

The system cannot be started

64.

Which of the following conditions will NOT cause a shutdown in the ladder diagram system?

a)

Level dropping below the LS1 set point

b)

Level rising above the LS4 set point

c)

The Trip Reset Switch failing in the open position

d)

Level rising above the LS3 set point

65.

The symbol for the solenoid valve in the P&ID (Figure 3) and ladder diagram (Handout 8.2-1) indicates it is a(n):

a)

Electrically actuated device

b)

Pneumatically actuated device

c)

Manually actuated device

d)

Hydraulically actuated device

66.

What is the primary safety function of the MOV ZV valve in Figure 20?

a)

To control the pressure in the HPPT

b)

To stop the flow of crude oil into the plant during an ESD

c)

To regulate the flow to the shipper pump

d)

To bypass the IPPT

67.

If a wire breaks in the circuit for the HPPT Level Switch (S1) in Figure 22, what is the result?

a)

An alarm will sound, but the system continues to run

b)

The system will shut down because R1 will de-energize

c)

The system will ignore the signal from S1

d)

Nothing will happen until the level actually reaches 12 feet

68.

The "Trip Reset Switch" in the ladder diagram is a:

a)

Normally Closed push button

b)

Normally Open push button

c)

Toggle switch

d)

Selector switch

69.

For relay R3 to be initially energized during startup, what two actions are required?

4 lines
70.

be initially energized during startup, what two actions are required?

a)

The level must be normal and the bypass switch must be closed

b)

Contacts R1-B and R2-B must be closed and the Trip Reset button must be pushed

c)

Switches LS1 and LS2 must be open

d)

The horn must be silenced and the RUN button pushed

71.

In the GOSP system, LCV-1 is designed to fail in which position?

a)

Air Open / Air Fails Close (AO/AFC)

b)

Air Close / Air Fails Open (AC/AFO)

c)

Fail in last position

d)

Manual override

72.

What is the set point for the IPPT Pressure Switch in the GOSP ESD system?

a)

120 psi

b)

180 psi

c)

90 psi

d)

12 feet

73.

In the ladder diagram, if relay R2 is energized, what is the status of indicator L4?

a)

It is OFF

b)

It is ON

c)

It is flashing

d)

It depends on the state of R1

74.

The use of a 24 Vdc control circuit (Figure 22) is common in industrial settings because it is:

a)

Higher power than 110 Vac

b)

Less expensive to install

c)

Considered a safer, lower voltage for control logic

d)

The only voltage relays can operate on

75.

If the RUN indicator L5 is ON, what is the state of the solenoid valve?

a)

It is de-energized

b)

It is energized (unless bypassed)

c)

It is closed

d)

It is in manual mode

76.

Which event is considered an "alarm only" and does not directly cause a trip?

a)

A high-high level condition (LS4)

b)

A low-low level condition (LS1)

c)

A low level condition (LS2)

d)

A failure of the Master Trip Relay (R3)

77.

In Figure 20, the Booster Pump and Shipper Pump are configured in:

a)

Parallel

b)

Series

c)

A standby arrangement

d)

A bypass loop

78.

The temperature switches in the GOSP logic (Figure 21) are monitoring the temperature of what?

a)

The crude oil in the HPPT

b)

The gas leaving the IPPT

c)

The bearings in the electric motors

d)

The ambient air temperature

79.

If contact R3-A in the ladder diagram were to fail open, what would be the result?

a)

The system would run normally

b)

The system would shut down and could not be reset

c)

The horn would sound continuously

d)

The bypass switch would not function

80.

The primary function of the IPPT is to:

a)

Receive crude oil directly from the inlet

b)

Separate gas and oil at a lower pressure than the HPPT

c)

Pump crude oil to the refinery

d)

Flare excess gas from the process

81.

In the ladder diagram, the contact R3-C (NC) in rung L serves what purpose?

a)

To turn on the RUN indicator when the system is running

b)

To turn on the STOP indicator when the system is shut down

c)

To energize the solenoid valve

d)

To sound the horn during a trip

82.

A technician finds that relay R1 is energized. This indicates:

a)

A high-high level condition

b)

A normal level condition

c)

A low-low level condition

d)

The system has been manually shut down

83.

In Figure 3, the dashed line around the solenoid valve and its connection to the actuator represents:

a)

An electrical connection

b)

A software or data link

c)

A pneumatic (air) line

d)

A mechanical linkage

84.

During an ESD in the GOSP system, PCV-1 and PCV-2 both close. What is the purpose of this action?

a)

To stop gas from being sent to the flare

b)

To stop feeding the gas compression plant

c)

To increase the pressure in the HPPT and IPPT

d)

To open a bypass around the traps

85.

In the ladder diagram, what would happen if the bulb for the "RUN Indicator" (L5) burned out?

a)

The system would shut down

b)

The solenoid valve would de-energize

c)

The system would continue to run normally, but without the visual indication

d)

The STOP indicator would turn on

86.

The device tagged FCV 010 in Figure 3 is what type of valve?

a)

An on/off motor-operated valve

b)

A pressure control valve

c)

A flow control valve

d)

A level control valve

87.

Why is it necessary for the ESD system to shut off the Booster Pump and Shipper Pump during a trip?

a)

To save electricity

b)

To prevent them from running dry or pumping into a blocked line

c)

To allow them to cool down

d)

To reduce plant noise levels

88.

In the ladder diagram, if the level is between the Low (LS2) and High (LS3) set points, how many indicator lights should be on?

a)

None

b)

One (L5 - RUN)

c)

Two (L5 and L6)

d)

Four (L1, L2, L3, L4)

89.

What is the function of the "PERMISSIVE START UP" logic in Figure 22?

a)

It allows the plant to start even if there is a fault

b)

It ensures all conditions are safe (all switches closed) before allowing the plant to run

c)

It bypasses all alarms during the startup sequence

d)

It is a manual override for the ESD system

90.

If the solenoid valve in the ladder diagram system fails and will not energize, what is the consequence?

a)

The process cannot be shut down

b)

The process cannot be started or run

c)

The level alarms will not function

d)

The system will operate normally

91.

Which component in the ladder diagram acts as the "brain" of the shutdown logic, holding the system in a run state or a trip state?

a)

Relay R1 (LL Relay)

b)

Relay R2 (HH Relay)

c)

Relay R3 (Master Trip Relay)

d)

The Solenoid Valve

92.

The term "actuate" for a switch means to:

a)

Trip and change from its normal state

b)

Return to its normal state after a trip

c)

Fail in its current position

d)

Send a continuous signal

93.

What is the purpose of FCV 4 in Figure 20?

a)

To control crude oil flow into the plant

b)

To control crude oil flow from the shipper pump to the refinery

c)

To bypass the shipper pump

d)

To control flow to the booster pump

94.

The GOSP ESD system uses what voltage for its final shutdown devices like solenoid valves and motor controls?

a)

24 Vdc

b)

12 Vdc

c)

110 Vac

d)

480 Vac

95.

In the ladder diagram, if R1-B and R2-B are both closed, but R3 will not energize when the reset button is pushed, what is a possible cause?

a)

The coil of relay R3 has failed

b)

The level is too high

c)

The level is too low

d)

The horn is disconnected

96.

What is the fail-safe action of FCV 2 in Figure 20?

a)

Air Open / Air Fails Close (AO/AFC)

b)

Air Close / Air Fails Open (AC/AFO)

c)

Fails in last position

d)

Manually closed

97.

If the level is rising, in what order will the switches in the ladder diagram be activated?

a)

LS1, LS2, LS3, LS4

b)

LS2, LS1, LS3, LS4

c)

LS3, LS4

d)

LS2, LS3, LS4

98.

When a process shutdown occurs in the GOSP, the MOV ZV valve is closed by what?

a)

An electric motor

b)

Instrument air pressure

c)

A large spring

d)

A manual handwheel

99.

The contact R2-A in the ladder diagram is a:

a)

Normally Closed contact from relay R2

b)

Normally Open contact from relay R2

c)

Normally Closed contact from relay R3

d)

Normally Open contact from relay R1

100.

The overall purpose of the complex relay logic in Figure 22 is to implement a simple:

a)

OR function

b)

NOT function

c)

XOR function

d)

AND function

101.

During a shutdown in the ladder diagram system, contact R3-C (NO) in rung J opens, which de-energizes what final control element?

a)

The Horn

b)

The RUN indicator

c)

The Solenoid Valve

d)

The STOP indicator

102.

For plant safety, where is the gas from PCV 3 routed during an emergency?

a)

Back to the IPPT

b)

To the Gas Compression Plant

c)

To the Flare

d)

To the Refinery